› List of Variances for Cruise Ship
List of Variances for Cruise Ship
Variances by:
Section
|
Cruise Ships
Cruise Ship:
Grande Caribe
Cruise Line:
American Canadian Caribbean Line, Inc.
VSP Operations Manual Section:
5.7.1.1.3
Manual Requirement:
The vessel shall provide a comprehensive cross- connection control program that provides safe connections to the potable water system through air gaps or appropriate backflow devices at the following locations, if present: (1) Potable water supply lines to swimming pools, whirlpool spas, hot tubs, bathtubs, showers, and similar facilities; (2) Photographic laboratory developing machines and utility sinks; (3) Beauty and barber shop spray-rinse hoses; (4) Potable water faucets where hoses are connected or can be connected by threaded or quick-connect outlets such as those serving tanks containing chlorine and other chemicals, and deck taps; (5) Garbage grinders and pulpers; (6) Mechanical warewashing machines; (7) Hospital and laundry equipment; (8) Air conditioning expansion tanks; (9) Boiler feed water tanks; (10) Fire systems; (11) Toilets; (12) Potable water, bilge, and sanitary pumps that require priming; (13) Freshwater or saltwater ballast systems; (14) Bilge or other waste water locations; (15) International shore connection; and (16) Any other connection between potable and non-potable water systems.
Request:
Variance to not have a backflow prevention device on the international shore connection.
Status:
Denied
Summary:
This backflow prevention device protects the shore-side water source in case of shipboard pressure of non-potable water for fire-fighting is greater than that coming from the shore-side water source.
VSP Operations Manual Section:
5.4.1.2.3
Manual Requirement:
Ensure that at least one backup halogen pump is available with automatic switchover to maintain the free residual halogen in the event that the primary pump fails.
Request:
Variance to not have automatic switchover for backup halogenation pumps on the distribution system.
Status:
Denied
Summary:
Variance to not have automatic switchover for backup halogenation pumps on the distribution system.