NIOSH Fire Fighter Fatality Investigation and Prevention Program

 

Propane Tank Explosion Results in the Death of Two Volunteer Fire Fighters, Hospitalization of Six Other Volunteer Fire Fighters and a Deputy Sheriff - Iowa

 
SUMMARY

On April 9, 1998, 20 fire fighters from a volunteer fire department responded to a propane tank fire located at a turkey farm about 2.5 miles from the fire department. Upon arrival at the fire scene a decision was made to water down the buildings adjacent to the propane tank and allow the tank to burn itself out since the tank was venting. Some of the fire fighters positioned themselves between the burning propane tank and the turkey sheds and were watering down the buildings as the remaining fire fighters performed other tasks, e.g., pulling hose and operating pumps.

About 8 minutes after the fire fighters arrived on scene, the tank exploded. When the tank exploded it separated into four parts and traveled in four different directions. Two fire fighters about 105 feet from the tank were struck by one piece of the exploding tank and killed instantly. Six other fire fighters and a deputy sheriff, who had arrived on scene just before the explosion, were also injured.

NIOSH investigators concluded that, to prevent similar incidents, fire departments should:

  • follow guidelines as outlined in published literature and guidebooks for controlling fire involving tanks containing propane
  • adhere to emergency response procedures contained in 29 CFR 1910.120(q) - Emergency response to hazardous substance release procedures
  • educate fire fighters to the many dangers associated with a propane tank explosion, which is also known as a Boiling Liquid Expanding Vapor Explosion (BLEVE).

 

Additionally, owners and users of propane tanks should:

 

18,000-gallon propane tank with protective fencing (similar to tank which exploded).

Figure 1. 18,000-gallon propane tank with protective fencing

(similar to tank which exploded).

 

The Fire Fighter Fatality Investigation and Prevention Program is conducted by the National Institute for Occupational Safety and Health (NIOSH). The purpose of the program is to determine factors that cause or contribute to fire fighter deaths suffered in the line of duty. Identification of causal and contributing factors enable researchers and safety specialists to develop strategies for preventing future similar incidents. To request additional copies of this report (specify the case number shown in the shield above), other fatality investigation reports, or further information, visit the Program Website at:

http://www.cdc.gov/niosh/firehome.html

or call toll free 1-800-35-NIOSH.

 

INTRODUCTION

On April 9, 1998, two male volunteer fire fighters aged 45 and 46 years old (the victims), were killed when an 18,000-gallon propane tank exploded. Additionally, six other volunteer fire fighters and a deputy sheriff were seriously injured. The fire fighters were part of a volunteer fire company that arrived on the fire scene about 2320 hours. The fire fighters were watering down buildings adjacent to the tank when it exploded at 2328 hours. The two victims were killed instantly by a flying tank part, and six other fire fighters and a deputy sheriff received varying injuries including burns and fractures.

On April 10, 1998, the United States Fire Administration notified NIOSH of the deaths. On April 15, 1998, two Safety and Occupational Health Specialists, Richard Braddee and Frank Washenitz, traveled to Iowa to conduct an investigation of this incident. Meetings were held with the Iowa State Fire Marshal, the 1st and 2nd assistant chiefs of the fire department involved in the incident, the State OSHA inspectors, representatives from the U.S. Chemical Safety and Hazard Investigation Board, and the local police department. Copies of photographs and measurements of the incident site were obtained along with the medical examiner and police department reports, and a site visit was conducted.

The volunteer fire department involved in the incident serves a population of 850 in a geographic area of 100 square miles, and is comprised of approximately 25 volunteer fire fighters. The fire department provides all new fire fighters with 24 hours of mandatory training. The training is designed to cover personal safety, forcible entry, ventilation, fire apparatus, ladders, self-contained breathing apparatus, hose loads, streams, and special hazards. The victims had 15 and 16 years fire of fighting experience, respectively.

 

INVESTIGATION

On April 9, 1998, at 2311 hours, a call came into the fire department regarding a turkey barn fire at a turkey farm about 2.5 miles from the department. The Chief in the command car #1190, and 19 fire fighters in Pumpers #1193 and #1194, Tanker #1195, Emergency Van #1196, and two private vehicles were dispatched to the scene. En route to the scene the Chief advised the command center that the fire involved a large propane tank and not a turkey barn. All the fire fighters arrived on the fire scene between 2314 and 2317 hours. At about 2305 hours two people riding a 4-wheel, off-road vehicle struck one of the two fixed metal pipes between the propane tank and the two vaporizers (a device other than a container that receives LP-Gas [Liquefied Petroleum-Gas] in liquid form and adds sufficient heat to convert the liquid to a gaseous state), breaking one pipe off completely. As the liquid propane spewed from the pipe the operator of the 4-wheel, off-road vehicle drove away to call 911. The propane vapors, which have a vapor density of 1.53 and are thus 1½ times heavier than air, spread along the ground and were eventually ignited by the pilot flame at the vaporizers. Burning propane vapors spread throughout the area and began to impinge on the tank, causing the pressure relief valve to activate and send burning propane flames high into the air.

Upon arrival at the fire scene an assessment by the Chief was made of the burning tank. Fire had engulfed the propane tank and it was venting burning propane vapors via two pressure relief vent pipes located on top of the tank. Also, an extremely loud noise similar to a jet engine was being emitted by the tank’s pressure relief vent pipes. The tank was manufactured in 1964 and the tank’s shell was constructed of 3/4-inch carbon steel. The tank was 42 feet, 2 inches long, with an inside diameter of 106 inches and an 18,000 - gallon capacity, and it rested on two concrete supports/saddles. The tank was cylindrical and contained about 10,000 gallons of liquid propane. The tank had been fitted with two internal spring-type pressure relief valves which would vent to the atmosphere via two 2-inch-diameter pressure relief vent pipes when the internal tank pressure reached a set limit. The tank also had a fixed metal piping system between the tank and two vaporizers located on the ground about 35 feet away. The piping was 3/4-inches in diameter, positioned about 36 inches above the ground, was unprotected and had not been fitted with an excess flow valve.

After seeing the flames and hearing the high-pitched shrill being emitted by pressure relief vent pipes located on the top west section of the tank, a decision was made to allow the tank to burn itself out and to try to save the adjacent buildings by watering them down. The fire fighters positioned themselves in various areas in a semicircle north, northeast and northwest of the tank (see Figure). The two victims, whose location was about 105 feet away from the tank and on the northwest side of a building used to house turkeys, began to water down the building. At 2328 a Boiling Liquid Expanding Vapor Explosion (BLEVE) occurred. The BLEVE ripped the tank into four parts, each flying in a different direction. One part of the tank traveled in a northwest direction toward the two victims, striking them and killing them instantly. Six other fire fighters and a deputy sheriff received varying degrees of burns and assorted injuries.

 

CAUSE OF DEATH

The cause of death was listed by the medical examiner as massive trauma to all systems.

 

RECOMMENDATIONS/DISCUSSION

Recommendation #1: Fire departments should follow guidelines as outlined in published literature and guidebooks for controlling fire involving tanks containing propane.

Discussion: Information contained in the North American Emergency Response Guidebook (NAERG),1 the National Propane Gas Association (NPGA),4 the International Fire Service Training Association (IFSTA),5 and the National Fire Protection Association (NFPA),6 contain guidelines for controlling Fire Involving Tanks, LP-Gas Fire Control, Suppressing Class "B" Fires, and Recommended Practice for Responding to Hazardous Materials Incidents, respectively. As these guidelines are comprehensive and expansive, they are not reflected here in their entirety. An example of the NAERG guidelines for controlling fire involving propane tanks include, but are not limited to the following: (1) fight fire from maximum distance or use unmanned hose holders or monitor nozzles, (2) cool containers with flooding quantities of water until well after fire is out, (3) do not direct water at source of leak or safety devices; icing may occur, (4) withdraw immediately in case of rising sound from venting safety devices or discoloration of tank, (5) always stay away from the ends of tanks, and (6) for massive fire, use unmanned hose holders or monitor nozzles; if this is impossible, withdraw from area and let fire burn. For additional information see REFERENCE section at the end of this report.

 

Recommendation #2: Emergency response personnel should adhere to the procedures outlined in 29 CFR 1910.120(q)2 - Emergency response to hazardous substance releases.

Discussion: 29 CFR 1910.120(q) contains procedures for dealing with emergency responses. These procedures include: (1) Emergency response plan, (2) Elements of an emergency response plan, (3) Procedures for handling emergency response, (4) Skilled support personnel, (5) Specialist employees, (6) Training, (7) Trainers, (8) Refresher training, (9) Medical surveillance and consultation, (10) Chemical protective clothing, and (11) Post-emergency response operations.

 

Recommendation # 3: All fire fighters should be educated to the many dangers associated with a BLEVE.

Discussion: Dangers associated with a BLEVE include, but are not limited to the following: (1) the fire ball can engulf and burn fire fighters operating near a burning tank when a BLEVE occurs, (2) metal parts of the tank can travel hundreds of feet and strike and critically injure fire fighters after a BLEVE, (3) a trail of burning liquid propane can douse and burn fire fighters, and (4) the shock wave, air blast, or flying metal tank parts created by a BLEVE can collapse buildings onto fire fighters or blow fire fighters out of windows or off roofs.3

Additionally, owners and users of propane tanks should:

 

Recommendation #4: Ensure that aboveground external piping is protected against physical damage via fencing or some other means of protection.

Discussion: Unprotected aboveground piping is subject to damage from a variety of sources (e.g., machinery, vehicles, people, animals, etc.). NFPA 58 (Standard for Storage and Handling of Liquefied Petroleum Gases) 3-2.8.77 states "Aboveground piping shall be supported and protected against physical damage." Property or tank owners should ensure that bulk propane tank piping is protected against damage by fencing or some other means to prevent accidental contact and physical damage.

 

Recommendation #5: Equip propane tank piping with excess-flow valves and/or emergency shutoff valves, where applicable.

Discussion: NFPA 58 (Standard for Storage and Handling of Liquefied Petroleum Gases) 3-4.10(c)8 states "Excess-flow valves complying with 2-3.3.3(b) shall be installed in the container outlet supply line, downstream of each shutoff valve, and at any point in the piping system where the pipe size is reduced. An excess-flow valve is a device that can be installed into piping and is designed to close when the liquid or vapor passing through it exceeds a prescribed flow rate as determined by pressure drop. Also, an emergency shutoff valve is a shutoff valve installed in the piping system that incorporates thermal and manual means of closing that also provides for a remote means of closing. In this instance, an excess-flow valve or emergency shutoff valve may have prevented an excess of liquid propane from spilling, and thus, prevented the initial ignition of the propane.

 

REFERENCES

1. U.S. Department of Transportation, Transport Canada, and the Secretariat of Communications and Transportation of Mexico [1996]. North American Emergency Response Guidebook. Washington, DC: U.S. Department of Transportation, Research and Special Programs Administration, Office of Hazardous Materials Initiatives and Training. p. 179. Internet: welisten@rspa.dot.gov

2. 29 CFR Part 1910.120, Code of Federal Regulations, Washington, D.C.: U.S. Government Printing Office, Office of the Federal Register.

3. Dunn V [1982]. Safety and Survival on the Fireground. Tulsa, OK: Penn Well, pp 151-155.

4. National Propane Gas Association [1992]. LP-Gas Fire Control and Hazmat Training Guide. Lisle, IL.: National Propane Gas Association Safety Bulletin No. 211.

5. International Fire Service Training Association [1992]. Essentials of Fire Fighting, 3rd ed. Stillwater, OK: Oklahoma State University.

6. National Fire Protection Association 471, 1997 Edition, Recommended Practice for Responding to Hazardous Materials Incidents, Quincy, MA.

7. National Fire Protection Association 58 3-2.8.7, 1997 Edition, Standard for Storage and Handling of Liquefied Petroleum Gases, Quincy, MA.

8. National Fire Protection Association 58 3-4.10(b), 1997 Edition, Standard for Storage and Handling of Liquefied Petroleum Gases, Quincy, MA.

 

Aerial View of Incident Scene

Figure 2. Aerial View of Incident Scene.

Key:

P — Position of propane tank

1 & 2 — Position of victims

F — Position of other fire fighters

A — Position of apparatus.