Cruise Ship Inspection Details

  Basic Search |  Advanced Search |  Ship Scored 100 |  Green Sheet
 
Cruise Ship: Norwegian Dawn Cruise line: Norwegian Cruise Lines Inspection Date: 09/19/2008 Score: 98
 
This cruise ship inspection report lists the deficiencies found during the inspection. Additional information corresponding to each item number is available in the lastest editions of the CDC VSP Operational Manual.



 
Cruise Ship's Corrective Action Statement  |  View/Print Summary Report  |  View/Print Detail Report
 
 
Note: Click on the Item no. to view the item detail.
 
Item No.DescriptionPoints Deducted
08PW filling hoses, caps, connections, procedures; Sample records, valves; PW system constructed, maintained0
17Temperature practices storage, preparation display, service, transportation; Thawing0
19Food protected storage, preparation, display, service, transportation; Original containers, labeling; Food handling minimized; In-use food dispensing, preparation utensils stored2
20PHF temperature maintenance facilities; Food-contact surfaces designed, constructed, installed, maintained; TMD=s provided, located, calibrated0
22Dishwashing / equipment washing facilities designed, constructed, maintained, installed, located, operated, TMDs, test kits0
33Decks / bulkheads / deckheads construction, repair, clean0
34Plumbing fixtures / supply lines / drain lines / drains installed, repair0
37Rooms / equipment vented, humidity, condensation0
38Unnecessary articles, cleaning equipment; Unauthorized personnel0
999Miscellaneous0
Selected Item Details
Item No.: 08
Site: Potable Water-Cross-Connection Control Program
Violation: The cross-connection control program listed one backflow prevention device for the hair salon area. The salon was protected by two backflow prevention devices: one for the potable hot water line and one for the potable cold water line.
Recommendation:Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
Site: Potable Water-Cross-Connection Control Program
Violation: The potable water connection for the steam generator in the spa area was not listed in the cross-connection control program. This connection had an appropriate backflow prevention device installed.
Recommendation:Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.