Cruise Ship: Norwegian Pearl Cruise line: Norwegian Cruise Lines Inspection Date: 12/07/2008 Score: 100
 
This cruise ship inspection report lists the deficiencies found during the inspection. Additional information corresponding to each item number is available in the lastest editions of the CDC VSP Operational Manual.



 
Cruise Ship's Corrective Action Statement  |  View/Print Summary Report  |  View/Print Detail Report
 
 
Note: Click on the Item no. to view the item detail.
 
Item No.DescriptionPoints Deducted
08PW filling hoses, caps, connections, procedures; Sample records, valves; PW system constructed, maintained0
10Swimming pools / spas maintained, safety equipment0
15Food source, sound condition; food not re-served0
16Potentially hazardous food temperatures storage, preparation display, service, transportation0
19Food protected storage, preparation, display, service, transportation; Original containers, labeling; Food handling minimized; In-use food dispensing, preparation utensils stored0
21Nonfood-contact surfaces designed, constructed, maintained, installed, located0
22Dishwashing / equipment washing facilities designed, constructed, maintained, installed, located, operated, TMDs, test kits0
27Equipment / utensils non-food-contact surfaces clean0
28Equipment / utensil / linen / single / service storage, handling, dispensed; Clean frequency0
29Facilities convenient, accessible, designed, installed0
30Hand cleanser, sanitary towels, waste receptacles, handwash signs; maintenance0
33Decks / bulkheads / deckheads construction, repair, clean0
34Plumbing fixtures / supply lines / drain lines / drains installed, repair0
36Lighting provided, shielded0
40IPM procedures developed; followed; outer openings protected0
41Child Activity Centers facilities, diaper changing, operation0
Selected Item Details
Item No.: 08
Site: Potable Water-
Violation: An air-gap was not provided at the fill for the passenger pool 1 expansion tank.
Recommendation:Provide an air gap at this location.
Site: Potable Water-
Violation: The potable water lines supplying the spa showers and toilets were not listed in the cross-connection control program.
Recommendation:Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
Site: Potable Water-
Violation: The potable water tank maintenance records did not consistently show that the free chlorine level was less than 5.0 ppm prior to putting the tanks back into service after disinfection.
Recommendation:Ensure that the disinfected parts of the system are flushed with potable water until the free residual halogen is at or below 5.00 mg/L (ppm).
*Inspections scores of 85 or lower are NOT satisfactory