Cruise Ship Inspection Details

  Basic Search |  Advanced Search |  Ship Scored 100 |  Green Sheet
 
Cruise Ship: The World Cruise line: Residensea Inspection Date: 02/24/2004 Score: 92
 
This cruise ship inspection report lists the deficiencies found during the inspection. Additional information corresponding to each item number is available in the lastest editions of the CDC VSP Operational Manual.



 
Cruise Ship's Corrective Action Statement  |  View/Print Summary Report  |  View/Print Detail Report
 
 
Note: Click on the Item no. to view the item detail.
 
Item No.DescriptionPoints Deducted
05PW system halogen analyzer maintained, operated, calibrated5
06Halogen analyzer chart recorder maintained, operated, records; Sampling, records0
07PW system protection cross-connections, backflow; Disinfection0
08PW filling hoses, caps, connections, procedures; Sample records, valves; PW system constructed, maintained0
09Swimming pools / spas halogen residuals3
20PHF temperature maintenance facilities; Food-contact surfaces designed, constructed, installed, maintained; TMD=s provided, located, calibrated0
22Dishwashing / equipment washing facilities designed, constructed, maintained, installed, located, operated, TMDs, test kits0
27Equipment / utensils non-food-contact surfaces clean0
29Facilities convenient, accessible, designed, installed0
37Rooms / equipment vented, humidity, condensation0
41Child Activity Centers facilities, diaper changing, operation0
999Miscellaneous0
Selected Item Details
Item No.: 05
Site: Other-POTABLE WATER
Violation: THE FAR POINT ANALYZER CHART-RECORDER NOTED 2.14 WHILE A MANUAL TEST NOTED 0.99. A SECOND TEST NOTED 1.00 PPM WHILE THE ANALYZER CHART-RECORDER NOTED 2.21 PPM. THE ENGINEER'S TESTS NOTED 2.11 PPM AND 2.17 PPM, RESPECTIVELY. AS PER TECHNICAL SUPPORT AT HACH THE ENGINEER'S TEST KIT WAS NOT USED PROPERLY AND THE TEST SAMPLE SHOULD HAVE BEEN DILUTED IN ACCORDANCE WITH THE TEST KIT'S MANUAL INSTRUCTIONS.
Recommendation:5.5.1.2.3 The free residual halogen measured by the halogen analyzer shall be ±0.2 mg/L (ppm) of the free residual halogen measured by the manual test. Ensure that the test kit is used in accordance with the manufacturer's instructions.
*Inspections scores of 85 or lower are NOT satisfactory