Item No. | Description | Points Deducted |
03 | PW bunker / production source; Halogen residual | 0 |
06 | Halogen analyzer chart recorder maintained, operated, records; Sampling, records | 0 |
08 | PW filling hoses, caps, connections, procedures; Sample records, valves; PW system constructed, maintained | 0 |
10 | Swimming pools / spas maintained, safety equipment | 0 |
16 | Potentially hazardous food temperatures storage, preparation display, service, transportation | 0 |
20 | PHF temperature maintenance facilities; Food-contact surfaces designed, constructed, installed, maintained; TMD=s provided, located, calibrated | 0 |
21 | Nonfood-contact surfaces designed, constructed, maintained, installed, located | 1 |
22 | Dishwashing / equipment washing facilities designed, constructed, maintained, installed, located, operated, TMDs, test kits | 0 |
26 | Food-contact surfaces equipment / utensils clean; Safe | 0 |
27 | Equipment / utensils non-food-contact surfaces clean | 1 |
30 | Hand cleanser, sanitary towels, waste receptacles, handwash signs; maintenance | 0 |
33 | Decks / bulkheads / deckheads construction, repair, clean | 0 |
34 | Plumbing fixtures / supply lines / drain lines / drains installed, repair | 0 |
38 | Unnecessary articles, cleaning equipment; Unauthorized personnel | 0 |
999 | Miscellaneous | 0 |
|
Selected Item Details
|
Item No.:
03
|
|
Site:
Other-POTABLE WATER |
Violation:
THERE WERE FOUR PRODUCTION RECORD ANALYSIS CHARTS (DATED: 12/23, 12/24, 12/27, 12/28/2002) WHERE IT COULD NOT BE DETERMINED IF THE CHLORINE RESIDUAL WAS AT LEAST 2 PPM. FIVE PRODUCTION RECORD ANALYSIS CHARTS NOTED FREE CHLORINE RESIDUAL LEVELS BELOW 2 PPM (DATED: 10/31/02, 11/1, 11/5, 11/7 AND 11/13/2002). |
Recommendation:5.2.1.1.1
Potable water shall be continuously halogenated to at least 2.0 mg/L (ppm) free residual halogen at the time of bunkering or production with an automatic halogenation device. |
|
|