Cruise Ship Inspection Details

  Basic Search |  Advanced Search |  Ship Scored 100 |  Green Sheet
 
Cruise Ship: Star Princess Cruise line: Princess Cruises Inspection Date: 11/20/2008 Score: 99
 
This cruise ship inspection report lists the deficiencies found during the inspection. Additional information corresponding to each item number is available in the lastest editions of the CDC VSP Operational Manual.



 
Cruise Ship's Corrective Action Statement  |  View/Print Summary Report  |  View/Print Detail Report
 
 
Note: Click on the Item no. to view the item detail.
 
Item No.DescriptionPoints Deducted
08PW filling hoses, caps, connections, procedures; Sample records, valves; PW system constructed, maintained0
10Swimming pools / spas maintained, safety equipment0
16Potentially hazardous food temperatures storage, preparation display, service, transportation0
17Temperature practices storage, preparation display, service, transportation; Thawing0
20PHF temperature maintenance facilities; Food-contact surfaces designed, constructed, installed, maintained; TMD=s provided, located, calibrated0
22Dishwashing / equipment washing facilities designed, constructed, maintained, installed, located, operated, TMDs, test kits0
27Equipment / utensils non-food-contact surfaces clean0
29Facilities convenient, accessible, designed, installed0
30Hand cleanser, sanitary towels, waste receptacles, handwash signs; maintenance0
33Decks / bulkheads / deckheads construction, repair, clean1
36Lighting provided, shielded0
37Rooms / equipment vented, humidity, condensation0
38Unnecessary articles, cleaning equipment; Unauthorized personnel0
41Child Activity Centers facilities, diaper changing, operation0
Selected Item Details
Item No.: 08
Site: Whirlpool/Spa-Spa Whirlpool Technical Room
Violation: The water was leaking continuously from the relief vent on the reduced pressure backflow prevention device on the cold water line.
Recommendation:Repair or replace the backflow prevention device.
Site: Potable Water-Port Bunker Station Hose Lockers
Violation: The "potable water only" labels on two of the hoses were faded and difficult to read.
Recommendation:Ensure that potable water hoses are labeled for use with the words "potable water only" in letters at least 13mm (0.5 inch) at each connecting end.
*Inspections scores of 85 or lower are NOT satisfactory