Cruise Ship Inspection Details

  Basic Search |  Advanced Search |  Ship Scored 100 |  Green Sheet
 
Cruise Ship: Regatta Cruise line: Oceania Cruises Inspection Date: 02/25/2008 Score: 100
 
This cruise ship inspection report lists the deficiencies found during the inspection. Additional information corresponding to each item number is available in the lastest editions of the CDC VSP Operational Manual.



 
Cruise Ship's Corrective Action Statement  |  View/Print Summary Report  |  View/Print Detail Report
 
 
Note: Click on the Item no. to view the item detail.
 
Item No.DescriptionPoints Deducted
08PW filling hoses, caps, connections, procedures; Sample records, valves; PW system constructed, maintained0
10Swimming pools / spas maintained, safety equipment0
16Potentially hazardous food temperatures storage, preparation display, service, transportation0
20PHF temperature maintenance facilities; Food-contact surfaces designed, constructed, installed, maintained; TMD=s provided, located, calibrated0
26Food-contact surfaces equipment / utensils clean; Safe0
33Decks / bulkheads / deckheads construction, repair, clean0
34Plumbing fixtures / supply lines / drain lines / drains installed, repair0
Selected Item Details
Item No.: 08
Site: Potable Water-Cross-connection Control Program
Violation: The cross-connection control program did not list the backflow prevention devices for the dishwash machines, coffee machines, juice machines, chemical dispensers and engine room laundry machines.
Recommendation:Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
Site: Potable Water-Whirlpool Pump Room
Violation: The potable water lines were painted white and blue. On this vessel, these colors were used for recirculated water.
Recommendation:Ensure that potable water piping and fittings are painted or striped auxiliary blue, or in accordance with ISO 14726, at 5 m (15 feet) intervals on each side of partitions, decks, and bulkheads in all spaces, except where the decor would be marred by such markings.
Site: Buffet-Crew Mess
Violation: There were no backflow prevention devices on the potable water lines supplying the coffee and juice machines.
Recommendation:Ensure that a continuous pressure-type backflow preventer is installed when a valve is located downstream from the backflow preventer.