Cruise Ship Inspection Details

  Basic Search |  Advanced Search |  Ship Scored 100 |  Green Sheet
 
Cruise Ship: MV Explorer Cruise line: V. Ships Leisure USA Inspection Date: 01/08/2007 Score: 99
 
This cruise ship inspection report lists the deficiencies found during the inspection. Additional information corresponding to each item number is available in the lastest editions of the CDC VSP Operational Manual.



 
Cruise Ship's Corrective Action Statement  |  View/Print Summary Report  |  View/Print Detail Report
 
 
Note: Click on the Item no. to view the item detail.
 
Item No.DescriptionPoints Deducted
08PW filling hoses, caps, connections, procedures; Sample records, valves; PW system constructed, maintained0
11Food handlers infections, communicable diseases0
33Decks / bulkheads / deckheads construction, repair, clean1
Selected Item Details
Item No.: 08
Site: Potable Water-Engine Room
Violation: The potable water line before the window washing backflow prevention device was not striped blue at 5 meter intervals.
Recommendation:Ensure that potable water piping and fittings are painted or stripped auxiliary blue, or in accordance with ISO 14726, at 5 m (15 feet) intervals on each side of partitions, decks, and bulkheads in all spaces, except where the decor would be marred by such markings.
Site: Potable Water-Spa
Violation: The backflow prevention device on the Vinchy Shower and the air gaps on the EcoLab dispensers were not listed on the comprehensive listing of backflow prevention devices.
Recommendation:Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
Site: Potable Water-
Violation: The listing of backflow prevention devices in AMOS did not list both the toilet and shower backflow prevention devices in the crew and passenger cabins.
Recommendation:Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
*Inspections scores of 85 or lower are NOT satisfactory