Cruise Ship Inspection Details

  Basic Search |  Advanced Search |  Ship Scored 100 |  Green Sheet
 
Cruise Ship: The World Cruise line: Residensea Inspection Date: 11/12/2008 Score: 100
 
This cruise ship inspection report lists the deficiencies found during the inspection. Additional information corresponding to each item number is available in the lastest editions of the CDC VSP Operational Manual.



 
Cruise Ship's Corrective Action Statement  |  View/Print Summary Report  |  View/Print Detail Report
 
 
Note: Click on the Item no. to view the item detail.
 
Item No.DescriptionPoints Deducted
08PW filling hoses, caps, connections, procedures; Sample records, valves; PW system constructed, maintained0
10Swimming pools / spas maintained, safety equipment0
21Nonfood-contact surfaces designed, constructed, maintained, installed, located0
22Dishwashing / equipment washing facilities designed, constructed, maintained, installed, located, operated, TMDs, test kits0
36Lighting provided, shielded0
41Child Activity Centers facilities, diaper changing, operation0
Selected Item Details
Item No.: 08
Site: Potable Water-Deck 11 Galley
Violation: There was a constant drip at the intermediate vent of the reduced pressure zone backflow preventer for the hood cleaning system.
Recommendation:Ensure that backflow preventers are maintained in good repair.
Site: Potable Water-Cross-Connection Control Program
Violation: The backflow prevention devices for the coffee machines were not listed on the program. According to staff, the list is in the process of being updated.
Recommendation:Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
Site: Potable Water-Minerlizer Backwash
Violation: The air gap for the mineralizer backwash drainage could not be located during the inspection.
Recommendation:Ensure that backflow prevention devices/methods are located so they may be inspected, serviced, and maintained.
*Inspections scores of 85 or lower are NOT satisfactory