Item No. | Description | Points Deducted |
08 | PW filling hoses, caps, connections, procedures; Sample records, valves; PW system constructed, maintained | 0 |
10 | Swimming pools / spas maintained, safety equipment | 0 |
20 | PHF temperature maintenance facilities; Food-contact surfaces designed, constructed, installed, maintained; TMD=s provided, located, calibrated | 0 |
21 | Nonfood-contact surfaces designed, constructed, maintained, installed, located | 0 |
26 | Food-contact surfaces equipment / utensils clean; Safe | 0 |
27 | Equipment / utensils non-food-contact surfaces clean | 0 |
33 | Decks / bulkheads / deckheads construction, repair, clean | 0 |
|
Selected Item Details
|
Item No.:
08
|
|
Site:
Potable Water-Cross-Connection Control Program |
Violation:
The listing of cross connections did not include the air gaps for the mineralizer, water softener, or evaporator drains. |
Recommendation:Ensure that air-gaps are included in the cross-connection control program listing. |
|
Site:
Potable Water-Cross-Connection Control Program |
Violation:
The cross-connection listing for the passenger and crew showers/toilets did not list the type of backflow prevention device/method used. |
Recommendation:Ensure that the cross-connection control program listing includes the backflow prevention method/device for each (non-continuous pressure type, continuous pressure type, atmospheric vacuum breaker, etc.), so that there is a match to the plumbing system component and location. |
|
|