Item No. | Description | Points Deducted |
06 | Halogen analyzer chart recorder maintained, operated, records; Sampling, records | 0 |
08 | PW filling hoses, caps, connections, procedures; Sample records, valves; PW system constructed, maintained | 0 |
10 | Swimming pools / spas maintained, safety equipment | 0 |
16 | Potentially hazardous food temperatures storage, preparation display, service, transportation | 0 |
19 | Food protected storage, preparation, display, service, transportation; Original containers, labeling; Food handling minimized; In-use food dispensing, preparation utensils stored | 0 |
21 | Nonfood-contact surfaces designed, constructed, maintained, installed, located | 0 |
22 | Dishwashing / equipment washing facilities designed, constructed, maintained, installed, located, operated, TMDs, test kits | 0 |
24 | Sanitizing rinse temperature, concentration, time | 0 |
26 | Food-contact surfaces equipment / utensils clean; Safe | 0 |
28 | Equipment / utensil / linen / single / service storage, handling, dispensed; Clean frequency | 0 |
33 | Decks / bulkheads / deckheads construction, repair, clean | 0 |
37 | Rooms / equipment vented, humidity, condensation | 0 |
41 | Child Activity Centers facilities, diaper changing, operation | 0 |
|
Selected Item Details
|
Item No.:
06
|
|
Site:
Potable Water-Upper & Lower Loop Far Point |
Violation:
The two far point halogen analyzers were incorrectly calibrated. The staff was using the high range sample cell to read in the low range setting. This was causing an inaccurate reading. The halogen readings when checked with the inspectors instrument were within the acceptable range. |
Recommendation:Ensure staff is knowledgeable in using calibration equipment. |
|
Site:
Potable Water-Upper & Lower Loop Far Point |
Violation:
The two far point halogen analyzers were incorrectly calibrated. The staff was using the high range sample cell to read in the low range setting. This was causing an inaccurate reading. The halogen readings when checked with the inspectors instrument were within the acceptable range. |
Recommendation:Ensure the manual comparison test is conducted correctly. |
|
|