Item No. | Description | Points Deducted |
08 | PW filling hoses, caps, connections, procedures; Sample records, valves; PW system constructed, maintained | 0 |
10 | Swimming pools / spas maintained, safety equipment | 0 |
15 | Food source, sound condition; food not re-served | 0 |
16 | Potentially hazardous food temperatures storage, preparation display, service, transportation | 0 |
19 | Food protected storage, preparation, display, service, transportation; Original containers, labeling; Food handling minimized; In-use food dispensing, preparation utensils stored | 0 |
21 | Nonfood-contact surfaces designed, constructed, maintained, installed, located | 0 |
22 | Dishwashing / equipment washing facilities designed, constructed, maintained, installed, located, operated, TMDs, test kits | 0 |
27 | Equipment / utensils non-food-contact surfaces clean | 0 |
28 | Equipment / utensil / linen / single / service storage, handling, dispensed; Clean frequency | 0 |
29 | Facilities convenient, accessible, designed, installed | 0 |
30 | Hand cleanser, sanitary towels, waste receptacles, handwash signs; maintenance | 0 |
33 | Decks / bulkheads / deckheads construction, repair, clean | 0 |
34 | Plumbing fixtures / supply lines / drain lines / drains installed, repair | 0 |
36 | Lighting provided, shielded | 0 |
40 | IPM procedures developed; followed; outer openings protected | 0 |
41 | Child Activity Centers facilities, diaper changing, operation | 0 |
|
Selected Item Details
|
Item No.:
08
|
|
Site:
Potable Water- |
Violation:
An air-gap was not provided at the fill for the passenger pool 1 expansion tank. |
Recommendation:Provide an air gap at this location. |
|
Site:
Potable Water- |
Violation:
The potable water lines supplying the spa showers and toilets were not listed in the cross-connection control program. |
Recommendation:Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing. |
|
Site:
Potable Water- |
Violation:
The potable water tank maintenance records did not consistently show that the free chlorine level was less than 5.0 ppm prior to putting the tanks back into service after disinfection. |
Recommendation:Ensure that the disinfected parts of the system are flushed with potable water until the free residual halogen is at or below 5.00 mg/L (ppm). |
|
|