Item No. | Description | Points Deducted |
06 | Halogen analyzer chart recorder maintained, operated, records; Sampling, records | 0 |
08 | PW filling hoses, caps, connections, procedures; Sample records, valves; PW system constructed, maintained | 0 |
16 | Potentially hazardous food temperatures storage, preparation display, service, transportation | 0 |
19 | Food protected storage, preparation, display, service, transportation; Original containers, labeling; Food handling minimized; In-use food dispensing, preparation utensils stored | 0 |
22 | Dishwashing / equipment washing facilities designed, constructed, maintained, installed, located, operated, TMDs, test kits | 0 |
27 | Equipment / utensils non-food-contact surfaces clean | 0 |
33 | Decks / bulkheads / deckheads construction, repair, clean | 0 |
|
Selected Item Details
|
Item No.:
06
|
|
Site:
Potable Water-Distribution Nework - Aft |
Violation:
The ship's potable water distribution network was divided into forward and aft distribution loops from the lower to upper decks. According to staff, there was no piping which joined these loops, but there was only a single monitoring analyzer and chart recorder installed for the forward loop on the bridge on deck 14. There was no analyzer or chart recorder at the far point for the aft distribution loop. |
Recommendation:Ensure that a halogen analyzer-chart recorder is installed at a distant point in the potable water distribution system where a significant water flow exists. In cases where dual distribution loops exist, and no pipes connec the loops, ensure that an analyzer and chart recorder is installed on each loop. |
|
|