Item No. | Description | Points Deducted |
08 | PW filling hoses, caps, connections, procedures; Sample records, valves; PW system constructed, maintained | 0 |
20 | PHF temperature maintenance facilities; Food-contact surfaces designed, constructed, installed, maintained; TMD=s provided, located, calibrated | 0 |
21 | Nonfood-contact surfaces designed, constructed, maintained, installed, located | 0 |
24 | Sanitizing rinse temperature, concentration, time | 0 |
33 | Decks / bulkheads / deckheads construction, repair, clean | 0 |
34 | Plumbing fixtures / supply lines / drain lines / drains installed, repair | 0 |
36 | Lighting provided, shielded | 0 |
|
Selected Item Details
|
Item No.:
08
|
|
Site:
Potable Water- |
Violation:
There were a few connections to the potable water system that were not listed in the comprehensive cross-connection control program. These connections were the hose connection in the chlorine dosing station for the potable water system, the crew galley combination oven, the hospital ward showers, and the spa therapy room showers. All of these connections were adequately protected. |
Recommendation:Ensure that all of the connections to the potable water system where contamination can occur are listed. |
|
Site:
Potable Water- |
Violation:
The potable water line in the hydropool pump room was not striped or painted blue. |
Recommendation:Ensure that each potable water filling line is painted auxiliary blue and clearly marked "POTABLE WATER FILLING" in letters at least 13 mm (0.5 inch) high, stamped on a non-corrosive label plate or the equivalent and located at or near the point of hose connection. |
|
|