Item No.:
08
|
Site:
Potable Water-Cross-Connection Control Program
|
Violation:
The listing of cross connections did not include the air gaps for the mineralizer, water softener, or evaporator drains.
|
Recommendation:
Ensure that air-gaps are included in the cross-connection control program listing.
|
|
Item No.:
08
|
Site:
Potable Water-Cross-Connection Control Program
|
Violation:
The cross-connection listing for the passenger and crew showers/toilets did not list the type of backflow prevention device/method used.
|
Recommendation:
Ensure that the cross-connection control program listing includes the backflow prevention method/device for each (non-continuous pressure type, continuous pressure type, atmospheric vacuum breaker, etc.), so that there is a match to the plumbing system component and location.
|
|
Item No.:
10
|
Site:
Swimming Pool-Deck 11 Aft Pool
|
Violation:
There was one screw missing from each of the two main drain covers.
|
Recommendation:
Ensure all drain cover fasteners are installed properly.
|
|
Item No.:
10
|
Site:
Swimming Pool-Passenger and Crew Pools
|
Violation:
The drain covers were not stamped with an approving organization or flow rate information. The documentation received from the yard stated that the covers were "anti-vortex", however the cited references were for construction materials.
|
Recommendation:
Ensure that the drain covers have either the plumbing/engineering approving organization stamp and flow rate affixed to the cover, or that a letter is maintained aboard the vessel certifying that the cover meets the safety requirements outlined in AMSE/ANSI A112.19.8M or an equivalent standard.
|
|
Item No.:
20
|
Site:
Buffet-La Pergola Beverage Station (Starboard)
|
Violation:
The bulk milk dispenser tube was not cut at an angle to allow the milk tube to drain.
|
Recommendation:
Ensure that the bulk milk container dispensing tube is cut on the diagonal leaving no more than 25mm (1 inch) protruding from the chilled dispensing head.
|
|
Item No.:
21
|
Site:
Bar-Deck 11 Pool Bar - Technical Space Below Espresso Machine
|
Violation:
There was a void space between the storage cabinet insert and the floor of the technical space located below the espresso machine.. The void space was sealed at the time of the inspection.
|
Recommendation:
Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
Item No.:
21
|
Site:
Galley-LeBistrot Dishwash Area
|
Violation:
Some of the large, black waiter trays were damaged along the edges.
|
Recommendation:
Replace damaged waiter trays.
|
|
Item No.:
21
|
Site:
Buffet-LeBistrot Beverage Stations (Port/Starboard)
|
Violation:
A void space was noted in the technical compartment of both beverage stations. The void was clean at the time of the finding. This was corrected.
|
Recommendation:
Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
Item No.:
21
|
Site:
Galley-Potwash Area
|
Violation:
The data plate on the mechanical pot washer was peeling.
|
Recommendation:
Replace the data plate.
|
|
Item No.:
21
|
Site:
Galley-Hot Galley
|
Violation:
There were peeling labels on the portside control panel of the grills.
|
Recommendation:
Replace labels as needed.
|
|
Item No.:
21
|
Site:
Galley-Dishwash Area
|
Violation:
A few waiter trays were damaged along the edges. This was corrected.
|
Recommendation:
Discard damaged waiter trays.
|
|
Item No.:
21
|
Site:
Galley-Deep Fat Fryer
|
Violation:
A peeling label was found on the this unit. This was corrected.
|
Recommendation:
Replace label as needed.
|
|
Item No.:
26
|
Site:
Galley-LeBistrot Dishwash Area
|
Violation:
Two previously cleaned cold cut trays, one fork and two medium-sized salad bowls were found soiled and stored as clean.
|
Recommendation:
Ensure that food only contacts surfaces of equipment and utensils that are cleaned and sanitized.
|
|
Item No.:
26
|
Site:
Galley-Potwash Area
|
Violation:
One previously cleaned spatula was found soiled and stored ready for use. This was corrected.
|
Recommendation:
Ensure that food only contacts surfaces of equipment and utensils that are cleaned and sanitized.
|
|
Item No.:
27
|
Site:
Galley-Deep Fat Fryer
|
Violation:
There was a small amount of grease on the exterior surface of the previously cleaned deep fat fryer technical area.
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
Item No.:
27
|
Site:
Galley-Ribbed Grill
|
Violation:
There was some encrusted food debris in the grease tray housing of this unit.
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
Item No.:
33
|
Site:
Galley-Potwash Area
|
Violation:
There was peeling sealant on the bulkhead near the handwash station and the clean storage rack. This was corrected.
|
Recommendation:
Remove sealant.
|
|
Item No.:
33
|
Site:
Galley-Soup Station
|
Violation:
There was peeling sealant on the bulkhead behind the combination oven and adjacent to the exit door.
|
Recommendation:
Remove sealant and re-seal seam as needed.
|
|
Item No.:
33
|
Site:
Pantry-Room Service Pantry
|
Violation:
There was peeling sealant on the bulkhead under the single-compartment dishwasher. This was corrected.
|
Recommendation:
Remove sealant and re-seal seam as needed.
|
|