Cruise Ship: Carnival Destiny Cruise line: Carnival Cruise Lines, Inc. Inspection Date: 10/16/2008 Score: 94
 
This cruise ship inspection report lists the deficiencies found during the inspection. Additional information corresponding to each item number is available in the lastest editions of the CDC VSP Operational Manual.



 
    Cruise Ship's Corrective Action Statement

Item No.: 03
Site: Potable Water-Bunkering Charts
Violation: On 07/08, 08/4, 11, 12, 19, 23, 26, 09/2 and 09/27, the ship bunkered potable water at less than 2 ppm for the entire bunkering period.
Recommendation: Ensure that potable water is continuously halogenated to at least 2.0 mg/L (ppm) free residual halogen at the time of bunkering or production with an automatic halogenation device that is controlled by a flow meter.
Item No.: 03
Site: Potable Water-Bunkering Charts
Violation: On 07/4, 7, 14 and 09/04, the initial chlorine residual for bunkering was less than 2 ppm. It took more than 1/2 an hour to reach 2 ppm during bunkering.
Recommendation: Ensure the chlorine residual level reaches 2 ppm within the first half hour of bunkering.
Item No.: 08
Site: Potable Water-Hair Salon
Violation: There was no backflow prevention device installed on the hot potable water line for the hair sink.
Recommendation: Ensure that a continuous pressure-type backflow preventer is installed when a valve is located downstream from the backflow preventer.
Item No.: 08
Site: Whirlpool/Spa-Aft Whirlpool Machinery Room
Violation: There was no backflow prevention device installed on the potable water line with a hose connection.
Recommendation: Ensure that backflow preventers are installed when air gaps are impractical or when water under pressure is required.
Item No.: 08
Site: Potable Water-Engine Room
Violation: The chlorine injection point for potable water bunkering was less than 3 meters from the chlorine sample point.
Recommendation: Ensure that water samples for halogen testing are obtained from a sample cock located on the bunker or production water line at least 3 m (10 feet) after the halogen injection point and before the storage tank.
Item No.: 08
Site: Potable Water-Port Midship Bunker Station
Violation: The cap for the potable water filling line was able to touch the deck when hanging free.
Recommendation: Ensure that the potable water filling line has a screw cap or plug fastened by a non-corroding chain to an adjacent bulkhead or surface in such a manner that the cap or plug does not touch the deck when hanging free. The connections for the hose attachments shall be unique and fit only potable water hoses.
Item No.: 08
Site: Galley-
Violation: The backflow prevention device in the hood cleaning system was dripping at the intermediate vent. A new backflow prevention device was on order.
Recommendation: Ensure that backflow preventers are maintained in good repair.
Item No.: 08
Site: Bar-Flagship Bar
Violation: There was a non-continuous pressure backflow prevention device installed on the potable water line to the coffee machine.
Recommendation: Ensure that a continuous pressure-type backflow preventer is installed when a valve is located downstream from the backflow preventer.
Item No.: 10
Site: Whirlpool/Spa-Lido Midship Whirlpool
Violation: A few of the suction covers were not anti-entrapment covers on both the starboard and port whirlpools. Per staff, they ordered the wrong ones and the new ones were on order.
Recommendation: Ensure that anti-entrapment drain covers or other drains that prevent entrapment hazards as specified in U.S. Consumer Product Safety Publication 363-009801 (dual drains/channel drains) are provided on swimming pools and whirlpool spas. Ensure that drain covers have either the plumbing/engineering approving organization stamp and flow rate affixed to the cover, or that a letter is maintained aboard the vessel certifying that the cover meets the safety requirements outlined in AMSE/ANSI A112.19.8M or an equivalent standard.
Item No.: 10
Site: Swimming Pool-Slide Pool
Violation: The shepherd's hook and the approved floatation device were not located in a prominent location.
Recommendation: Ensure that an easy-access shepherd's hook and approved floatation device (with a length of line 1/2 the pool width or 16 m (50 feet)) is provided at a prominent location near each public swimming pool.
Item No.: 10
Site: Whirlpool/Spa-All Whirlpools
Violation: The stamp on the suction covers stated "important this side down". The suction covers were incorrectly installed with the stamp on top.
Recommendation: Ensure suction covers are installed according to manufacturer's instructions.
Item No.: 10
Site: Swimming Pool-Aft Pool
Violation: The approved floatation device was not located in a prominent location.
Recommendation: Ensure that an easy-access shepherd's hook and approved floatation device (with a length of line 1/2 the pool width or 16 m (50 feet)) is provided at a prominent location near each public swimming pool.
Item No.: 16
Site: Buffet-Beverage Stations
Violation: The milk containers at the beverage stations had blue lids at 0945. According to the time as a public health control plan, the containers should have been replaced with containers with black lids at 0800. The containers were replaced.
Recommendation: Ensure the milk containers are replaced according to the time as a public health control plan.
Item No.: 19
Site: Buffet-New York Deli
Violation: There were side-dish items placed under a sneeze guard for passenger self-service. The sneeze guard was adjusted too high to protect the food and a container of chips were placed outside the sneeze guard. This was corrected and the buffet was not yet open for passengers.
Recommendation: Ensure that food on display is protected from contamination by the use of packaging; counter, service line, or salad bar food guards; display cases; or other effective means.
Item No.: 20
Site: Food Service General-Slicers
Violation: There was soft sealant around the back plate of several slicers. The sealant was food-grade sealant.
Recommendation: Ensure the sealant is hard or semi-hard.
Item No.: 21
Site: Buffet-Forward Starboard Grill Pantry
Violation: There was excess electrical cable under the hot holding unit. The excess cable was draped on the counter under the unit.
Recommendation: Remove the excess electrical cable.
Item No.: 21
Site: Buffet-Grand Buffet
Violation: There was an unsealed pipe penetration in the back of the technical compartment below the port side induction cooker.
Recommendation: Seal the pipe penetration.
Item No.: 22
Site: Galley-Dishwash
Violation: The temperature gauge on the flight-type dishwash machine was not accurate. The temperature indicated 162°F and the plate temperature was measured at 163°F.
Recommendation: Ensure that warewashing equipment is maintained in good repair and proper adjustment including: (1) Being maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; and (2) Maintaining water pressure, and water temperature measuring devices in good repair and ensuring their accuracy within the intended range of use.
Item No.: 27
Site: Galley-Tilting Pans
Violation: The turning handle for the center tiling pan was soiled on the back with dried food debris.
Recommendation: Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 33
Site: Pantry-Port and Starboard Forward Pantries
Violation: There was a large open void on the door frame where the locking pin inserted allowing access for insects and making cleaning difficult.
Recommendation: Seal the opening.
Item No.: 33
Site: Provisions-Dry Stores #1
Violation: The pipe penetration for the new sprinkler system in the upper right corner above the entrance was not sealed.
Recommendation: Seal the pipe penetration.
Item No.: 33
Site: Provisions-Frozen Vegetables
Violation: To the right of the entrance, there was a bulkhead panel that had buckled, creating a vertical gap near the lower edge of the bulkhead.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 33
Site: Preparation Room-Fish/Poultry Preparation
Violation: There was missing and peeling sealant along the backsplash/bulkhead juncture.
Recommendation: Replace the sealant.
Item No.: 33
Site: Food Service General-Deck Grout
Violation: There was cracked, recessed and missing grout throughout the galley, especially at drain and gutterway junctures with deck tiles.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 33
Site: Galley-
Violation: The deck below the ice cream dipper well was soiled.
Recommendation: Ensure that decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, are cleaned as often as necessary.
Item No.: 33
Site: Food Service General-Doors
Violation: Each of the painted steel door frames had holes for the locking pins. The holes did not have recessed nipples and were open to the door frame void.
Recommendation: Seal the holes in the door frames.
Item No.: 33
Site: Food Service General-Waiter Stations
Violation: The deck/cabinet junctures in the lido buffet area and deck/bulkhead junctures in the dining room waiter stations were not coved.
Recommendation: Ensure that bulkhead and deck junctures are coved (including galleys, pantries, deck/counter junctures at buffets, bars, waiter stations, and dining room work counters).
Item No.: 33
Site: Bar-Starboard Solar Bar
Violation: There were excess electrical wires on the deck in the technical compartment below the computer. The deck under the wires was soiled.
Recommendation: Ensure that decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, are cleaned as often as necessary.
Item No.: 33
Site: Bar-Starboard Solar Bar
Violation: There were excess electrical wires on the deck in the technical compartment below the computer. The deck under the wires was soiled.
Recommendation: Ensure that exposed utility service lines and pipes, including lines for fire detection and protection systems, are installed so they do not obstruct or prevent cleaning.
Item No.: 34
Site: Buffet-Beverage Station
Violation: There was a water leak under the coffee machine.
Recommendation: Ensure that a plumbing system in a food area is maintained in good repair.
Item No.: 36
Site: Pantry-Stellar Bar
Violation: The overhead light at the glass storage rack was not working, resulting in light levels less than 220 lux.
Recommendation: Replace the overhead light.
Item No.: 37
Site: Galley-Aft Dishwash
Violation: There was heavy condensation in the hood above the dishwash unit.
Recommendation: Ensure that ventilation hood systems and devices are sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads.