Fatality Assessment and Control Evaluation (FACE) Program |
|
Two Vietnamese Floor Sanders Die When Wood Floor Finish Product Ignites |
| |||||||||||
SummaryOn September 2, 2004, two 35-year-old floor sanders (victims) were fatally injured and two other floor sanders were burned, one seriously, when the three-family house they were working in caught fire. The victims were refinishing the wood floors in the third floor unit and the stairs leading up to the third floor unit of the multifamily house. The incident occurred when the flammable lacquer floor sealer that they were applying ignited, causing the house to catch fire. Calls were placed to emergency medical services (EMS) and the fire department. Within minutes, EMS and fire department personnel arrived at the site to attend to the victims and control the fire. One of the victims was pronounced dead at the scene. The other three workers were transported to a local hospital where a second worker died of his burns the following day. The Massachusetts FACE Program concluded that to prevent similar occurrences in the future, employers should:
The wood floor finishing industry and other stakeholders, such as contractors, insurance companies, and government agencies should:
Homeowners finishing wood floors themselves or through hired contractors should:
In addition, policymakers should:
BackgroundWood floor sanding and finishing can expose workers, building occupants, and homeowners to a variety of health and safety hazards. In Massachusetts, three workers have died within a ten month period (September 2004 – July 2005) in fires resulting from wood floor finishing when the flammable lacquer floor sealer they were applying ignited. All three of these fatally injured workers were Vietnamese immigrants. According to a Safety Bulletin released by the Boston Fire Department, between 1995 and September 2004, Boston, Massachusetts has experienced more than 25 fires directly attributed to hardwood floor installation and refinishing, resulting in a property loss value of over 1.5 million dollars. This Safety Bulletin has been included at the end of this Massachusetts FACE report. Nationally from 1992-2002, 52 fatal injuries were sustained by workers in the floor laying/other floor work business (Bureau of Labor Statistic, Census of Fatal Occupational Injuries data, using Standard Industrial Code 1752, not necessarily wood floors). Of these injuries, 21% (11/52) resulted from fires and explosions. Five of the workers who died due to fire or explosion were employed specifically in wood floor sanding. In 2004, the Massachusetts Floor Finishing Safety Task Force was formed with members from community, health, safety, academic, and economic development organizations. A report has been released by this task force and is referenced at the end of this Massachusetts FACE report. Back to TopIntroductionOn September 3, 2004, the Massachusetts FACE Program was alerted by local media that on September 2, 2004, one floor sander was fatally injured and three others were seriously burned when the house they were working in caught fire. An investigation was initiated. On September 6, 2004, the Massachusetts FACE Program was again alerted by local media that a second worker had died of the injuries he sustained during the September 2, 2004 incident. On October 10, 2004 the Massachusetts FACE Director interviewed a representative of the victims’ company. The fire report, death certificates, corporate information, and Occupational Safety and Health Administration (OSHA) information were reviewed during the course of the investigation. The employer, a wood floor company, had been in business for 21 years at the time of the incident. The company employed approximately eight workers that were split into two work crews comprised of two to four workers per crew, depending on the job size. The victims each had between two and five years of experience. The company did not have a written comprehensive hazard communication program. Although the victims did receive on-the-job training, the training did not address the hazards associated with this incident. The company provided workers with respirators, but did not have safety procedures for respirator use. The employees did not have union representation. Both of the fatally injured workers were Vietnamese immigrants. The company owner is also Vietnamese. Back to TopInvestigationThe company was hired to refinish the wood floor in a third floor unit and two sets of wood stairs leading up to the third floor in a multifamily house (Figure 1). One stairway connected the first floor to the second floor and the other stairway connected the second floor to the third floor. At the time of the incident, the third floor unit was vacant and the bottom two units were occupied. The owners of the multifamily house lived in the first unit, which comprised the entire first floor and a section of the second floor. The remaining area on the second floor comprised the second unit and the entire third floor was one unit. The owners of the house were home at the time of the incident and the second unit occupants were not home. During the interview, the company representative described their usual floor finishing procedure, which included but was not limited to the following:
The day of the incident was the company's first day on site. Four floor sanders were assigned to the job, with one of the floor sanders also acting as a field supervisor. Two of the workers arrived at the house at 8:45 a.m. and started sanding the stairway that led from the first floor to the second floor. These workers then moved to sanding the stairway that led from the second floor to the third floor and the wood floors in the third floor unit. Once finished with the sanding task, the two workers vacuumed the remaining wood dust within the third floor unit and the stairs that connected the second floor to the third floor. At approximately 11:00 a.m. the workers stopped vacuuming and started to apply the lacquer sealer to the wood floors in the third floor unit. According to the manufacturer’s material safety data sheet (MSDS), the lacquer sealer being used contained, but was not limited to, acetone, toluene, xylene, and keytones and had the following physical characteristics:
At approximately 11:30 a.m., two more workers arrived at the house to help apply the wood floor finishing products. Immediately prior to the incident, at approximately 12:45 p.m., one of the two surviving workers was vacuuming the second floor stairway landing and the other surviving worker was in the second floor bathroom. At this same time, the two victims were up on the third floor of the house applying the lacquer sealer. One was inside the third floor unit (victim #1) and the other victim (victim #2) was located in the upper section of the stairway that led up to the third floor from the second floor. When the vapors from the lacquer sealer ignited it caused an explosion and created a fireball that traveled through the two stairways down to the first floor. The explosion also resulted in a fire that engulfed the entire third floor of the multifamily house. The two surviving floor sanders had been the furthest from the explosion and were the first two workers to exit the burning house. The floor sander who was located in the stairway that led to the third floor unit (victim #2) exited the house with his clothes on fire shortly after the two surviving workers exited the house. The fourth floor sander (victim #1), who was working inside the third floor unit, did not exit the burning house. There were multiple ignition sources within the third floor unit, such as gas appliances and electrical sources. Gas appliances within the third floor unit included, but were not limited to the gas heating unit located above the ceiling, and the gas stove located in the kitchen. Electrical ignition sources included, but were not limited to, the refrigerator located in the kitchen, and electrical switches located throughout the unit. The two owners of the house and a friend of theirs were home at the time of the incident. After hearing the explosion and realizing that the house was on fire, they called 911 and exited the house. A nearby off-duty firefighter, who had heard the smoke alarms and noticed the smoke, arrived at the incident site and attended to the three floor sanders who had exited the house. Personnel from the local fire department and emergency medical services (EMS) arrived within minutes of notification. Due to a language barrier between the floor sanders, who spoke Vietnamese and the fire fighter and EMS personnel who spoke English, the information that a fourth floor sander (victim #1) was still inside the burning house was not able to be communicated. Victim #1 was found by fire fighters inside the first floor stairway and was pronounced dead at the scene. The three floor sanders who exited the house were all taken to a local hospital. At the hospital, a second floor sander (victim #2) died of his severe burns the following day. One of the two surviving floor sanders was released from the hospital a few days later, and the other remained in critical condition in the hospital for an extended period of time with severe burns. A short time after the incident, the house was torn down due to extensive fire damage. Investigations conducted by OSHA, the Massachusetts State Fire Marshal, and the local fire department determined that the ignition source was most likely the gas stove pilot located in the kitchen of the third floor unit. In addition, it was concluded that the windows in the third floor unit were most likely closed at the time of the incident. Back to TopCause of DeathThe medical examiner listed the cause of death for victim #1 as severe charring thermal burns and for victim #2 as complications of severe thermal burns. Recommendations/DiscussionRecommendation #1: Employers should use wood floor finishing products that are less flammable (products with flash points greater than 100° F) for indoor applications.Discussion: The flash point of a liquid is the lowest temperature at which it gives off enough vapors to ignite when a source of ignition (see recommendation #2) is present. The lower the flash point of a liquid, the higher the risk of fire or explosion. Many floor finishing products with flash points greater than 100° F, which are less flammable, are available. The flash point of a product can be found on the product label or the manufacturer’s material safety data sheet (MSDS) or by calling the manufacturer. In this incident, a highly flammable lacquer sealer (flash point of 9° F) was being used indoors. When finishing wood floors indoors, less flammable floor finishing products (products with flash points greater than 100° F) should always be used. Less flammable products will greatly reduce the risk of product ignition, explosions, and fires.
|
Figure 1 – Two photos of
the house involved in the incident. (Photographs from the Somerville News accessed on 5/26/2005 at: http://www.Somervillenews.typepad.com/the_somerville_news/news/index.html) |
|
Figure 2. Example of a Hazardous Material Identification System (HMIS) label with the HMIS ratings for the lacquer sealer used in this incident. |
In light of the recent tragic event in Somerville regarding the death
of two construction
workers, the Boston Fire Department is issuing the following safety bulletin.
This safety
bulletin is designed to inform contractors, managers and homeowners to
the potential
hazards and dangers associated with hardwood floor installation and finishing/refinishing.
Since 1995 the City of Boston has experienced more than 25 fires directly
attributed to
hardwood floor installation and refinishing. This resulted in a property
loss value of over
1.5 million dollars. In the majority of cases the cause of the fire resulted
from failure to
follow the manufacturer’s safety precautions in the handling, use
and storage of the floor
finishing chemicals.
The process of hardwood floor installation and finishing or refinishing
involves the use of
any number of the following kinds of products:
Contractors must be thoroughly familiar with the manufacturer’s
instructions and safety
precautions associated with the products in use. Building managers and
property owners
should question their contractor as to the type of finishing chemicals
the contractor is
planning on using. In particular they should request from the contractor
a copy of the
manufacturer’s safety precautions and review those sections pertaining
to flammability
and health hazards.
Improper handling of these products may present the following hazards:
Fire or Explosion - The use of these chemicals in poorly ventilated or enclosed areas may cause a significant build-up of flammable vapors. A spark or open flame could ignite the vapors causing a fire or explosion.
Refinishing can create a large amount of dust from sanding. There is
also the potential
for chemical emissions from the sealer or surface finish. These products
contain organic
solvents and other substances: polyurethane, ureaformaldehyde and various
resins.
Workers who improperly handle the products can be exposed to high levels
of vapors.
Prolonged and repeated exposure may produce adverse health effects.
Commonwealth of Massachusetts regulations to date:
Flammable Liquids used for Floor Refinishing
527 CMR 14.03 (6) allows recognized tradesmen or artisans to have and
use 5 gallons of
flammable liquids without obtaining a permit, provided it is removed from
the building or
structure upon completion of each working day.
They must have a suitable fire extinguisher of a least 1A-10BC rating
available at all
times.
527 CMR 14.04 (8) in locations where flammable vapors may be present,
precautions
shall be taken to prevent ignition by eliminating or controlling sources
of ignition.
Sources of ignition shall include open flames, lightening, smoking, cutting,
and welding,
hot surfaces, frictional heat, sparks, static (electrical and mechanical),
spontaneous
ignition, physical chemical reactions and radiant heat. The Head of the
Fire Department
shall prohibit the use of devices or order the suspension of an operation
when proper
precautionary measures are not taken.
Other sources of ignition: stoves, refrigerators, electric lights and
switches, heating
equipment, fans used for ventilation if not of the proper type.
BFPC 17.02 Permit Required
A permit shall be obtained for application of finishing materials by
spraying, dipping or
other means of which use of more than one gallon of flammable or combustible
liquids or
fluidized powders in any working day. No permit will be required for small,
intermittent
spraying operations for domestic or other incidental use unless required
by the Head of
the Fire Department when such operations are a major process of a business.
In closing this information is provided on the Boston Fire Department
web site at
http://www.cityofboston.gov/BFD/index.html. (Link no longer valid 4/12/2007)
Additional questions can be directed to the Fire Marshal at:
Boston Fire Department
Fire Marshal
1010 Massachusetts Avenue
Boston, MA 02118
Phone: 617-343-3402
To contact Massachusetts State FACE program personnel regarding State-based FACE reports, please use information listed on the Contact Sheet on the NIOSH FACE web site Please contact In-house FACE program personnel regarding In-house FACE reports and to gain assistance when State-FACE program personnel cannot be reached.