![]() |
|
![]() |
Fatality Assessment and Control Evaluation (FACE) Program |
![]() |
52-year-old Female Janitor Died as a Result of a Vapor Flashback While Using Flammable Lacquer Thinner to Remove Carpet Glue From Concrete Basement Floor | ![]() |
| ||||||||||||||
SummaryOn September 17, 2004, a 52-year-old female janitor for a public housing commission died from burn injury complications sustained on September 9, 2004. The victim was removing carpet glue from a concrete floor in the basement “den” area of a townhouse unit with a flammable lacquer thinner. See Figure 1 for an example of a townhouse basement unit layout. The victim was assisting a co-worker in preparing the townhouse unit for a new tenant. While her co-worker was cleaning the second story of the townhouse, she proceeded to the basement. The mechanical room contained the gas hot water heater and furnace, plumbing and electrical for a washer and dryer, and a laundry tub. The victim was using the flammable lacquer thinner on the floor to soften the carpet glue so she could remove it. Although both basement rooms had 17” x 11” windows, she did not open them. It is hypothesized that she poured the lacquer thinner on the floor. The vapors from the lacquer thinner migrated into the mechanical room, contacted the open flame of the hot water heater and flashed back and burned her. Her co-worker working upstairs heard the victim scream and came to assist her. The co-worker found the victim at the top of the basement stairs and assisted her outside. The co-worker used her walkie-talkie to contact the housing commission office, and office personnel contacted 911. The victim was transported to a local hospital where she died approximately a week later.
Recommendations:
IntroductionOn September 17, 2004, a 52-year-old female janitor for a public housing commission died from burn injuries sustained on September 9, 2004. The victim was removing carpet glue from a concrete floor in the basement “den” area of a townhouse unit with a flammable lacquer thinner. On September 20, 2004, MIFACE investigators were informed by the Michigan Occupational Safety and Health Administration (MIOSHA) personnel who had received a report on their 24-hour-a-day hotline that a work-related injury had occurred on September 9, 2004 and had resulted in the individual’s death nine days later. On October 26, 2004, the MIFACE researcher interviewed the Executive Director of the Housing Commission. The Director also accompanied the MIFACE researcher to a townhouse that was similarly constructed as the one in which the victim was burned. The Director permitted MIFACE to take pictures of a similarly constructed townhouse basement (Figure 1). During the course of writing the report, the Fire Department report and pictures, police report, medical examiner’s case report, and MIOSHA citations were obtained. Figures 2, 3, 4, 5, and 6 are pictures taken by the Fire Department at the time of their investigation. The employer, a housing commission, administers federal funds for low-income housing. This housing commission has been at the site since 1960 and had grown in size over the years. The housing commission employed 13 people. Two people have the same job title as the victim, which is janitor. The victim was also a supervisor for all of the community service individuals and other maintenance workers. The victim worked full time, from 8:00 a.m.-4:00 p.m., and had been employed by the housing commission for seven years. Due to her work performance over the seven years of employment, she was given additional job responsibilities, such as overseeing extermination activities and crew cleanup of rental units. The Executive Director of the housing commission characterized her as a very conscientious employee. The housing commission did not have a written Health and Safety Program. Employees had not received health and safety training. The commission did not have a Health and Safety Committee and did not have a written disciplinary procedure in place for safety and health violations. The Executive Director of the housing commission had been in that position for approximately one year and was unaware that the commission site did not have appropriate training or written programs. He was also unaware of the full extent of HUD audits and inspections. The Executive Director indicated that he was unaware of any safety training that had been conducted or that there were any special cleaning problems with that particular unit. As a result of their inspection after the fatality, MIOSHA issued the following Serious citation to the employer regarding the Hazard Communication standard: the employer had not provided employees with effective information and training on hazardous chemicals in the work area at the time of their initial assignment and whenever a new physical or health hazard was introduced into their work area. Back to TopInvestigationDescription of the Work Area: A stairway led to the basement and had a door at both the top and bottom of the stairs. The basement walls were constructed of cement block and the floors were poured concrete. The basement’s ceiling height as measured from the basement floor to the floor joists above was approximately 7’ tall. Both rooms contained a 17” x 11” window that was located approximately 5’9” up from the floor. Both windows were closed while the deceased was working. The basement was divided into two rooms, the mechanical room and the den. The stairway to the basement exited to the mechanical room. The mechanical room was 12’ x 12’ and contained a natural gas furnace, natural gas hot water heater, plumbing and electrical for a washer and dryer, and a laundry tub. A 3’ wide “door” opening allowed passage between the mechanical room and the 12’ x 15’ den (Figure 1). Both the gas-fired furnace and the 40-gallon gas hot water heater were lit and operational. The hot water heater pilot light, located less than 4” above the floor was lit because hot water was needed to clean and prepare the townhouse for the next tenants (Figure 2). The hot water heater was located approximately 4 ½’ away from the door between the two rooms. The hot water heater had affixed warning signs including a sign warning of an explosion/fire hazard associated with a flammable solvent vapor on the side near the top of the unit (Figure 3). The furnace pilot light and burners were located more than 20” from the floor.
The den floor had remnants of carpet glue that had not been removed when workers had previously removed carpet tiles that had been installed by the previous tenants (Figure 4). Day of the Incident: The victim started work at approximately 7:30 a.m. on the day of the incident cleaning the office space for the Housing Commission. After finishing her work in the Administration Building, the victim proceeded to the townhouse that was being cleaned for the new tenants and assisted another co-worker. Because the den’s concrete floor was to be painted, she wanted to remove the remaining carpet glue from the floor. It is hypothesized that she poured the lacquer thinner (Figure 5) on the floor to soften the glue so she could remove it from the floor. It is unknown what tool she used to remove the glue. A push broom, still smoking from contact with the flames, was found at the scene by firefighters.
Although the lacquer thinner can had a legible warning label (Figure 6), she apparently was unaware of the hazards associated with using a flammable solvent indoors near an ignition source without ventilation. The flammable vapors from the thinner migrated into the mechanical room, were ignited by the hot water heater’s pilot light, and flashed back to their source in the den and burned the victim. The victim screamed and ascended the basement stairs. Her co-worker working upstairs heard the scream and came downstairs to assist her. Smoke filled the basement and first floor of the townhouse. Finding her at the top of the basement stairs, her co-worker assisted the victim outside and then used a walkie-talkie to contact the housing commission office. Office personnel contacted 911. Emergency response arrived and the victim was transported to a nearby hospital. She sustained burn injuries to her arms, face, neck, ears, legs, and back. She died approximately a week later from the injuries she sustained at the time of the incident.
Fire Department Inspection: The Fire Department found a metal one-gallon can of lacquer thinner in the mechanical room, and a cap consistent with the type that would cover this container located in the entryway from the mechanical room to the den. The Fire Department reported physical evidence that provided support for a fuel vapor explosion with a pressure wave. The pressure wave closed the basement door and blew dust from the cold air return into the living room. The Fire Department investigation noted that there were small amounts of fire debris and carbon particles on the stairs and that the walls were lightly covered with soot. Both the furnace and hot water heater pilot lights were extinguished, most likely due to the pressure wave or the consumption of oxygen from the flash fire. The Fire Department suspected that the pilot or the burner for the hot water heater was the source of the flashback because of its location less than 4” from the floor. The furnace pilot and burners were located more than 20" from the floor level, and based on the properties of the vapor for the lacquer thinner, the water heater is suspected due to the location of the pilot. The report indicated that the volume of the vapor generated from the use of the lacquer thinner could not be accurately calculated due to the potential for numerous unknowns. These unknowns included the amount of thinner that was on the floor, the size of the pool of thinner, and the room temperature at the time of the ignition, the duration that the thinner had been sitting on the floor. Back to TopCause of DeathThe death certificate stated the cause of death as medical complications from thermal burns. An autopsy and toxicological tests were not performed. Recommendations/DiscussionThe Housing Commission should develop and implement a hazard communication (Right-to-Know) program.The Michigan Right to Know Law, MIOSHA Hazard Communication Standard Part 92, Rule 1910.1200 mandates employers to develop a written hazard communication program. This program must evaluate the potential hazards of chemicals and communicate information concerning the identified hazards and appropriate protective measures to employees. It is vital for employees to understand the chemical hazard information provided on chemical container labels and material safety data sheets and to apply this information as they work to minimize exposure and prevent the occurrence of adverse effects to themselves and their co-workers. In this incident, the victim was working with a flammable liquid in a poorly ventilated area. A flammable liquid is any liquid whose flash point, the temperature at which its vapors can ignite when there is a spark or open flame or static electricity, is below 100 degrees Fahrenheit. To work safely with flammable liquids, it is important to control three potential hazards: temperature, ignition sources and vapor concentration. When working with flammable materials indoors, the material should be used in a well-ventilated area that is free from ignition sources, such as heating equipment, ordinary electric equipment, open flame and sparks. Fans should have non- sparking or nonferrous blades, and the motor and controls should be explosion-proof. Rule 1910.1200(h) details the information and training that employers must provide to employees at the time of their initial assignment and whenever a new physical hazard or health hazard the employees have not previously been trained about is introduced into their workplace. Training must equip employees with the skills to detect the presence or release of a hazardous chemical in the work area, recognize the physical and health hazards of the chemical, and the measures they can take to protect themselves from these hazards. Training must also include specific procedures that the employer has implemented to protect an employee from hazardous chemical exposure, such as appropriate work practices, emergency procedures and personal protective equipment. The MIOSHA Consultation, Education and Training (CET) Division has developed a publication to assist employers in developing and implementing a hazard communication (Right-To-Know) program for their workplace. The sample CET Hazard Communication program can be downloaded from the MIOSHA web site at http://www.michigan.gov/documents/CIS_WSH_CET_235_49288_7.doc
| ||||||||||||||||
![]() |
||||||||||||||||
![]() |