PART 111_ELECTRIC SYSTEMS_GENERAL REQUIREMENTS--Table of Contents

 

     Subpart 111.97_Electric Power-Operated Watertight Door Systems

 

Sec.  111.97-7  Distribution.



    (a) Each distribution panelboard for a watertight door system must 

be above the uppermost continuous deck and must have means for locking.

    (b) Each feeder supplying a watertight door operating system must be 

above the uppermost continuous deck.

    (c) Each watertight door operating system must have a separate 

branch circuit.