PART 111_ELECTRIC SYSTEMS_GENERAL REQUIREMENTS--Table of Contents

 

               Subpart 111.60_Wiring Materials and Methods

 

Sec.  111.60-5  Cable installation.



    (a) Each cable installation must meet--

    (1) Sections 20 and 22, except 20.11, of IEEE Std 45; or

    (2) IEC 92-3 and paragraph 8 of IEC 92-352.

    (b) Each cable installation made in accordance with paragraph 8 of 

IEC 92-352 must utilize the conductor ampacity values of Table I of IEC 

92-352.

    (c) Cable must not be located in any tanks except to supply 

equipment or instrumentation specially designed for and compatible with 

such location and whose function require its installation in the tank. 

The cable must be compatible with the liquid or gas in the tank or be 

protected by an enclosure.

    (d) Braided cable armor or cable metallic sheath must not be used as 

the grounding conductor.



[CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by CGD 94-108, 61 FR 

28280, June 4, 1996]