[Code of Federal Regulations] [Title 46, Volume 4] [Revised as of October 1, 2006] From the U.S. Government Printing Office via GPO Access [CITE: 46CFR111.105-3] [Page 245] TITLE 46_SHIPPING (This book contains parts 90 to 139) CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED) PART 111_ELECTRIC SYSTEMS_GENERAL REQUIREMENTS--Table of Contents Subpart 111.105_Hazardous Locations Sec. 111.105-3 General requirements. All electrical installations in hazardous locations must comply with the general requirements of section 43 of IEEE Std 45 and either the NEC articles 500-505 or IEC series 79 publications. When installations are made in accordance with the NEC articles, marine shipboard cable that complies with subpart 111.60 of this chapter may be used instead of rigid metal conduit, if installed fittings are approved for the specific hazardous location and the cable type. [CGD 94-108, 61 FR 28284, June 4, 1996]