                            TITLE 46_SHIPPING



                  (This book contains parts 90 to 139)

 

   CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED)

 

PART 98_SPECIAL CONSTRUCTION, ARRANGEMENT, AND OTHER PROVISIONS FOR 

CERTAIN DANGEROUS CARGOES IN BULK--Table of Contents

 

                 Subpart 98.25_Anhydrous Ammonia in Bulk

 

Sec.  98.25-70  Venting.



    (a) Except as provided in paragraph (b) of this section, each safety 

valve installed on a cargo tank shall be connected to a branch vent of a 

venting system which shall be constructed so that the discharge of gas 

will be directed vertically upward to a point at least 10 feet above the 

weather deck or the top of any tank or house located above the weather 

deck.

    (b) The capacity of branch vents or vent headers shall depend upon 

the number of cargo tanks connected to such branch or header as provided 

in Table 98.25-70(b).



       Table 98.25-70(b)--Capacity of Branch Vents or Vent Headers

------------------------------------------------------------------------

                                                             Percent of

                  Number of cargo tanks                     total valve

                                                             discharge

------------------------------------------------------------------------

1 or 2...................................................      100

3........................................................       90

4........................................................       80

5........................................................       70

6 or more................................................       60

------------------------------------------------------------------------



    (c) In addition to the requirement specified in paragraph (b) of 

this section, the size of the branch vents or vent headers shall be such 

that the back pressure in relief valve discharge lines shall not be more 

than 10 percent of the safety relief valve setting.

    (d) Return bends and restrictive pipe fittings are prohibited. Vents 

and headers shall be so installed as to prevent stresses on safety 

relief valve mountings.

    (e) When vent discharge risers are installed, they shall be so 

located as to provide protection against physical damage and be fitted 

with loose raincaps.

    (f) No shut-off valve shall be fitted in the venting system between 

the safety relief valve and the vent outlets. Suitable provision shall 

be made for draining the venting system if liquid can collect therein.



[CGFR 65-50, 30 FR 17022, Dec. 30, 1965, as amended by CGFR 70-10, 35 FR 

3712, Feb. 25, 1970; 35 FR 6431, Apr. 22, 1970]