Sec.  112.20-5  Failure of power from the normal source or final 

emergency power source.



    (a) If there is a reduction of potential of the normal source by 15 

to 40 percent, the loads under Sec.  112.15-1 must be automatically 

supplied from the temporary emergency power source.

    (b) For systems in which a reduction of frequency of the normal 

source or final emergency power source adversely affects the emergency 

system and emergency loads, there must be means to transfer the loads 

under Sec.  112.15-1 to the temporary emergency power source upon a 

reduction in the frequency of the normal source or final emergency power 

source.