Subpart D_Fire Extinguishing Systems
Sec. 108.441 Piping and discharge rates for CO[bdi2] systems.
(a) The size of branch lines to spaces protected by a CO2
system must meet Table 108.441.
(b) Distribution piping within a space must be proportioned from the
supply line to give proper distribution to the outlets without
throttling.
(c) The number, type, and location of discharge outlets must
distribute the CO2 uniformly throughout the space.
Table 108.441--CO2 System Pipe Size
------------------------------------------------------------------------
Minimum pipe size (inches),
CO2 supply in system, kilograms (pounds) millimeters (inches)
------------------------------------------------------------------------
45 (100).................................. 12.7 (\1/2\).
104 (225)................................. 19.05 (\3/4\).
136 (300)................................. 25.4 (1).
272 (600)................................. 31.75 (1\1/4\).
450 (1,000)............................... 38.10 (1\1/2\).
1,110 (2,450)............................. 50.80 (2).
1,130 (2,500)............................. 63.5 (2\1/2\).
2,023 (4,450)............................. 76.2 (3).
3,229 (7,100)............................. 88.9 (3\1/2\).
4,750 (10,000)............................ 101.6 (4).
6,818 (15,000)............................ 114.3 (4\1/2\).
------------------------------------------------------------------------
(d) The total area of all discharge outlets must be more than 35
percent and less than 85 percent of the nominal cylinder outlet area or
the area of the supply pipe, whichever is smaller. The nominal cylinder
outlet area in square centimeters is determined by multiplying the
factor 0.0313 by the number of kilograms of CO2 required.
(The nominal cylinder outlet area in square inches is determined by
multiplying the factor 0.0022 by the number of pounds of CO2
required). The nominal cylinder outlet area must not be less than 71
square millimeters (0.110 square inches).
(e) A CO2 system must discharge at least 85 percent of
the required amount within 2 minutes.