Sec. 108.437 Pipe sizes and discharge rates for enclosed ventilation
systems for rotating electrical equipment.
(a) The minimum pipe size for the initial charge must meet table
108.441 and the discharge of the required amount of CO2 must
be completed within 2 minutes.
(b) The minimum pipe size for the delayed discharge must be at least
1.25 centimeters (\1/2\ inch) standard pipe.
(c) The pipe used for the initial discharge must not be used for the
delayed discharge, except systems having a volume of less than 57 cubic
meters (2,000 cubic feet).