                   TITLE 40--PROTECTION OF ENVIRONMENT
 
         CHAPTER I--ENVIRONMENTAL PROTECTION AGENCY (CONTINUED)
 
PART 141_NATIONAL PRIMARY DRINKING WATER REGULATIONS--Table of Contents
 
                  Subpart H_Filtration and Disinfection
 
Sec. 141.73  Filtration.

    A public water system that uses a surface water source or a ground 
water source under the direct influence of surface water, and does not 
meet all of the criteria in Sec. 141.71 (a) and (b) for avoiding 
filtration, must provide treatment consisting of both disinfection, as 
specified in Sec. 141.72(b), and filtration treatment which complies 
with the requirements of paragraph (a), (b), (c), (d), or (e) of this 
section by June 29, 1993, or within 18 months of the failure to meet any 
one of the criteria for avoiding filtration in Sec. 141.71 (a) and (b), 
whichever is later. Failure to meet any requirement of this section 
after the date specified in this introductory paragraph is a treatment 
technique violation.
    (a) Conventional filtration treatment or direct filtration. (1) For 
systems using conventional filtration or direct filtration, the 
turbidity level of representative samples of a system's filtered water 
must be less than or equal to 0.5 NTU in at least 95 percent of the 
measurements taken each month, measured as specified in Sec. 141.74 
(a)(1) and (c)(1), except that if the State determines that the system 
is capable of achieving at least 99.9 percent removal and/or 
inactivation of Giardia lamblia cysts at some turbidity level higher 
than 0.5 NTU in at least 95 percent of the measurements taken each 
month, the State may substitute this higher turbidity limit for that 
system. However, in no case may the State approve a turbidity limit that 
allows more than 1 NTU in more than 5 percent of the samples taken each 
month, measured as specified in Sec. 141.74 (a)(1) and (c)(1).
    (2) The turbidity level of representative samples of a system's 
filtered water must at no time exceed 5 NTU, measured as specified in 
Sec. 141.74 (a)(1) and (c)(1).
    (3) Beginning January 1, 2002, systems serving at least 10,000 
people must meet the turbidity requirements in Sec. 141.173(a).
    (4) Beginning January 1, 2005, systems serving fewer than 10,000 
people must meet the turbidity requirements in Sec. Sec. 141.550 
through 141.553.
    (b) Slow sand filtration. (1) For systems using slow sand 
filtration, the turbidity level of representative samples of a system's 
filtered water must be less than or equal to 1 NTU in at least 95 
percent of the measurements taken each month, measured as specified in 
Sec. 141.74 (a)(1) and (c)(1), except that if the State determines 
there is no significant interference with disinfection at a higher 
turbidity level, the State may substitute this higher turbidity limit 
for that system.
    (2) The turbidity level of representative samples of a system's 
filtered water must at no time exceed 5 NTU, measured as specified in 
Sec. 141.74 (a)(1) and (c)(1).
    (c) Diatomaceous earth filtration. (1) For systems using 
diatomaceous earth filtration, the turbidity level of representative 
samples of a system's filtered water must be less than or equal to 1 NTU 
in at least 95 percent of the measurements taken each month, measured as 
specified in Sec. 141.74 (a)(1) and (c)(1).
    (2) The turbidity level of representative samples of a system's 
filtered water must at no time exceed 5 NTU, measured as specified in 
Sec. 141.74 (a)(1) and (c)(1).
    (d) Other filtration technologies. A public water system may use a 
filtration technology not listed in paragraphs (a) through (c) of this 
section if it demonstrates to the State, using pilot plant studies or 
other means, that the alternative filtration technology, in combination 
with disinfection treatment that meets the requirements of Sec. 
141.72(b), consistently achieves 99.9 percent removal and/or 
inactivation of Giardia lamblia cysts and 99.99 percent

[[Page 451]]

removal and/or inactivation of viruses. For a system that makes this 
demonstration, the requirements of paragraph (b) of this section apply. 
Beginning January 1, 2002, systems serving at least 10,000 people must 
meet the requirements for other filtration technologies in Sec. 
141.173(b). Beginning January 14, 2005, systems serving fewer than 
10,000 people must meet the requirements for other filtration 
technologies in Sec. 141.550 through 141.553.

[54 FR 27527, June 29, 1989, as amended at 63 FR 69516, Dec. 16, 1998; 
66 FR 3776, Jan. 16, 2001; 67 FR 1836, Jan. 14, 2002; 69 FR 38855, June 
29, 2004]