SURVEY FORM 20: ALARMS

Use with the Minimum Requirements Summary Sheets and ADAAG.

Facility Name:

See Minimum Requirements Summary Sheets I and J for special requirements and exceptions which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7.

Note: Emergency warning systems in medical care facilities may be modified to suit standard health care alarm design practice. (4.1.3(14))

Alarm Location:

Section Item Technical Requirements Comments Yes No
4.1.3(14) Alarms: Does the building or facility have a fire, evacuation or emergency alarm?      
    Is there a visual alarm (e.g., flashing light) which operates at the same time as an audible alarm?      
4.28.1 Visual Alarms - Areas Required: Are there visual alarms in public and common use restrooms?      
    Are visual alarms provided in all general use areas of the building such as meeting rooms, hallways, and lobbies?      
4.28.3   Are the visual alarm signal appliances integrated into the building or facility alarm system?      
    If single-station audible alarms are provided, then are single-station visual alarm signals provided?      
  Photometric Requirements: Do all required visual alarm signals comply with the following minimum photometric requirements:      
    Is the lamp a xenon strobe type or equivalent?      
    Is the color clear or nominal white (i.e., unfiltered or clear filtered white light)?      
    Is the maximum pulse duration two-tenths of one second with a maximum duty cycle of 40 percent? (The pulse duration is defined as the time interval between initial and final points of 10 percent of maximum signal.)      
    Is the intensity a minimum of 75 candela?      
    Is the flash rate a minimum of 1 Hz and a maximum of 3 Hz?      
4.28.3 Location: Is the visual signal appliance placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower?      
    Are all portions of any room, space, corridor or hallway that is required to have a visual signal appliance no more than 50 feet from the signal (in the horizontal plane)?      
    In large rooms and spaces exceeding 100 feet across which do not have partitions or obstructions 6 feet or higher above the finish floor, are the visual signal appliances spaced around the perimeter no less than 100 feet apart or are they suspended from the ceiling?      
4.28.2 Audible Alarms: If provided, do audible alarms exceed the prevailing equivalent sound level in the room or space by at least 15 dbA, or do audible alarms exceed by 5 dbA any maximum sound level which has a duration of 60 seconds, whichever is louder?
(In no case should sound levels for alarm signals exceed 120 dbA.)
     
4.28.4 Auxiliary Alarms - Sleeping Rooms: Do accessible dwelling units and sleeping accommodations have a visual alarm connected to the building emergency alarm system?
OR
Is there a standard 110-volt electrical receptacle into which an alarm can be connected and a means by which the building alarm system will trigger such an alarm?
     
    When visual alarms are in place, is the signal visible in all areas of the unit or room?      
4.28.4 Instructions: Are instructions for using the auxiliary alarm provided?      