CHAPTER
6: PLUMBING ELEMENTS AND FACILITIES |
|
ANSI
Chapter 6. Plumbing Elements and Facilities |
||
601
General |
|
ANSI
601 General |
||
601.1
Scope. The provisions of Chapter 6 shall apply where
required by Chapter 2 or where referenced by a requirement in this document. |
|
ANSI
601.1 Scope. Plumbing elements and facilities required to be
accessible by scoping provisions adopted by the administrative authority
shall comply with the applicable provisions of Chapter 6. |
||
602
Drinking Fountains |
4.15 Drinking Fountains
and Water Coolers. |
ANSI
602 Drinking Fountains |
||
602.1
General. Drinking fountains shall comply with 307 and
602. |
4.15.1Minimum Number. Drinking
fountains or water coolers required to be accessible by 4.1 shall comply with
4.15. |
ANSI
602.1 General. Accessible drinking fountains shall comply with
Sections 602 and 307. |
||
602.2
Clear Floor Space. Units shall have a clear floor or ground space
complying with 305 positioned for a forward approach and centered on the
unit. Knee and toe clearance complying with 306 shall be provided. EXCEPTION: A
parallel approach complying with 305 shall be permitted at units for
children's use where the spout is 30 inches (760 mm) maximum above the finish
floor or ground and is 3 1/2 inches (90 mm) maximum from the front edge of
the unit, including bumpers. |
4.15.5 Clearances. (1)
Wall- and post-mounted cantilevered units shall have a clear knee space
between the bottom of the apron and the floor or ground at least 27 in (685
mm) high, 30 in (760 mm) wide, and 17 in to 19 in (430 mm to 485 mm) deep (see
Fig. 27(a) and (b)). Such units shall also have a minimum clear floor space
30 in by 48 in (760 mm by 1220 mm) to allow a person in a wheelchair to
approach the unit facing forward. See also Appendix 4.15.5 (2) Free-standing or built-in units not having a
clear space under them shall have a clear floor space at least 30 in by 48 in
(760 mm by 1220 mm) that allows a person in a wheelchair to make a parallel
approach to the unit (see Fig. 27(c) and (d)). This clear floor space shall
comply with 4.2.4. NOTE: Figure
27(a) indicates that, in addition to clearances discussed in the text, the
following knee clearance is required underneath the fountain: 27 inches (685
mm) minimum from the floor to the underside of the fountain which extends 8
inches (205 mm) minimum measured from the front edge underneath the fountain
back towards the wall; if a minimum 9 inches (230 mm) of toe clearance is
provided, a maximum of 6 inches (150 mm) of the 48 inches (1220 mm) of clear
floor space required at the fixture may extend into the toe space. (4.15.2,
4.15.5) Figure 27(b) show a 48
inch (1220 mm) minimum by 30 inch (760 mm) minimum clear floor space is
required for a forward approach to a wall-mounted fountain. If the
wall-mounted fountain is in an alcove, the minimum width of the alcove is 30
inches (760 mm) and the depth is 24 inches (610 mm) maximum. Figure 27(c) illustrates a free-standing
fountain or cooler. A 48 inch (1220 mm) minimum by 30 inch (760 mm)
minimum clear floor space is required for a side approach (long side parallel
to the front of the fountain or cooler). Figure 27(d) shows a built-in fountain or
cooler. A 48 inch (1220 mm) minimum by 30 inch (760 mm)
minimum clear floor space is required for a side approach (long side parallel
to the front of the fountain or cooler). The recess for the fountain is not
to exceed the fountain depth. |
ANSI
602.2 Clear Floor Space. A clear floor space complying with
Section 305, positioned for a forward approach to the drinking fountain,
shall be provided. Knee and toe space complying with Section 306 shall be
provided. The clear floor space shall be centered on the drinking fountain. EXCEPTIONS: 1. Drinking fountains for standing persons. 2. Drinking fountains primarily for children’s
use shall be permitted where the spout is 30 inches (760 mm) maximum above
the floor, and a parallel approach complying with Section 305, centered on
the drinking fountain, is provided. 305, centered on the drinking fountain, shall be
permitted. 3. In existing buildings, existing drinking
fountains providing a parallel approach complying with Section 305, centered
on the drinking fountain, shall be permitted. 4. Where specifically permitted by the
administrative authority, a parallel approach complying with Section 305,
centered on the drinking fountain, shall be permitted for drinking fountains
that replace existing drinking fountains with a parallel approach. |
||
602.3
Operable Parts. Operable parts shall comply with 309. |
4.15.4 Controls. Controls
shall comply with 4.27.4. Unit controls shall be front mounted or side
mounted near the front edge. |
ANSI
602.3 Operable Parts. Operable parts shall comply with Section
309. |
||
602.4
Spout Height. Spout outlets shall be 36 inches (915 mm) maximum
above the finish floor or ground. |
4.15.2 Spout Height.
Spouts shall be no higher than 36 in (915 mm), measured from the floor or
ground surfaces to the spout outlet (see Fig. 27(a)). |
ANSI
602.4 Spout Outlet Height. Spout outlets of wheelchair accessible
drinking fountains shall be 36 inches (915 mm) maximum above the floor. Spout
outlets of drinking fountains for standing persons shall be 38 inches (965
mm) minimum and 43 inches (1090 mm) maximum above the floor. |
||
602.5
Spout Location. The spout shall be located 15 inches (380 mm)
minimum from the vertical support and 5 inches (125 mm) maximum from the
front edge of the unit, including bumpers. |
4.15.3 Spout Location. The
spouts of drinking fountains and water coolers shall be at the front of the
unit and shall direct the water flow in a trajectory that is parallel or
nearly parallel to the front of the unit. The spout shall provide a flow of
water at least 4 in (100 mm) high so as to allow the insertion of a cup or
glass under the flow of water. On an accessible drinking fountain with a
round or oval bowl, the spout must be positioned so the flow of water is
within 3 in (75 mm) of the front edge of the fountain. |
ANSI
602.5 Spout Location. The spout shall be located 15 inches
(380 mm) minimum from the vertical support and 5 inches (125 mm) maximum from
the front edge of the drinking fountain, including bumpers. Where only a
parallel approach is provided, the spout shall be located 31/2 inches (89 mm)
maximum from the front edge of the drinking fountain, including bumpers. |
||
602.6
Water Flow. The spout shall provide a flow of water 4 inches
(100 mm) high minimum and shall be located 5 inches (125 mm) maximum from the
front of the unit. The angle of the water stream shall be measured
horizontally relative to the front face of the unit. Where spouts are located
less than 3 inches (75 mm) of the front of the unit, the angle of the water
stream shall be 30 degrees maximum. Where spouts are located between 3 inches
(75 mm) and 5 inches (125 mm) maximum from the front of the unit, the angle
of the water stream shall be 15 degrees maximum. |
ANSI
602.6 Water Flow. The spout shall provide a flow of water 4 inches
(102 mm) minimum in height. The angle of the water stream from spouts within
3 inches (76 mm) of the front of the drinking fountain shall be 30 degrees
maximum, and from spouts between 3 inches (76 mm) and 5 inches (125 mm) from
the front of the drinking fountain shall be 15 degrees maximum, measured
horizontally relative to the front face of the drinking fountain. |
|||
602.7
Drinking Fountains for Standing Persons. Spout outlets of
drinking fountains for standing persons shall be 38 inches (965 mm) minimum
and 43 inches (1090 mm) maximum above the finish floor or ground. |
|
|
||
603
Toilet and Bathing Rooms |
|
ANSI
603 Toilet and Bathing Rooms |
||
4.23 Bathrooms, Bathing Facilities, and Shower
Rooms. |
||||
603.1
General. Toilet and bathing rooms shall comply with 603. |
4.22.1 Minimum Number.
Toilet facilities required to be accessible by 4.1 shall comply with 4.22.
Accessible toilet rooms shall be on an accessible route. |
ANSI
603.1 General. Accessible toilet and bathing rooms shall comply
with Section 603. |
||
4.23.1 Minimum Number. Bathrooms,
bathing facilities, or shower rooms required to be accessible by 4.1 shall
comply with 4.23 and shall be on an accessible route. |
||||
603.2
Clearances. Clearances shall comply with 603.2. |
4.22.3 Clear Floor Space
[Toilet Rooms]. The accessible fixtures and controls required
in 4.22.4, 4.22.5, 4.22.6, and 4.22.7 shall be on an accessible route. An
unobstructed turning space complying with 4.2.3 shall be provided within an
accessible toilet room. The clear floor space at fixtures and controls, the
accessible route, and the turning space may overlap. 4.23.3 Clear Floor Space
[Bathrooms, Bathing Facilities, and Shower Rooms]. The accessible
fixtures and controls required in 4.23.4, 4.23.5, 4.23.6, 4.23.7, 4.23.8, and
4.23.9 shall be on an accessible route. An unobstructed turning space
complying with 4.2.3 shall be provided within an accessible bathroom. The
clear floor spaces at fixtures and controls, the accessible route, and the
turning space may overlap. |
ANSI
603.2 Clearances. |
||
603.2.1
Turning Space. Turning space complying with 304 shall be
provided within the room. |
ANSI
603.2.1 Turning Space. A turning space complying with Section
304 shall be provided within the room. |
|||
603.2.2
Overlap. Required clear floor spaces, clearance at
fixtures, and turning space shall be permitted to overlap. |
ANSI
603.2.2 Overlap. Clear floor spaces, clearances at fixtures, and
turning spaces shall be permitted to overlap. |
|||
603.2.3
Door Swing. Doors shall not swing into the clear floor space
or clearance required for any fixture. Doors shall be permitted to swing into
the required turning space. EXCEPTIONS: 1. Doors to a toilet room or bathing room for a
single occupant accessed only through a private office and not for common use
or public use shall be permitted to swing into the clear floor space or
clearance provided the swing of the door can be reversed to comply with
603.2.3. 2. Where the toilet room or bathing room is for
individual use and a clear floor space complying with 305.3 is provided
within the room beyond the arc of the door swing, doors shall be permitted to
swing into the clear floor space or clearance required for any fixture. |
4.22.2 Doors [Toilet Rooms].
All doors to accessible toilet rooms shall comply with 4.13. Doors shall not
swing into the clear floor space required for any fixture. |
ANSI
603.2.3 Door Swing. Doors shall not swing into the clear
floor space or clearance for any fixture. EXCEPTIONS:
1. Doors to a toilet and bathing room for a
single occupant, accessed only through a private office and not for common
use or public use shall be permitted to swing into the clear floor space,
provided the swing of the door can be reversed to meet Section 603.2.3. 2. Where the room is for individual use and a
clear floor space complying with Section 305.3 is provided within the room
beyond the arc of the door swing. |
||
4.23.2 Doors Space [Bathrooms,
Bathing Facilities, and Shower Rooms]. Doors to accessible bathrooms shall
comply with 4.13. Doors shall not swing into the floor space required for any
fixture. |
||||
603.3
Mirrors. Mirrors located above lavatories or countertops
shall be installed with the bottom edge of the reflecting surface 40 inches
(1015 mm) maximum above the finish floor or ground. Mirrors not located above
lavatories or countertops shall be installed with the bottom edge of the
reflecting surface 35 inches (890 mm) maximum above the finish floor or
ground. |
4.22.6 Lavatories and
Mirrors[Toilet Rooms]. If lavatories and mirrors are provided,
then at least one of each shall comply with 4.19. |
ANSI
603.3 Mirrors. Mirrors located above lavatories, sinks or
counters shall be mounted with the bottom edge of the reflecting surface 40
inches (1015 mm) maximum above the floor. Mirrors not located above
lavatories, sinks or counters shall be mounted with the bottom edge of the
reflecting surface 35 inches (890 mm) maximum above the floor. |
||
4.23.6 Lavatories and Mirrors
Space [Bathrooms, Bathing Facilities, and Shower Rooms]. If lavatories
and mirrors are provided, then at least one of each shall comply with 4.19. |
||||
4.19.6 Mirrors. Mirrors
shall be mounted with the bottom edge of the reflecting surface no higher
than 40 in (1015 mm) above the finish floor (see Fig. 31). |
||||
603.4
Coat Hooks and Shelves. Coat hooks shall be located within one
of the reach ranges specified in 308. Shelves shall be located 40 inches
(1015 mm) minimum and 48 inches (1220 mm) maximum above the finish floor. |
|
ANSI
603.4 Coat Hooks and Shelves. Coat hooks shall be located
within one of the reach ranges specified in Section 308. Shelves shall be 40
inches (1015 mm) minimum and 48 inches (1220 mm) maximum above the floor. |
||
604
Water Closets and Toilet Compartments |
ANSI
604 Water Closets and Toilet Compartments |
|||
4.17
Toilet Stalls. |
||||
604.1
General. Water closets and toilet compartments shall
comply with 604.2 through 604.8. EXCEPTION: Water
closets and toilet compartments for children's use shall be permitted to
comply with 604.9. |
4.16.1
General. Accessible water closets shall comply with
4.16.2 through 4.16.6. See also Appendix 4.16.1 |
ANSI
604.1 General. Accessible water closets and toilet compartments
shall comply with Section 604. Compartments containing more than one plumbing
fixture shall comply with Section 603. Wheelchair accessible compartments
shall comply with Section 604.8. Ambulatory accessible compartments shall
comply with Section 604.9. EXCEPTION:
Water closets and toilet compartments primarily for children’s use shall be
permitted to comply with Section 604.10 as applicable. |
||
4.17.1
Location. Accessible toilet stalls shall be on an
accessible route and shall meet the requirements of 4.17.2 through 4.17.6. 4.17.2
Water Closets. Water closets in accessible stalls shall comply
with 4.16. See also Appendix 4.17.1 |
||||
604.2
Location. The water closet shall be positioned with a wall
or partition to the rear and to one side. The centerline of the water closet
shall be 16 inches (405 mm) minimum to 18 inches (455 mm) maximum from the
side wall or partition, except that the water closet shall be 17 inches (430
mm) minimum and 19 inches (485 mm) maximum from the side wall or partition in
the ambulatory accessible toilet compartment specified in 604.8.2. Water
closets shall be arranged for a left-hand or right-hand approach. |
4.16.2 Clear Floor Space.
Clear floor space for water closets not in stalls shall comply with Fig. 28.
Clear floor space may be arranged to allow either a left-handed or
right-handed approach. NOTE: Figure 28 shows that for a front transfer to the
water closet, the minimum clear floor space at the water closet is a minimum
48 inches (1220 mm) in width by a minimum of 66 inches (1675 mm) in length.
For a diagonal transfer to the water closet, the minimum clear floor space is
a minimum of 48 inches (1220 mm) in width by a minimum of 56 inches (1420 mm)
in length. For a side transfer to the water closet, the minimum clear floor
space is a minimum of 60 inches (1525 mm) in width by a minimum of 56 inches
(1420 mm) in length. (4.16.2, A4.22.3) |
ANSI
604.2 Location. The water closet shall be located with a wall or
partition to the rear and to one side. The centerline of the water closet
shall be 16 inches (405 mm) minimum to 18 inches (455 mm) maximum from the
side wall or partition. Water closets located in ambulatory accessible
compartments specified in Section 604.9 shall have the centerline of the
water closet 17 inches (430 mm) minimum to 19 inches (485 mm) maximum from
the side wall or partition. |
||
604.3
Clearance. Clearances around water closets and in toilet
compartments shall comply with 604.3. |
ANSI
604.3 Clearance. |
|||
604.3.1
Size. Clearance around a water closet shall be 60 inches (1525 mm) minimum
measured perpendicular from the side wall and 56 inches (1420 mm) minimum
measured perpendicular from the rear wall. |
ANSI
604.3.1 Size. A clearance around a water closet 60 inches
(1525 mm) minimum, measured perpendicular from the sidewall, and 56 inches
(1420 mm) minimum, measured perpendicular from the rear wall, shall be
provided. |
|||
604.3.2
Overlap. The required clearance around the water closet
shall be permitted to overlap the water closet, associated grab bars,
dispensers, sanitary napkin disposal units, coat hooks, shelves, accessible
routes, clear floor space and clearances required at other fixtures, and the
turning space. No other fixtures or obstructions shall be located within the
required water closet clearance. EXCEPTION: In
residential dwelling units, a lavatory complying with 606 shall be permitted
on the rear wall 18 inches (455 mm) minimum from the water closet centerline
where the clearance at the water closet is 66 inches (1675 mm) minimum
measured perpendicular from the rear wall. |
ANSI
604.3.2 Overlap. The required clearance around the water closet
shall be permitted to overlap the water closet, associated grab bars, paper
dispensers, sanitary napkin receptacles, coat hooks, shelves, accessible
routes, clear floor space at other fixtures and the turning space. No other
fixtures or obstructions shall be within the required water closet clearance. |
|||
604.4
Seats. The seat height of a water closet above the
finish floor shall be 17 inches (430 mm) minimum and 19 inches (485 mm)
maximum measured to the top of the seat. Seats shall not be sprung to return
to a lifted position. EXCEPTIONS:
1. A water closet in a toilet room for a single
occupant accessed only through a private office and not for common use or
public use shall not be required to comply with 604.4. 2. In residential dwelling units, the height of
water closets shall be permitted to be 15 inches (380 mm) minimum and 19
inches (485 mm) maximum above the finish floor measured to the top of the
seat. |
4.16.3 Height. The height of
water closets shall be 17 in to 19 in (430 mm to 485 mm), measured to the top
of the toilet seat (see Fig. 29(b)). Seats shall not be sprung to return to a
lifted position. Note: In Figure 29(b) the top of the seat of the
water closet is 17 in to 19 in (430 mm to 485 mm). |
ANSI
604.4 Height. The height of water closet seats shall be 17
inches (430 mm) minimum and 19 inches (485 mm) maximum above the floor,
measured to the top of the seat. Seats shall not be sprung to return to a
lifted position. EXCEPTION: A
water closet in a toilet room for a single occupant, accessed only through a
private office and not for common use or public use, shall not be required to
comply with Section 604.4. |
||
604.5
Grab Bars. Grab bars for water closets shall comply with
609. Grab bars shall be provided on the side wall closest to the water closet
and on the rear wall. EXCEPTIONS: 1. Grab bars shall not be required to be
installed in a toilet room for a single occupant accessed only through a
private office and not for common use or public use provided that
reinforcement has been installed in walls and located so as to permit the
installation of grab bars complying with 604.5. 2. In residential dwelling units, grab bars shall
not be required to be installed in toilet or bathrooms provided that
reinforcement has been installed in walls and located so as to permit the
installation of grab bars complying with 604.5. 3. In detention or correction facilities, grab
bars shall not be required to be installed in housing or holding cells that
are specially designed without protrusions for purposes of suicide
prevention. |
4.16.4 Grab Bars.
Grab bars for water closets not located in stalls shall comply with 4.26 and
Fig. 29. The grab bar behind the water closet shall be 36 in (915 mm)
minimum. |
ANSI
604.5 Grab Bars. Grab bars for water closets shall comply with
Section 609 and shall be provided in accordance with Sections 604.5.1 and
604.5.2. Grab bars shall be provided on the rear wall and on the side wall
closest to the water closet. EXCEPTIONS: 1. Grab bars are not required to be installed in
a toilet room for a single occupant, accessed only through a private office
and not for common use or public use, provided reinforcement has been
installed in walls and located so as to permit the installation of grab bars
complying with Section 604.5. 2. In
detention or correction facilities, grab bars are not required to be
installed in housing or holding cells or rooms that are specially designed
without protrusions for purposes of suicide prevention. 3. In Type
A units, grab bars are not required to be installed where reinforcement
complying with Section 1003.11.4 is installed for the future installation of
grab bars. 4. In Type B units located in institutional
facilities and assisted living facilities, two swing–up grab bars shall be
permitted to be installed in lieu of the rear wall and side wall grab bars.
Swing–up grab bars shall comply with Sections 604.5.3 and 609. 5. In a Type B unit, where fixtures are located
on both sides of the water closet, a swing–up grab bar complying with
Sections 604.5.3 and 609 shall be permitted. The swing–up grab bar shall be
installed on the side of the water closet with the 18 inch (455 mm) clearance
required by Section 1004.11.3.1.2. |
||
604.5.1
Side Wall. The side wall grab bar shall be 42 inches (1065
mm) long minimum, located 12 inches (305 mm) maximum from the rear wall and
extending 54 inches (1370 mm) minimum from the rear wall. |
Note: In Figure 29(a) a 36 inches (915 mm)
minimum length grab bar, mounted 33-36 inches (840-915 mm) above the finish
floor, is required behind the water closet. The grab bar must extend at least
12 inches (305 mm) from the centerline of the water closet toward the side
wall and at least 24 inches (610 mm) from the centerline of the water closet
toward the open side. In Figure 29(b) a 42 inch
(1065 mm) minimum length grab bar is required to the side of the water closet
spaced 12 inches (305 mm) maximum from the back wall and extending a minimum
of 54 inches (1370 mm) from the back wall at a height between 33 and 36
inches (840-915 mm). The toilet paper dispenser shall be mounted at a minimum
height of 19 inches (485 mm). (4.16.3, 4.16.4, 4.16.6) |
ANSI
604.5.1 Fixed Side Wall Grab Bars. Fixed sidewall grab bars
shall be 42 inches (1065 mm) minimum in length, located 12 inches (305 mm)
maximum from the rear wall and extending 54 inches (1370 mm) minimum from the
rear wall. In addition, a vertical grab bar 18 inches (455 mm) minimum in
length shall be mounted with the bottom of the bar located between 39 inches
(990 mm) and 41 inches (1040 mm) above the floor, and with the center line of
the bar located between 39 inches (990 mm) and 41 inches (1040 mm) from the
rear wall. EXCEPTIONS: 1. In Type A and Type B units, the vertical grab
bar component is not required. 2. In a Type B unit, when a side wall is not
available for a 42–inch (1065 mm) grab bar, the sidewall grab bar shall be
permitted to be 18 inches (455 mm)
minimum in length, located 12 inches (305 mm) maximum from the rear wall and
extending 30 inches (760 mm) minimum from the rear wall. |
||
604.5.2
Rear Wall. The rear wall grab bar shall be 36 inches (915
mm) long minimum and extend from the centerline of the water closet 12 inches
(305 mm) minimum on one side and 24 inches (610 mm) minimum on the other
side. EXCEPTIONS: 1. The rear grab bar shall be permitted to be 24
inches (610 mm) long minimum, centered on the water closet, where wall space
does not permit a length of 36 inches (915 mm) minimum due to the location of
a recessed fixture adjacent to the water closet. 2. Where an administrative authority requires
flush controls for flush valves to be located in a position that conflicts
with the location of the rear grab bar, then the rear grab bar shall be
permitted to be split or shifted to the open side of the toilet area. |
NOTE: In Figure 29(a) a 36 inch (915 mm) minimum length
grab bar is required behind the water closet mounted at a height between 33
and 36 inches (840-915 mm). The grab bar must extend a minimum of 12 inches
(305) beyond the center of the water closet toward the side wall and a
minimum of 24 inches (610 mm) toward the open side for either a left or right
side approach. Figure 30(c) indicates the
grab bar on the back wall shall be 36 inches minimum in length, extending
from the wall toward the open side of the water closet, 33-36 inches above
the finish floor. |
ANSI
604.5.2 Rear Wall Grab Bars. The rear wall grab bar shall
be 36 inches (915 mm) minimum in length, and extend from the centerline of
the water closet 12 inches (305 mm) minimum on the side closest to the wall,
and 24 inches (610 mm) minimum on the transfer side. EXCEPTIONS: 1. The rear grab bar shall be permitted to be 24
inches (610 mm) minimum in length, centered on the water closet, where wall
space does not permit a grab bar 36 inches (915 mm) minimum in length due to
the location of a recessed fixture adjacent to the water closet. 2. In a Type A or Type B unit, the rear grab bar
shall be permitted to be 24 inches (610 mm) minimum in length, centered on
the water closet, where wall space does not permit a grab bar 36 inches (915
mm) minimum in length. 3. Where an administrative authority requires
flush controls for flush valves to be located in a position that conflicts
with the location of the rear grab bar, that grab bar shall be permitted to
be split or shifted to the open side of the toilet area. |
||
|
|
ANSI
604.5.3 Swing–up Grab Bars. Where swing–up grab bars are
installed, a clearance of 18 inches (455 mm) minimum from the centerline of
the water closet to any side wall or obstruction shall be provided. A
swing–up grab bar shall be installed with the centerline of the grab bar
153/4 inches (400 mm) from the centerline of the water closet. Swing–up grab
bars shall be 28 inches (710 mm) minimum in length, measured from the wall to
the end of the horizontal portion of the grab bar. |
||
604.6
Flush Controls. Flush controls shall be hand operated or
automatic. Hand operated flush controls shall comply with 309. Flush controls
shall be located on the open side of the water closet except in ambulatory
accessible compartments complying with 604.8.2. |
4.16.5 Flush Controls. Flush
controls shall be hand operated or automatic and shall comply with 4.27.4.
Controls for flush valves shall be mounted on the wide side of toilet areas
no more than 44 in (1120 mm) above the floor. |
ANSI
604.6 Flush Controls. Flush controls shall be hand operated or
automatic. Hand operated flush controls shall comply with Section 309. Flush
controls shall be located on the open side of the water closet. EXCEPTION: In
ambulatory accessible compartments complying with Section 604.9, flush
controls shall be permitted to be located on either side of the water closet. |
||
604.7
Dispensers. Toilet
paper dispensers shall comply with 309.4 and shall be 7 inches (180 mm)
minimum and 9 inches (230 mm) maximum in front of the water closet measured
to the centerline of the dispenser. The outlet of the dispenser shall be 15
inches (380 mm) minimum and 48 inches (1220 mm) maximum above the finish
floor and shall not be located behind grab bars. Dispensers shall not be of a
type that controls delivery or that does not allow continuous paper flow. |
4.16.6 Dispensers. Toilet
paper dispensers shall be installed within reach, as shown in Fig. 29(b).
Dispensers that control delivery, or that do not permit continuous paper
flow, shall not be used. NOTE: In
Figure 29(b) the toilet paper dispenser is required to be mounted at a
minimum height of 19 inches (485 mm). (4.16.3, 4.16.4, 4.16.6) |
ANSI
604.7 Dispensers. Toilet paper dispensers shall comply with
Section 309.4 and shall be 7 inches (180 mm) minimum and 9 inches (230 mm)
maximum in front of the water closet measured to the centerline of the
dispenser. The outlet of the dispenser shall be 15 inches (380 mm) minimum
and 48 inches (1220 mm) maximum above the floor, and shall not be located
behind the grab bars. Dispensers shall not be of a type that control
delivery, or do not allow continuous paper flow. |
||
604.8
Toilet Compartments. Wheelchair accessible toilet
compartments shall meet the requirements of 604.8.1 and 604.8.3. Compartments
containing more than one plumbing fixture shall comply with 603. Ambulatory
accessible compartments shall comply with 604.8.2 and 604.8.3. |
|
|
||
604.8.1
Wheelchair Accessible Compartments. Wheelchair accessible
compartments shall comply with 604.8.1. |
|
ANSI
604.8 Wheelchair Accessible Compartments. |
||
ANSI
604.8.1 General. Wheelchair accessible compartments shall comply
with Section 604.8. |
||||
604.8.1.1
Size. Wheelchair accessible compartments shall be 60
inches (1525 mm) wide minimum measured perpendicular to the side wall, and 56
inches (1420 mm) deep minimum for wall hung water closets and 59 inches (1500
mm) deep minimum for floor mounted water closets measured perpendicular to
the rear wall. Wheelchair accessible compartments for children's use shall be
60 inches (1525 mm) wide minimum measured perpendicular to the side wall, and
59 inches (1500 mm) deep minimum for wall hung and floor mounted water
closets measured perpendicular to the rear wall. |
4.17.3 Size
and Arrangement. The size and arrangement of the standard toilet stall
shall comply with Fig. 30(a), Standard Stall. Standard toilet stalls with a
minimum depth of 56 in (1420 mm) (see Fig. 30(a)) shall have wall-mounted
water closets. If the depth of a standard toilet stall is increased at least
3 in (75 mm), then a floor-mounted water closet may be used. Arrangements
shown for standard toilet stalls may be reversed to allow either a left- or
right-hand approach. Additional stalls shall be provided in conformance with
4.22.4. EXCEPTION: In instances of alteration
work where provision of a standard stall (Fig. 30(a)) is technically
infeasible or where plumbing code requirements prevent combining existing
stalls to provide space, either alternate stall (Fig. 30(b)) may be provided
in lieu of the standard stall. NOTE: In Figure 30(a), the location of the door is illustrated to be in
front of the clear space (next to the water closet), with a maximum stile
width of 4 inches (100 mm). An alternate door location is illustrated to be
on the side of the toilet stall with a maximum stile width of 4 inches (100
mm). The minimum width of the standard stall shall be 60 inches (1525 mm).
The centerline of the water closet shall be 18 inches (455 mm) from the side
wall. Figure 30(a-1) indicates that where a standard stall is provided at
the end of a row of stalls, the door (if located on the side of the stall)
may swing into to the stall, if the length of the stall is extended at least
a minimum of 36 inches (915 mm) beyond the required minimum length. In
Figure 30(b), two alternate stalls are
illustrated; one alternate stall is required to be 36 inches (915 mm) in
width. The other alternate stall is required to be a minimum of 48 inches
(1220 mm) in width. If a wall mounted water closet is used, the depth of the
stall is required to be a minimum of 66 inches (1675 mm). If a floor mounted
water closet is used, the depth of the stall is required to be a minimum of
69 inches (1745 mm). The 36 inch wide stall shall have parallel grab bars on
the side walls. The 48 inch minimum stall shall have a grab bar behind the
water closet and one on the side wall next to the water closet. In each
alternate, the centerline of the water closet is 18 inches (455 mm) from a
side wall. |
ANSI
604.8.2 Size. The minimum area of a wheelchair accessible
compartment shall be 60 inches (1525 mm) minimum in width measured
perpendicular to the side wall, and 56 inches (1420 mm) minimum in depth for wall
hung water closets, and 59 inches (1500 mm) minimum in depth for floor
mounted water closets measured perpendicular to the rear wall. The minimum
area of a wheelchair accessible compartment for primarily children’s use
shall be 60 inches (1525 mm) minimum in width measured perpendicular to the
side wall, and 59 inches (1500 mm) minimum in depth for wall hung and floor
mounted water closets measured perpendicular to the rear wall. |
||
604.8.1.2
Doors. Toilet compartment doors, including door hardware,
shall comply with 404 except that if the approach is to the latch side of the
compartment door, clearance between the door side of the compartment and any
obstruction shall be 42 inches (1065 mm) minimum. Doors shall be located in
the front partition or in the side wall or partition farthest from the water
closet. Where located in the front partition, the door opening shall be 4
inches (100 mm) maximum from the side wall or partition farthest from the
water closet. Where located in the side wall or partition, the door opening
shall be 4 inches (100 mm) maximum from the front partition. The door shall
be self-closing. A door pull complying with 404.2.7 shall be placed on both
sides of the door near the latch. Toilet compartment doors shall not swing
into the minimum required compartment area. |
4.17.5 Doors.
Toilet stall doors, including door hardware, shall comply with 4.13. If
toilet stall approach is from the latch side of the stall door, clearance
between the door side of the stall and any obstruction may be reduced to a
minimum of 42 in (1065 mm) (Fig. 30). |
ANSI
604.8.3 Doors. Toilet compartment doors, including door
hardware, shall comply with Section 404.1, except if the approach is to the
latch side of the compartment door clearance between the door side of the
stall and any obstruction shall be 42 inches (1065 mm) minimum. Doors shall
be located in the front partition or in the side wall or partition farthest
from the water closet. Where located in the front partition, the door opening
shall be 4 inches (100 mm) maximum from the side wall or partition farthest
from the water closet. Where located in the side wall or partition, the door
opening shall be 4 inches (100 mm) maximum from the front partition. The door
shall be self–closing. A door pull complying with Section 404.2.6 shall be
placed on both sides of the door near the latch. Toilet compartment doors
shall not swing into the required minimum area of the compartment. |
||
604.8.1.3
Approach. Compartments shall be arranged for left-hand or
right-hand approach to the water closet. |
See 4.17.3 |
ANSI
604.8.4 Approach. Wheelchair accessible compartments shall be
arranged for left–hand or right–hand approach to the water closet. |
||
604.8.1.4
Toe Clearance. The front partition and at least one side
partition shall provide a toe clearance of 9 inches (230 mm) minimum above
the finish floor and 6 inches (150 mm) deep minimum beyond the
compartment-side face of the partition, exclusive of partition support
members. Compartments for children's use shall provide a toe clearance of 12
inches (305 mm) minimum above the finish floor. EXCEPTION: Toe
clearance at the front partition is not required in a compartment greater
than 62 inches (1575 mm) deep with a wall-hung water closet or 65 inches
(1650 mm) deep with a floor-mounted water closet. Toe clearance at the side
partition is not required in a compartment greater than 66 inches (1675 mm)
wide. Toe clearance at the front partition is not required in a compartment
for children's use that is greater than 65 inches (1650 mm) deep. |
4.17.4 Toe Clearances. In
standard stalls, the front partition and at least one side partition shall
provide a toe clearance of at least 9 in (230 mm) above the floor. If the depth
of the stall is greater than 60 in (1525 mm), then the toe clearance is not
required. |
ANSI
604.8.5 Toe Clearance. The front partition and at least one
side partition shall provide a toe clearance of 9 inches (230 mm) minimum
above the floor and extending 6 inches (150 mm) beyond the compartment side
face of the partition, exclusive of partition support members. Compartments
primarily for children’s use shall provide a toe clearance of 12 inches (305
mm) minimum above the floor and extending 6 inches (150 mm) beyond the
compartment side face of the partition, exclusive of partition support
members. EXCEPTIONS: 1. Toe clearance at the front partition is not
required in a compartment greater than 62 inches (1575 mm) in depth with a
wall–hung water closet, or greater than 65 inches (1650 mm) in depth with a
floor–mounted water closet. In a compartment primarily for children’s use,
greater than 65 inches (1650 mm) in depth, toe clearance at the front
partition is not required. 2. Toe clearance at the side partition is not
required in a compartment greater than 66 inches (1675 mm) in width. |
||
604.8.1.5
Grab Bars. Grab bars shall comply with 609. A side-wall grab
bar complying with 604.5.1 shall be provided and shall be located on the wall
closest to the water closet. In addition, a rear-wall grab bar complying with
604.5.2 shall be provided. |
4.17.6 Grab Bars.
Grab bars complying with the length and positioning shown in Fig. 30(a), (b),
(c), and (d) shall be provided. Grab bars may be mounted with any desired
method as long as they have a gripping surface at the locations shown and do
not obstruct the required clear floor area. Grab bars shall comply with 4.26.
NOTE:
Figure 30(c) indicates grab
bars located behind the water closet shall be at least 36 inches (915 mm) in
length. One end of the grab bar is shown near the corner of the stall closest
to the water closet. Figure 30(a) shows this end 6 inches (150 mm) maximum
from the corner. All grab bars shall be located 33-36 inches (840-915 mm)
above the finish floor. |
ANSI
604.8.6 Grab Bars. Grab bars shall comply with Section 609. Side
wall grab bars complying with Section 604.5.1 located on the wall closest to
the water closet, and a rear wall grab bar complying with Section 604.5.2,
shall be provided. |
||
604.8.2
Ambulatory Accessible Compartments. Ambulatory accessible
compartments shall comply with 604.8.2. |
|
ANSI
604.9 Ambulatory Accessible Compartments. |
||
ANSI
604.9.1 General. Ambulatory accessible compartments shall comply
with Section 604.9. |
||||
604.8.2.1
Size. Ambulatory accessible compartments shall have a depth of 60 inches
(1525 mm) minimum and a width of 35 inches (890 mm) minimum and 37 inches
(940 mm) maximum. |
4.22.4 Water Closets. If toilet stalls are
provided, then at least one shall be a standard toilet stall complying with
4.17; where 6 or more stalls are provided, in addition to the stall complying
with 4.17.3, at least one stall 36 in (915 mm) wide with an outward swinging,
self-closing door and parallel grab bars complying with Fig. 30(d) and 4.26
shall be provided. Water closets in such stalls shall comply with 4.16. If
water closets are not in stalls, then at least one shall comply with 4.16. |
ANSI
604.9.2 Size. The minimum area of an ambulatory accessible
compartment shall be 60 inches (1525 mm) minimum in depth and 36 inches (915
mm) in width. |
||
604.8.2.2
Doors. Toilet compartment doors, including door
hardware, shall comply with 404, except that if the approach is to the latch
side of the compartment door, clearance between the door side of the
compartment and any obstruction shall be 42 inches (1065 mm) minimum. The
door shall be self-closing. A door pull complying with 404.2.7 shall be
placed on both sides of the door near the latch. Toilet compartment doors
shall not swing into the minimum required compartment area. |
|
ANSI
604.9.3 Doors. Toilet compartment doors, including door
hardware, shall comply with Section 404, except if the approach is to the
latch side of the compartment door the clearance between the door side of the
compartment and any obstruction shall be 42 inches (1065 mm) minimum. The
door shall be self–closing. A door pull complying with Section 404.2.6 shall
be placed on both sides of the door near the latch. Compartment doors shall
not swing into the required minimum area of the compartment. |
||
604.8.2.3
Grab Bars. Grab bars shall comply with 609. A side-wall
grab bar complying with 604.5.1 shall be provided on both sides of the
compartment. |
NOTE: Figure 30(d) indicates the side grab bar shall
be 40-42 inches in length, beginning 12 inches maximum from the rear wall,
33-36 inches above the finish floor. |
ANSI
604.9.4 Grab Bars. Grab bars shall comply with Section 609. Side wall
grab bars complying with Section 604.5.1 shall be provided on both sides of
the compartment. |
||
604.8.3
Coat Hooks and Shelves. Coat hooks shall be located within one
of the reach ranges specified in 308. Shelves shall be located 40 inches
(1015 mm) minimum and 48 inches (1220 mm) maximum above the finish floor. |
|
ANSI
604.11 Coat Hooks and Shelves. Coat hooks provided within
toilet compartments shall be 48 inches (1220 mm) maximum above the floor.
Shelves shall be 40 inches (1015 mm) minimum and 48 inches (1220 mm) maximum
above the floor. |
||
604.9
Water Closets and Toilet Compartments for Children's Use.
Water closets and toilet compartments for children's use shall comply with
604.9. |
See Appendix 4.16.7 and Appendix 4.17.7 |
ANSI
604.10 Water Closets and Toilet Compartments for Children’s Use. |
||
ANSI
604.10.1 General. Accessible water closets and toilet compartments
primarily for children’s use shall comply with Section 604.10. |
||||
604.9.1
Location. The water closet shall be located with a wall or
partition to the rear and to one side. The centerline of the water closet
shall be 12 inches (305 mm) minimum and 18 inches (455 mm) maximum from the
side wall or partition, except that the water closet shall be 17 inches (430
mm) minimum and 19 inches (485 mm) maximum from the side wall or partition in
the ambulatory accessible toilet compartment specified in 604.8.2.
Compartments shall be arranged for left-hand or right-hand approach to the
water closet. |
ANSI
604.10.2 Location. The water closet shall be located with a wall or
partition to the rear and to one side. The centerline of the water closet
shall be 12 inches (305 mm) minimum to 18 inches (455 mm) maximum from the
side wall or partition. Water closets located in ambulatory accessible toilet
compartments specified in Section 604.9 shall be located as specified in
Section 604.2. |
|||
604.9.2
Clearance. Clearance around a water closet shall comply
with 604.3. |
ANSI
604.10.3 Clearance. A clearance around a water closet complying with
Section 604.3 shall be provided. |
|||
604.9.3
Height. The height of water closets shall be 11 inches
(280 mm) minimum and 17 inches (430 mm) maximum measured to the top of the
seat. Seats shall not be sprung to return to a lifted position. |
ANSI
604.10.4 Height. The height of water closet seats shall be 11
inches (280 mm) minimum and 17 inches (430 mm) maximum above the floor,
measured to the top of the seat. Seats shall not be sprung to return to a
lifted position. |
|||
604.9.4
Grab Bars. Grab bars for water closets shall comply with
604.5. |
ANSI
604.10.5 Grab Bars. Grab bars for water closets shall comply with
Section 604.5. |
|||
604.9.5
Flush Controls. Flush controls shall be hand operated or
automatic. Hand operated flush controls shall comply with 309.2 and 309.4 and
shall be installed 36 inches (915 mm) maximum above the finish floor. Flush
controls shall be located on the open side of the water closet except in
ambulatory accessible compartments complying with 604.8.2. |
ANSI
604.10.6 Flush Controls. Flush controls shall be hand operated or
automatic. Hand operated flush controls shall comply with Sections 309.2 and
309.4 and shall be installed 36 inches (915 mm) maximum above the floor.
Flush controls shall be located on the open side of the water closet. EXCEPTION:
In ambulatory accessible compartments complying with Section 604.9, flush
controls shall be permitted to be located on either side of the water closet. |
|||
604.9.6
Dispensers. Toilet paper dispensers shall comply with 309.4
and shall be 7 inches (180 mm) minimum and 9 inches (230 mm) maximum in front
of the water closet measured to the centerline of the dispenser. The outlet
of the dispenser shall be 14 inches (355 mm) minimum and 19 inches (485 mm)
maximum above the finish floor. There shall be a clearance of 1 1/2 inches
(38 mm) minimum below the grab bar. Dispensers shall not be of a type that
controls delivery or that does not allow continuous paper flow. |
ANSI
604.10.7 Dispensers. Toilet paper dispensers shall comply
with Section 309.4 and shall be 7 inches (180 mm) minimum and 9 inches (230
mm) maximum in front of the water closet measured to the center line of the
dispenser. The outlet of the dispenser shall be 14 inches (355 mm) minimum
and 19 inches (485 mm) maximum above the floor. There shall be a clearance of
1 1/2 inches (38 mm) minimum below the grab bar. Dispensers shall not be of a
type that control delivery or do not allow continuous paper flow. |
|||
604.9.7
Toilet Compartments. Toilet compartments shall comply with
604.8. |
ANSI
604.10.8 Toilet Compartments. Toilet compartments shall
comply with Sections 604.8 and 604.9, as applicable. |
|||
605 Urinals |
4.18 Urinals.
|
ANSI
605 Urinals |
||
605.1
General. Urinals shall comply with 605. |
4.18.1
General. Accessible urinals shall comply with 4.18. |
ANSI
605.1 General. Accessible urinals shall comply with Section 605. |
||
605.2
Height and Depth. Urinals shall be the stall-type or the wall-hung
type with the rim 17 inches (430 mm) maximum above the finish floor or
ground. Urinals shall be 13 1/2 inches (345 mm) deep minimum measured from
the outer face of the urinal rim to the back of the fixture. |
4.18.2 Height. Urinals
shall be stall-type or wall-hung with an elongated rim at a maximum of 17 in
(430 mm) above the finish floor. |
ANSI
605.2 Height. Urinals shall be of the stall type or shall be
of the wall hung type with the rim at 17 inches (430 mm) maximum above the
floor. |
||
605.3
Clear Floor Space. A clear floor or ground space complying with 305
positioned for forward approach shall be provided. |
4.18.3 Clear
Floor Space. A clear floor space 30 in by 48 in (760 mm by 1220 mm) shall
be provided in front of urinals to allow forward approach. This clear space
shall adjoin or overlap an accessible route and shall comply with 4.2.4.
Urinal shields that do not extend beyond the front edge of the urinal rim may
be provided with 29 in (735 mm) clearance between them. |
ANSI
605.3 Clear Floor Space. A clear floor space complying with
Section 305, positioned for forward approach, shall be provided. |
||
605.4
Flush Controls. Flush controls shall be hand operated or
automatic. Hand operated flush controls shall comply with 309. |
4.18.4 Flush
Controls. Flush controls shall be hand operated or automatic, and shall
comply with 4.27.4, and shall be mounted no more than 44 in (1120 mm) above
the finish floor |
ANSI
605.4 Flush Controls. Flush controls shall be hand operated or
automatic. Hand operated flush controls shall comply with Section 309. |
||
606
Lavatories and Sinks |
4.19
Lavatories and Mirrors. |
ANSI
606 Lavatories and Sinks |
||
4.24
Sinks. |
||||
606.1
General. Lavatories and sinks shall comply with 606. |
4.19.1 General.
The requirements of 4.19 shall apply to lavatory fixtures, vanities, and
built-in lavatories. |
ANSI
606.1 General. Accessible lavatories and sinks shall comply
with Section 606. |
||
4.24.1 General. Sinks
required to be accessible by 4.1 shall comply with 4.24. |
||||
606.2
Clear Floor Space. A clear floor space complying with 305,
positioned for a forward approach, and knee and toe clearance complying with
306 shall be provided. EXCEPTIONS: 1. A parallel approach complying with 305 shall
be permitted to a kitchen sink in a space where a cook top or conventional
range is not provided and to wet bars. 2. A lavatory in a toilet room or bathing
facility for a single occupant accessed only through a private office and not
for common use or public use shall not be required to provide knee and toe
clearance complying with 306. 3. In residential dwelling units, cabinetry shall
be permitted under lavatories and kitchen sinks provided that all of the
following conditions are met: (a) the cabinetry can be removed without removal
or replacement of the fixture; (b) the finish floor extends under the cabinetry;
and (c) the walls behind and surrounding the
cabinetry are finished. 4. A knee clearance of
24 inches (610 mm) minimum above the finish floor or ground shall be
permitted at lavatories and sinks used primarily by children 6 through 12
years where the rim or counter surface is 31 inches (785 mm) maximum above
the finish floor or ground. 5. A parallel approach complying with 305 shall
be permitted to lavatories and sinks used primarily by children 5 years and
younger. 6. The dip of the overflow shall not be
considered in determining knee and toe clearances. 7. No more than one bowl of a multi-bowl sink
shall be required to provide knee and toe clearance complying with 306. |
4.19.3 Clear Floor Space. A
clear floor space 30 in by 48 in (760 mm by 1220 mm) complying with 4.2.4
shall be provided in front of a lavatory to allow forward approach. Such
clear floor space shall adjoin or overlap an accessible route and shall
extend a maximum of 19 in (485 mm) underneath the lavatory (see Fig. 32). NOTE: Figure
32 indicates the minimum depth of the lavatory is 17 inches (430 mm).
(4.19.3, 4.24.5) |
ANSI
606.2 Clear Floor Space. A clear floor space complying with
Section 305.3, positioned for forward approach, shall be provided. Knee and
toe clearance complying with Section 306 shall be provided. The dip of the
overflow shall not be considered in determining knee and toe clearances. EXCEPTIONS:
1. A parallel approach complying with Section 305
shall be permitted to a kitchen sink in a space where a cook top or conventional
range is not provided. 2. The requirement for knee and toe clearance
shall not apply to a lavatory in a toilet and bathing facility for a single
occupant, accessed only through a private office and not for common use or
public use. 3. A knee clearance of 24 inches (610 mm) minimum
above the floor shall be permitted at lavatories and sinks used primarily by
children ages 6 through 12 where the rim or counter surface is 31 inches (785
mm) maximum above the floor. 4. A parallel approach complying with Section 305
shall be permitted at lavatories and sinks used primarily by children ages 5
and younger. 5. The requirement for knee and toe clearance
shall not apply to more than one bowl of a multibowl sink. 6. A parallel approach shall be permitted at wet
bars. |
||
4.24.5 Clear Floor Space. A clear floor space at
least 30 in by 48 in (760 mm by 1220 mm) complying with 4.2.4 shall be
provided in front of a sink to allow forward approach. The clear floor space
shall be on an accessible route and shall extend a maximum of 19 in (485 mm)
underneath the sink (see Fig. 32). |
||||
4.24.3 Knee
Clearance. Knee clearance that is at least 27 in (685 mm)
high, 30 in (760 mm) wide, and 19 in (485 mm) deep shall be provided
underneath sinks. See also Appendix 4.19.2 EXCEPTIONS |
||||
606.3
Height. Lavatories and sinks shall be installed with the
front of the higher of the rim or counter surface 34 inches (865 mm) maximum
above the finish floor or ground. EXCEPTIONS: 1. A lavatory in a toilet or bathing facility for
a single occupant accessed only through a private office and not for common
use or public use shall not be required to comply with 606.3. 2. In residential dwelling unit kitchens, sinks
that are adjustable to variable heights, 29 inches (735 mm) minimum and 36
inches (915 mm) maximum, shall be permitted where rough-in plumbing permits
connections of supply and drain pipes for sinks mounted at the height of 29
inches (735 mm). |
4.19.2 Height
and Clearances. Lavatories shall be mounted with the rim or counter
surface no higher than 34 in (865 mm) above the finish floor. Provide a
clearance of at least 29 in (735 mm) above the finish floor to the bottom of
the apron. Knee and toe clearance shall comply with Fig. 31. NOTE: Figure
31 indicates that, in addition to clearances discussed in the text, the
following knee clearance is required underneath the lavatory: 27 inches (685
mm) minimum from the floor to the underside of the lavatory which extends 8
inches (205 mm) minimum measured from the front edge underneath the lavatory
back towards the wall; if a minimum 9 inches (230 mm) of toe clearance is
provided, a maximum of 6 inches (150 mm) of the 48 inches (1220 mm) of clear
floor space required at the fixture may extend into the toe space. (4.19.2, 4.19.6). Additionally, the figure shows a vertical
clearance of 29 inches (735 mm) to the underside of the lavatory apron. |
ANSI
606.3 Height. The front of lavatories and sinks shall be 34
inches (865 mm) maximum above the floor, measured to the higher of the rim or
counter surface. EXCEPTION: A lavatory in a toilet and bathing facility
for a single occupant, accessed only through a private office and not for
common use or public use, shall not be required to comply with Section 606.3. |
||
|
4.24.2 Height. Sinks shall
be mounted with the counter or rim no higher than 34 in (865 mm) above the
finish floor. |
|
||
|
4.24.4 Depth. Each sink
shall be a maximum of 6-1/2 in (165 mm) deep. |
|
||
606.4
Faucets. Controls for faucets shall comply with 309.
Hand-operated metering faucets shall remain open for 10 seconds minimum. |
4.19.5 Faucets. Faucets
shall comply with 4.27.4. Lever-operated, push-type, and electronically
controlled mechanisms are examples of acceptable designs. If self-closing
valves are used the faucet shall remain open for at least 10 seconds. |
ANSI
606.4 Faucets. Faucets shall comply with Section 309.
Hand–operated metering faucets shall remain open for 10 seconds minimum. |
||
4.24.7 Faucets. Faucets shall comply with
4.27.4. Lever-operated, push-type, touch-type, or electronically controlled
mechanisms are acceptable designs. |
||||
606.5
Exposed Pipes and Surfaces. Water supply and drain pipes
under lavatories and sinks shall be insulated or otherwise configured to
protect against contact. There shall be no sharp or abrasive surfaces under
lavatories and sinks. |
4.19.4 Exposed
Pipes and Surfaces. Hot water and drain pipes under lavatories shall be
insulated or otherwise configured to protect against contact. There shall be
no sharp or abrasive surfaces under lavatories. |
ANSI
606.6 Exposed Pipes and Surfaces. Water supply and drainpipes
under lavatories and sinks shall be insulated or otherwise configured to
protect against contact. There shall be no sharp or abrasive surfaces under
lavatories and sinks. |
||
4.24.6 Exposed Pipes and
Surfaces. Hot water and drain pipes exposed under sinks shall be
insulated or otherwise configured so as to protect against contact. There
shall be no sharp or abrasive surfaces under sinks. |
||||
|
|
ANSI
606.7 Operable Parts. Operable parts on towel dispensers and
hand dryers shall comply with Table 606.7. |
||
607
Bathtubs |
4.20
Bathtubs. |
ANSI
607 Bathtubs |
||
607.1
General. Bathtubs shall comply with 607. |
4.20.1 General. Accessible
bathtubs shall comply with 4.20. |
ANSI
607.1 General. Accessible bathtubs shall comply with Section
607. |
||
607.2
Clearance. Clearance in front of bathtubs shall extend the
length of the bathtub and shall be 30 inches (760 mm) wide minimum. A
lavatory complying with 606 shall be permitted at the control end of the
clearance. Where a permanent seat is provided at the head end of the bathtub,
the clearance shall extend 12 inches (305 mm) minimum beyond the wall at the
head end of the bathtub. |
4.20.2
Floor Space. Clear floor space in front of bathtubs shall be
as shown in Fig. 33. NOTE: Figure
33(a) indicates that, if the approach is parallel to the bathtub, a 30 inch
(760 mm) minimum width by 60 inch (1525 mm) minimum length clear space is
required alongside the bathtub. If the approach is perpendicular to the
bathtub, a 48 inch (1220 mm) minimum width by 60 inch (1525 mm) minimum
length clear space is required. Figure 33(b) indicates that,
if the approach is parallel to the bathtub with a seat at the head end, a 30
inch (760 mm) minimum width by 75 inch (1905 mm) minimum length clear space
is required alongside the bathtub. The seat width must be 15 inches (380 mm)
and must extend the full width of the bathtub. |
ANSI
607.2 Clearance. A clearance in front of bathtubs extending the
length of the bathtub and 30 inches (760 mm) minimum in depth shall be
provided. Where a permanent seat is provided at the head end of the bathtub,
the clearance shall extend 12 inches (305 mm) minimum beyond the wall at the
head end of the bathtub. |
||
607.3
Seat. A permanent seat at the head end of the bathtub or a removable in-tub
seat shall be provided. Seats shall comply with 610. |
4.20.3 Seat.
An in-tub seat or a seat at the head end of the tub shall be provided as
shown in Fig. 33 and 34. The structural strength of seats and their
attachments shall comply with 4.26.3. Seats shall be mounted securely and
shall not slip during use. |
ANSI
607.3 Seat. A permanent seat at the head end of the bathtub
or a removable in–tub seat shall be provided. Seats shall comply with Section
610. |
||
607.4
Grab Bars. Grab bars for bathtubs shall comply with 609 and
shall be provided in accordance with 607.4.1 or 607.4.2. EXCEPTIONS: 1. Grab bars shall not be required to be
installed in a bathtub located in a bathing facility for a single occupant
accessed only through a private office and not for common use or public use
provided that reinforcement has been installed in walls and located so as to
permit the installation of grab bars complying with 607.4. 2. In residential dwelling units, grab bars shall
not be required to be installed in bathtubs located in bathing facilities
provided that reinforcement has been installed in walls and located so as to
permit the installation of grab bars complying with 607.4. |
4.20.4 Grab Bars. Grab bars
complying with 4.26 shall be provided as shown in Fig. 33 and 34. |
ANSI
607.4 Grab Bars. Grab bars shall comply with Section 609 and
shall be provided in accordance with Section 607.4.1 or 607.4.2. EXCEPTIONS: 1. Grab bars shall not be required to be
installed in a bathing facility for a single occupant accessed only through a
private office and not for common use or public use, provided reinforcement
has been installed in walls and located so as to permit the installation of
grab bars complying with Section 607.4. 2. In Type A units, grab bars are not required to
be installed where reinforcement complying with Section 1003.11.9 is
installed for the future installation of grab bars. |
||
607.4.1
Bathtubs With Permanent Seats. For bathtubs with permanent
seats, grab bars shall be provided in accordance with 607.4.1. |
ANSI
607.4.1 Bathtubs with Permanent Seats. For bathtubs with permanent
seats, grab bars complying with Section 607.4.1 shall be provided. |
|||
607.4.1.1
Back Wall. Two grab bars shall be installed on the back
wall, one located in accordance with 609.4 and the other located 8 inches
(205 mm) minimum and 10 inches (255 mm) maximum above the rim of the bathtub.
Each grab bar shall be installed 15 inches (380 mm) maximum from the head end
wall and 12 inches (305 mm) maximum from the control end wall. |
NOTE: Figure
34(a) indicates at the foot of the tub, the grab bar shall be 24 inches (610
mm) minimum in length measured from the outer edge of the tub. On the back
wall, two grab bars are required. The grab bars mounted on the back (long)
wall shall be a minimum 24 inches (610 mm) in length located 12 inches (305
mm) maximum from the foot of the tub and 24 inches (610 mm) maximum from the
head of the tub. One grab bar shall be located 9 inches (230 mm) above the
rim of the tub. The others shall be 33 to 36 inches (840 mm to 910 mm) above
the bathroom floor. At the head of the tub, the grab bar shall be a minimum
of 12 inches (305 mm) in length measured from the outer edge of the tub. |
ANSI
607.4.1.1 Back Wall. Two horizontal grab bars shall be
provided on the back wall, one complying with Section 609.4 and the other 9
inches (230 mm) above the rim of the bathtub. Each grab bar shall be located
15 inches (380 mm) maximum from the head end wall and extend to 12 inches
(305 mm) maximum from the control end wall. |
||
607.4.1.2
Control End Wall. A grab bar 24 inches (610 mm) long minimum shall
be installed on the control end wall at the front edge of the bathtub. |
|
ANSI
607.4.1.2 Control End Wall. Control end wall grab bars
shall comply with Section 607.4.1.2. EXCEPTION: An L–shaped continuous grab bar of
equivalent dimensions and positioning shall be permitted to serve the
function of separate vertical and horizontal grab bars. |
||
|
|
ANSI
607.4.1.2.1 Horizontal Grab Bar. A horizontal grab bar 24
inches (610 mm) minimum in length shall be provided on the control end wall
at the front edge of the bathtub. |
||
|
|
ANSI
607.4.1.2.2 Vertical Grab Bar. A vertical grab bar 18
inches (455 mm) minimum in length shall be provided on the control end wall 3
inches (75 mm) minimum to 6 inches (150 mm) maximum above the horizontal grab
bar, and 4 inches (100 mm) maximum inward from the front edge of the bathtub. |
||
607.4.2
Bathtubs Without Permanent Seats. For bathtubs without
permanent seats, grab bars shall comply with 607.4.2. |
See 4.20.4 |
ANSI
607.4.2 Bathtubs without Permanent Seats. For bathtubs without
permanent seats, grab bars complying with Section 607.4.2 shall be provided. |
||
607.4.2.1
Back Wall. Two grab bars shall be installed on the back
wall, one located in accordance with 609.4 and other located 8 inches (205
mm) minimum and 10 inches (255 mm) maximum above the rim of the bathtub. Each
grab bar shall be 24 inches (610 mm) long minimum and shall be installed 24
inches (610 mm) maximum from the head end wall and 12 inches (305 mm) maximum
from the control end wall. |
NOTE: Figure
34(b) indicates at the foot of the tub, the grab bar shall be a minimum of 24
inches (610 mm) in length measured from the outer edge of the tub. On the
back wall, two grab bars are required. The grab bars mounted on the back wall
shall be a minimum of 48 inches (1220 mm) in length located a maximum of 12
inches (305 mm) from the foot of the tub and a maximum of 15 inches (380 mm)
from the head of the tub. Heights of grab bars are as described above. |
ANSI
607.4.2.1 Back Wall. Two horizontal grab bars shall be
provided on the back wall, one complying with Section 609.4 and the other 9
inches (230 mm) above the rim of the bathtub. Each grab bar shall be 24
inches (610 mm) minimum in length, located 24 inches (610 mm) maximum from
the head end wall and extend to 12 inches (305 mm) maximum from the control
end wall. |
||
607.4.2.2
Control End Wall. A grab bar 24 inches (610 mm) long minimum shall
be installed on the control end wall at the front edge of the bathtub. |
ANSI
607.4.2.2 Control End Wall. Control end wall grab bars
shall comply with Section 607.4.2.2. EXCEPTION: An L–shaped continuous grab
bar of equivalent dimensions and positioning shall be permitted to serve the
function of separate vertical and horizontal grab bars. |
|||
|
|
ANSI
607.4.2.2.1 Horizontal Grab Bar. A horizontal grab bar 24
inches (610 mm) minimum in length shall be provided on the control end wall
beginning near the front edge of the bathtub and extend toward the inside
corner of the bathtub. |
||
|
|
ANSI
607.4.2.2.2 Vertical Grab Bar. A vertical grab bar 18
inches (455 mm) minimum in length shall be provided on the control end wall 3
inches (76 mm) minimum to 6 inches (150 mm) maximum above the horizontal grab
bar, and 4 inches (102 mm) maximum inward from the front edge of the bathtub. |
||
607.4.2.3
Head End Wall. A grab bar 12 inches (305 mm) long minimum shall
be installed on the head end wall at the front edge of the bathtub. |
See 4.20.4 NOTE: Figure
34(a) indicates at the foot of the tub, the grab bar shall be 24 inches (610
mm) minimum in length measured from the outer edge of the tub. On the back
wall, two grab bars are required. The grab bars mounted on the back (long)
wall shall be a minimum 24 inches (610 mm) in length located 12 inches (305
mm) maximum from the foot of the tub and 24 inches (610 mm) maximum from the
head of the tub. One grab bar shall be located 9 inches (230 mm) above the
rim of the tub. The others shall be 33 to 36 inches ( 840 mm to 910 mm) above
the bathroom floor. At the head of the tub, the grab bar shall be a minimum
of 12 inches (305 mm) in length measured from the outer edge of the tub. |
ANSI
607.4.2.3 Head End Wall. A horizontal grab bar 12 inches (305 mm)
minimum in length shall be provided on the head end wall at the front edge of
the bathtub. |
||
607.5
Controls. Controls, other than drain stoppers, shall be
located on an end wall. Controls shall be between the bathtub rim and grab
bar, and between the open side of the bathtub and the centerline of the width
of the bathtub. Controls shall comply with 309.4. |
4.20.5 Controls.
Faucets and other controls complying with 4.27.4 shall be located as shown in
Fig. 34. NOTE: In
figures 34(a) and (b) the control area at the foot of the tub is located on
the open side of the tub. |
ANSI
607.5 Controls. Controls, other than drain stoppers, shall be
provided on an end wall, located between the bathtub rim and grab bar, and
between the open side of the bathtub and the midpoint of the width of the
bathtub. Controls shall comply with Section 309.4. |
||
607.6
Shower Spray Unit and Water. A shower spray unit with a
hose 59 inches (1500 mm) long minimum that can be used both as a
fixed-position shower head and as a hand-held shower shall be provided. The
shower spray unit shall have an on/off control with a non-positive shut-off.
If an adjustable-height shower head on a vertical bar is used, the bar shall
be installed so as not to obstruct the use of grab bars. Bathtub shower spray
units shall deliver water that is 120°F (49°C) maximum. |
4.20.6 Shower Unit. A shower
spray unit with a hose at least 60 in (1525 mm) long that can be used both as
a fixed shower head and as a hand-held shower shall be provided. |
ANSI
607.6 Hand Shower. A hand shower with a hose 59 inches (1500 mm)
minimum in length, that can be used as both a fixed shower head and as a hand
shower, shall be provided. The hand shower shall have a control with a
nonpositive shut–off feature. An adjustable–height hand shower mounted on a
vertical bar shall be installed so as to not obstruct the use of grab bars. |
||
ANSI
607.8 Water Temperature. Bathtubs shall deliver water that is 120
degrees F (49 degrees C) maximum. |
||||
607.7
Bathtub Enclosures. Enclosures for bathtubs shall not obstruct
controls, faucets, shower and spray units or obstruct transfer from
wheelchairs onto bathtub seats or into bathtubs. Enclosures on bathtubs shall
not have tracks installed on the rim of the open face of the bathtub. |
4.20.7 Bathtub Enclosures. If
provided, enclosures for bathtubs shall not obstruct controls or transfer
from wheelchairs onto bathtub seats or into tubs. Enclosures on bathtubs
shall not have tracks mounted on their rims. |
ANSI
607.7 Bathtub Enclosures. Enclosures for bathtubs shall not
obstruct controls or transfer from wheelchairs onto bathtub seats or into
bathtubs. Enclosures on bathtubs shall not have tracks installed on the rim
of the bathtub. |
||
608
Shower Compartments |
ANSI
608 Shower Compartments |
|||
608.1
General. Shower compartments shall comply with 608. |
4.21.1 General. Accessible shower
stalls shall comply with 4.21. |
ANSI
608.1 General. Accessible shower compartments shall comply with
Section 608. |
||
608.2
Size and Clearances for Shower Compartments.
Shower compartments shall have sizes and clearances complying with 608.2. |
4.21.2 Size and Clearances.
Except as specified in 9.1.2, shower stall size and clear floor space shall
comply with Fig. 35(a) or (b). The shower stall in Fig. 35(a) shall be 36 in
by 36 in (915 mm by 915 mm). Shower stalls required by 9.1.2 shall comply
with Fig. 57(a) or (b). The shower stall in Fig. 35(b) will fit into the
space required for a bathtub. NOTE: Figure
35(a) shows that the clear floor space shall be a minimum of 48 inches (1220
mm)in length by a minimum of 36 inches (915 mm) in width and allow for a
parallel approach. The clear floor space shall extend 1 foot beyond the
shower wall on which the seat is mounted.
|
ANSI
608.2 Size and Clearances. |
||
608.2.1
Transfer Type Shower Compartments. Transfer type shower
compartments shall be 36 inches (915 mm) by 36 inches (915 mm) clear inside
dimensions measured at the center points of opposing sides and shall have a
36 inch (915 mm) wide minimum entry on the face of the shower compartment.
Clearance of 36 inches (915 mm) wide minimum by 48 inches (1220 mm) long
minimum measured from the control wall shall be provided. |
ANSI
608.2.1 Transfer–Type Shower Compartments. Transfer–type shower
compartments shall have a clear inside dimension of 36 inches (915 mm) in
width and 36 inches (915 mm) in depth, measured at the center point of
opposing sides. An entry 36 inches (915 mm) minimum in width shall be
provided. A clearance of 48 inches (1220 mm) minimum in length measured
perpendicular from the control wall, and 36 inches (915 mm) minimum in depth
shall be provided adjacent to the open face of the compartment. |
|||
608.2.2
Standard Roll-In Type Shower Compartments. Standard
roll-in type shower compartments shall be 30 inches (760 mm) wide minimum by
60 inches (1525 mm) deep minimum clear inside dimensions measured at center
points of opposing sides and shall have a 60 inches (1525 mm) wide minimum
entry on the face of the shower compartment. |
ANSI
608.2.2 Standard Roll–in–Type Shower Compartments.
Standard roll–in–type shower compartments shall have a clear inside dimension
of 60 inches (1525 mm) minimum in width and 30 inches (760 mm) minimum in
depth, measured at the center point of opposing sides. An entry 60 inches
(1525 mm) minimum in width shall be provided. A clearance of 60 inches (1525
mm) minimum in length adjacent to the 60–inch (1525 mm) width of the open
face of the shower compartment, and 30 inches (760 mm) minimum in depth, shall
be provided. A lavatory complying with Section 606 shall be permitted at the
end of the clearance opposite the shower compartment side where shower
controls are positioned. Where shower controls are located on the back wall
and no seat is provided, the lavatory shall be permitted at either end of the
clearance. |
|||
608.2.2.1
Clearance. A 30 inch (760 mm) wide minimum by 60 inch (1525
mm) long minimum clearance shall be provided adjacent to the open face of the
shower compartment. EXCEPTION: A
lavatory complying with 606 shall be permitted on one 30 inch (760 mm) wide
minimum side of the clearance provided that it is not on the side of the
clearance adjacent to the controls or, where provided, not on the side of the
clearance adjacent to the shower seat. |
|
|||
608.2.3
Alternate Roll-In Type Shower Compartments. Alternate roll-in
type shower compartments shall be 36 inches (915 mm) wide and 60 inches (1525
mm) deep minimum clear inside dimensions measured at center points of
opposing sides. A 36 inch (915 mm) wide minimum entry shall be provided at
one end of the long side of the compartment. |
9.1.2 Accessible Units, Sleeping Rooms, and Suites. Accessible sleeping rooms or suites that comply
with the requirements of 9.2 (Requirements for Accessible Units, Sleeping
Rooms, and Suites) shall be provided in conformance with the table below. In
addition, in hotels, of 50 or more sleeping rooms or suites, additional
accessible sleeping rooms or suites that include a roll- in shower shall also
be provided in conformance with the table below. Such accommodations shall
comply with the requirements of 9.2, 4.21, and Figure 57(a) or (b). NOTE: Figure 57(a) indicates that where a fixed seat is provided in a 30 inch
minimum by 60 inch (716 mm by 1220 mm) minimum shower stall, the controls and
spray unit on the back (long) wall shall be located a maximum of 27 inches
(685 mm) from the side wall where the seat is attached. (4.21.2, 9.1.2) In Figure 57(b), an alternate
36 inch minimum by 60 inch (915 mm by 1220 mm) minimum shower stall is
illustrated. The width of the stall opening stall shall be a minimum of 36
inches (915 mm) clear located on a long wall at the opposite end of the
shower from the controls. The shower seat shall be 24 inches (610 mm) minimum
in length by 16 inches (330 mm) minimum in width and may be rectangular in
shape. The seat shall be located next to the opening to the shower and
adjacent to the end wall containing the shower head and controls. (4.21.2,
9.1.2, A4.23.3) |
ANSI 608.2.3
Alternate Roll–in–Type Shower Compartments. Alternate roll–in
shower compartments shall have a clear inside dimension of 60 inches (1525
mm) minimum in width, and 36 inches (915 mm) in depth, measured at the center
point of opposing sides. An entry 36 inches (915) mm) minimum in width shall
be provided at one end of the 60–inch (1525 mm) width of the compartment. A
seat wall, 24 inches (610 mm) minimum and 36 inches (915 mm) maximum in
length, shall be provided on the entry side of the compartment. |
||
608.3
Grab Bars. Grab bars shall comply with 609 and shall be
provided in accordance with 608.3. Where multiple grab bars are used,
required horizontal grab bars shall be installed at the same height above the
finish floor. EXCEPTIONS: 1. Grab bars shall not be required to be
installed in a shower located in a bathing facility for a single occupant
accessed only through a private office, and not for common use or public use
provided that reinforcement has been installed in walls and located so as to
permit the installation of grab bars complying with 608.3. 2. In residential dwelling units, grab bars shall
not be required to be installed in showers located in bathing facilities
provided that reinforcement has been installed in walls and located so as to
permit the installation of grab bars complying with 608.3. |
4.21.4 Grab Bars. Grab bars
complying with 4.26 shall be provided as shown in Fig. 37. NOTE: In
Figure 37(a), the diagram illustrates an L-shaped grab bar that is located
along the full depth of the control wall (opposite the seat) and halfway
along the back wall. The grab bar shall be mounted between 33 to 36 inches
(840-915 mm) above the shower floor. The bottom of the control area shall be
a maximum of 38 inches (965 mm) high and the top of the control area shall be
a maximum of 48 inches (1220 mm) high. The controls and spray unit shall be
within 18 inches (455 mm) of the front of the shower. In Figure 37(b), the diagram
illustrates a U-shaped grab bar that wraps around the stall. The grab bar
shall be between 33 to 36 inches (840-915 mm) high. The controls are placed
in an area between 38 inches and 48 inches (965 mm and 1220 mm) above the
floor. If the controls are located on the back (long) wall they shall be
located 27 inches (685 mm) from the side wall. The shower head and control
area may be located on either side wall. |
ANSI
608.3 Grab Bars. Grab bars shall comply with Section 609 and
shall be provided in accordance with Section 608.3. Where multiple grab bars
are used, required horizontal grab bars shall be installed at the same height
above the floor. EXCEPTIONS: 1. Grab bars are not required to be installed in
a shower facility for a single occupant, accessed only through a private
office and not for common use or public use, provided reinforcement has been
installed in walls and located so as to permit the installation of grab bars
complying with Section 608.3. 2. In Type A units, grab bars are not required to
be installed where reinforcement complying with Section 1003.11.9 is
installed for the future installation of grab bars. |
||
608.3.1
Transfer Type Shower Compartments. In transfer type
compartments, grab bars shall be provided across the control wall and back
wall to a point 18 inches (455 mm) from the control wall. |
ANSI
608.3.1 Transfer–Type Showers. Grab bars for transfer type
showers shall comply with Section 608.3.1. |
|||
ANSI 608.3.1.1 Horizontal Grab Bars. Horizontal
grab bars shall be provided across the control wall and on the back wall to a
point 18 inches (455 mm) from the control wall. |
||||
|
ANSI
608.3.1.2 Vertical Grab Bar. A vertical grab bar 18 inches
(455 mm) minimum in length shall be provided on the control end wall 3 inches
(75 mm) minimum to 6 inches (150 mm) maximum above the horizontal grab bar,
and 4 inches (100 mm) maximum inward from the front edge of the shower. |
|||
|
ANSI
608.3.1.3 Grab Bar Configuration. Grab bars complying with
Sections 608.3.1.1 and 608.3.1.2 shall be permitted to be separate bars, a
single piece bar, or combination thereof. |
|||
608.3.2
Standard Roll-In Type Shower Compartments. Where a seat is
provided in standard roll-in type shower compartments, grab bars shall be
provided on the back wall and the side wall opposite the seat. Grab bars
shall not be provided above the seat. Where a seat is not provided in
standard roll-in type shower compartments, grab bars shall be provided on
three walls. Grab bars shall be installed 6 inches (150 mm) maximum from
adjacent walls. |
ANSI
608.3.2 Standard Roll–in–Type Showers. In standard roll–in type
showers, grab bars shall be provided on three walls of showers without seats.
Where a seat is provided in a standard roll–in type shower, grab bars shall
be provided on the back wall and on the wall opposite the seat. Grab bars
shall not be provided above the seat. Grab bars shall be 6 inches (150 mm)
maximum from the adjacent wall. |
|||
608.3.3
Alternate Roll-In Type Shower Compartments. In alternate roll-in
type shower compartments, grab bars shall be provided on the back wall and
the side wall farthest from the compartment entry. Grab bars shall not be
provided above the seat. Grab bars shall be installed 6 inches (150 mm)
maximum from adjacent walls. |
See 9.1.2 |
ANSI
608.3.3 Alternate Roll–in–Type Showers. In alternate roll–in
type showers, grab bars shall be provided on the back wall and the end wall
adjacent to the seat. Grab bars shall not be provided above the seat. Grab
bars shall be 6 inches (150 mm) maximum from the adjacent wall. |
||
608.4
Seats. A folding or non-folding seat shall be provided
in transfer type shower compartments. A folding seat shall be provided in
roll-in type showers required in transient lodging guest rooms with mobility
features complying with 806.2. Seats shall comply with 610. EXCEPTION: In
residential dwelling units, seats shall not be required in transfer type
shower compartments provided that reinforcement has been installed in walls
so as to permit the installation of seats complying with 608.4. |
4.21.3 Seat. A seat shall be provided in shower
stalls 36 in by 36 in (915 mm by 915 mm) and shall be as shown in Fig. 36.
The seat shall be mounted 17 in to 19 in (430 mm to 485 mm) from the bathroom
floor and shall extend the full depth of the stall. In a 36 in by 36 in (915
mm by 915 mm) shower stall, the seat shall be on the wall opposite the
controls. Where a fixed seat is provided in a 30 in by 60 in minimum (760 mm
by 1525 mm) shower stall, it shall be a folding type and shall be mounted on
the wall adjacent to the controls as shown in Fig. 57. The structural
strength of seats and their attachments shall comply with 4.26.3. |
ANSI
608.4 Seats. A folding or nonfolding seat shall be provided in
transfer–type shower compartments. A seat shall be provided in an alternate
roll–in–type shower compartment. In standard and alternate roll–in–type
showers where a seat is provided, if the seat extends over the minimum clear
inside dimension required by Section 608.2.2 or 608.2.3, the seat shall be a
folding seat. Seats shall comply with Section 610. EXCEPTIONS: 1. A shower seat is not required to be installed
in a shower facility for a single occupant, accessed only through a private
office and not for common use or public use, provided reinforcement has been
installed in walls and located so as to permit the installation of a shower
seat complying with Section 608.4. 2. In Type A units, a shower seat is not required
to be installed where reinforcement complying with Section 1003.11.9 is
installed for the future installation of a shower seat. |
||
608.5
Controls. Controls, faucets, and shower spray units shall
comply with 309.4. |
4.21.5 Controls. Faucets and other controls
complying with 4.27.4 shall be located as shown in Fig. 37. In shower stalls
36 in by 36 in (915 mm by 915 mm), all controls, faucets, and the shower unit
shall be mounted on the side wall opposite the seat. |
ANSI
608.5 Controls and Hand Showers. Controls and hand showers
shall comply with Sections 608.5 and 309.4. |
||
608.5.1
Transfer Type Shower Compartments. In transfer type shower
compartments, the controls, faucets, and shower spray unit shall be installed
on the side wall opposite the seat 38 inches (965 mm) minimum and 48 inches
(1220 mm) maximum above the shower floor and shall be located on the control
wall 15 inches (380 mm) maximum from the centerline of the seat toward the
shower opening. |
ANSI
608.5.1 Transfer–Type Showers. In transfer–type showers, the
controls and hand shower shall be located on the control wall opposite the
seat, 38 inches (965 mm) minimum and 48 inches (1220 mm) maximum above the
shower floor, within 15 inches (380 mm), left or right, of the centerline of
the seat. |
|||
608.5.2
Standard Roll-In Type Shower Compartments. In standard roll-in
type shower compartments, the controls, faucets, and shower spray unit shall
be located above the grab bar, but no higher than 48 inches (1220 mm) above
the shower floor. Where a seat is provided, the controls, faucets, and shower
spray unit shall be installed on the back wall adjacent to the seat wall and
shall be located 27 inches (685 mm) maximum from the seat wall. |
ANSI
608.5.2 Standard Roll–in Showers. In standard roll–in
showers, the controls and hand shower shall be located 38 inches (965 mm)
minimum and 48 inches (1220 mm) maximum above the shower floor. In standard
roll–in showers with seats, the controls and hand shower shall be located on
the back wall, no more than 27 inches (685 mm) maximum from the end wall
behind the seat. |
|||
608.5.3
Alternate Roll-In Type Shower Compartments. In alternate roll-in
type shower compartments, the controls, faucets, and shower spray unit shall
be located above the grab bar, but no higher than 48 inches (1220 mm) above
the shower floor. Where a seat is provided, the controls, faucets, and shower
spray unit shall be located on the side wall adjacent to the seat 27 inches
(685 mm) maximum from the side wall behind the seat or shall be located on
the back wall opposite the seat 15 inches (380 mm) maximum, left or right, of
the centerline of the seat. Where a seat is not provided, the controls,
faucets, and shower spray unit shall be installed on the side wall farthest
from the compartment entry. |
See 9.1.2 |
ANSI
608.5.3 Alternate Roll–in Showers. In alternate roll–in
showers, the controls and hand shower shall be located 38 inches (965 mm)
minimum and 48 inches (1220 mm) maximum above the shower floor. In alternate
roll–in showers with controls and hand shower located on the end wall
adjacent to the seat, the controls and hand shower shall be 27 inches (685
mm) maximum from the seat wall. In alternate roll–in showers with the
controls and hand shower located on the back wall opposite the seat, the
controls and hand shower shall be located within 15 inches (380 mm), left or
right, of the centerline of the seat. EXCEPTION: A
fixed shower head with the controls and shower head located on the back wall
opposite the seat shall be permitted. |
||
608.6
Shower Spray Unit and Water. A shower spray unit with a
hose 59 inches (1500 mm) long minimum that can be used both as a
fixed-position shower head and as a hand-held shower shall be provided. The
shower spray unit shall have an on/off control with a non-positive shut-off.
If an adjustable-height shower head on a vertical bar is used, the bar shall
be installed so as not to obstruct the use of grab bars. Shower spray units
shall deliver water that is 120°F (49°C) maximum. EXCEPTION:
A fixed shower head located at 48 inches (1220 mm) maximum above the
shower finish floor shall be permitted instead of a hand-held spray unit in
facilities that are not medical care facilities, long-term care facilities,
transient lodging guest rooms, or residential dwelling units. |
4.21.6 Shower
Unit. A shower spray unit with a hose at least 60 in (1525 mm) long that
can be used both as a fixed shower head and as a hand-held shower shall be
provided. EXCEPTION: In unmonitored facilities
where vandalism is a consideration, a fixed shower head mounted at 48 in
(1220 mm) above the shower floor may be used in lieu of a hand-held shower
head. |
ANSI
608.6 Hand Showers. A hand shower with a hose 59 inches (1500 mm)
minimum in length, that can be used both as a fixed shower head and as a hand
shower, shall be provided. The hand shower shall have a control with a
nonpositive shut–off feature. An adjustable–height shower head mounted on a
vertical bar shall be installed so as to not obstruct the use of grab bars. EXCEPTION: A
fixed shower head shall be permitted in lieu of a hand shower where the
scoping provisions of the administrative authority require a fixed shower head. |
||
ANSI
608.9 Water Temperature. Showers shall deliver water that is 120
degrees F (49 degrees C) maximum. |
||||
608.7
Thresholds. Thresholds in roll-in type shower compartments
shall be 1/2 inch (13 mm) high maximum in accordance with 303. In transfer
type shower compartments, thresholds 1/2 inch (13 mm) high maximum shall be
beveled, rounded, or vertical. EXCEPTION: A
threshold 2 inches (51 mm) high maximum shall be permitted in transfer type
shower compartments in existing facilities where provision of a 1/2 inch (13
mm) high threshold would disturb the structural reinforcement of the floor
slab. |
4.21.7 Curbs. If provided,
curbs in shower stalls 36 in by 36 in (915 mm by 915 mm) shall be no higher
than 1/2 in (13 mm). Shower stalls that are 30 in by 60 in (760 mm by 1525
mm) minimum shall not have curbs. |
ANSI
608.7 Thresholds. Thresholds in roll–in–type shower compartment
shall be 1/2 inch (13 mm) maximum in height in accordance with Section 303.
In transfer–type shower compartments, thresholds 1/2 inch (13 mm) maximum in
height shall be beveled, rounded, or vertical. EXCEPTION: In
existing facilities, in transfer–type shower compartments where provision of
a threshold 1/2 inch (13 mm) in height would disturb the structural
reinforcement of the floor slab, a threshold 2 inches (51 mm) maximum in
height shall be permitted. |
||
608.8
Shower Enclosures. Enclosures for shower compartments shall not
obstruct controls, faucets, and shower spray units or obstruct transfer from
wheelchairs onto shower seats. |
4.21.8 Shower Enclosures. If
provided, enclosures for shower stalls shall not obstruct controls or
obstruct transfer from wheelchairs onto shower seats. |
ANSI
608.8 Shower Enclosures. Shower compartment enclosures for shower
compartments shall not obstruct controls or obstruct transfer from
wheelchairs onto shower seats. |
||
609
Grab Bars |
4.26 Handrails, Grab Bars, and Tub and
Shower Seats. |
ANSI
609 Grab Bars |
||
609.1
General. Grab bars in toilet facilities and bathing
facilities shall comply with 609. |
4.26.1 General. All
handrails, grab bars, and tub and shower seats required to be accessible by
4.1, 4.8, 4.9, 4.16, 4.17, 4.20 or 4.21 shall comply with 4.26. |
ANSI
609.1 General. Grab bars in accessible toilet or bathing
facilities shall comply with Section 609. |
||
609.2
Cross Section. Grab bars shall have a cross section complying
with 609.2.1 or 609.2.2. |
4.26.2 Size and Spacing of Grab Bars and Handrails.
The diameter or width of the gripping surfaces of a handrail or grab bar
shall be 1-1/4 in to 1-1/2 in (32 mm to 38 mm), or the shape shall provide an
equivalent gripping surface. If handrails or grab bars are mounted adjacent
to a wall, the space between the wall and the grab bar shall be 1-1/2 in (38
mm) (see Fig. 39(a), (b), (c), and (e)). Handrails may be located in a recess
if the recess is a maximum of 3 in (75 mm) deep and extends at least 18 in
(455 mm) above the top of the rail (see Fig. 39(d)). |
ANSI
609.2 Cross Section. Grab bars shall have a cross section
complying with Section 609.2.1 or 609.2.2. |
||
609.2.1
Circular Cross Section. Grab bars with circular cross sections
shall have an outside diameter of 1 1/4 inches (32 mm) minimum and 2 inches
(51 mm) maximum. |
NOTE: In Figure 39(b), the
handrail shape has a rounded gripping surface shaped from a
rectangular stock. Spacing between handrail and the adjacent wall shall be
1-1/2 inches (38 mm). Handrail gripping surface shall be 1-1/4 to 1-1/2
inches diameter (32 - 38 mm). |
ANSI
609.2.1 Circular Cross Section. Grab bars with a circular
cross section shall have an outside diameter of 1 1/4 inch (32 mm) minimum
and 2 inches (51 mm) maximum. |
||
609.2.2
Non-Circular Cross Section. Grab bars with non-circular
cross sections shall have a cross-section dimension of 2 inches (51 mm)
maximum and a perimeter dimension of 4 inches (100 mm) minimum and 4.8 inches
(120 mm) maximum. |
NOTE: Figure 39(c) shows a
rounded gripping surface provided on top of a rectangular railing supported
from a bottom bracket attached to a side wall. Spacing between handrail and
the adjacent wall shall be 1-1/2 inches (38 mm). Rounded handrail surface
shall be 1-1/4 to 1-1/2 inches diameter (32 - 38 mm). |
ANSI
609.2.2 Noncircular Cross Section. Grab bars with a noncircular
cross section shall have a cross section dimension of 2 inches (51 mm)
maximum, and a perimeter dimension of 4 inches (102 mm) minimum and 4.8
inches (122 mm) maximum. |
||
609.3
Spacing. The space between the wall and the grab bar
shall be 1 1/2 inches (38 mm). The space between the grab bar and projecting
objects below and at the ends shall be 1 1/2 inches (38 mm) minimum. The
space between the grab bar and projecting objects above shall be 12 inches
(305 mm) minimum. EXCEPTION: The
space between the grab bars and shower controls, shower fittings, and other
grab bars above shall be permitted to be 1 1/2 inches (38 mm) minimum. |
NOTE: Figure
39(a) indicates spacing between handrail and the adjacent wall
shall be 1 1/2 inches (38 mm). Handrail shall be 1-1/4 to 1-1/2 inches
diameter (32 - 38 mm). Support for the handrail is from below. Figure 39(d) illustrates a handrail
mounted into a recessed section of a wall. The bottom of the recessed section
is not more than 3 inches wide where the handrail is located. The recessed
section shown extends vertically approximately 6 inches and then angles to a
point on the flush wall a minimum of 18 inches (455 mm) above the grab bar.
This profile is provided to permit grasping from a standing position. Spacing
between handrail and the adjacent wall shall be 1- 1/2 inches (38 mm).
Handrail shall be 1-1/4 to 1-1/2 inches diameter (32 - 38 mm). Support for
the handrail is from below. In Figure 39(e), the round
grab bar surface is 1-1/4 to 1-1/2 inches diameter (32 - 38 mm). Spacing from
the face of the grab bar to the wall is 1- 1/2 inches (38 mm). |
ANSI
609.3 Spacing. The space between the wall and the grab bar
shall be 1 1/2 inches (38 mm). The space between the grab bar and projecting
objects below and at the ends of the grab bar shall be 1 1/2 inches (38 mm)
minimum. The space between the grab bar and projecting objects above the grab
bar shall be 12 inches (305 mm) minimum. EXCEPTIONS: 1. The space between the grab bars and shower
controls, shower fittings, and other grab bars above the grab bar shall be
permitted to be 1 1/2 inches (38 mm) minimum. 2. Swing–up grab bars shall not be required to comply
with Section 609.3. |
||
609.4
Position of Grab Bars. Grab bars shall be installed in a
horizontal position, 33 inches (840 mm) minimum and 36 inches (915 mm)
maximum above the finish floor measured to the top of the gripping surface,
except that at water closets for children's use complying with 604.9, grab
bars shall be installed in a horizontal position 18 inches (455 mm) minimum
and 27 inches (685 mm) maximum above the finish floor measured to the top of
the gripping surface. The height of the lower grab bar on the back wall of a
bathtub shall comply with 607.4.1.1 or 607.4.2.1. |
|
ANSI
609.4 Position of Grab Bars. Grab bars shall be installed
in a horizontal position, 33 inches (840 mm) minimum and 36 inches (915 mm)
maximum above the floor measured to the top of the gripping surface. At water
closets primarily for children’s use complying with Section 604.10, grab bars
shall be installed in a horizontal position 18 inches (455 mm) minimum to 27
inches (685 mm) maximum above the floor measured to the top of the gripping
surface. EXCEPTIONS: 1. The lower grab bar on the back wall of a
bathtub required by Section 607.4.1.1 or 607.4.2.1. 2. Vertical grab bars required by Sections
604.5.1, 607.4.1.2.2, 607.4.2.2.2, and 608.3.1.2. |
||
609.5
Surface Hazards. Grab bars and any wall or other surfaces
adjacent to grab bars shall be free of sharp or abrasive elements and shall
have rounded edges. |
4.26.4 Eliminating
Hazards. A handrail or grab bar and any wall or other surface adjacent to
it shall be free of any sharp or abrasive elements. Edges shall have a
minimum radius of 1/8 in (3.2 mm). |
ANSI
609.5 Surface Hazards. Grab bars, and any wall or other
surfaces adjacent to grab bars, shall be free of sharp or abrasive elements.
Edges shall be rounded. |
||
609.6
Fittings. Grab bars shall not rotate within their
fittings. |
4.26.3(5) Grab bars shall not rotate within their
fittings. |
ANSI
609.6 Fittings. Grab bars shall not rotate within their
fittings. |
||
609.7
Installation. Grab bars shall be installed in any manner that
provides a gripping surface at the specified locations and that does not
obstruct the required clear floor space. |
|
ANSI
609.7 Installation. Grab bars shall be installed in any manner that
provides a gripping surface at the locations specified in this standard and
does not obstruct the clear floor space. |
||
609.8
Structural Strength. Allowable stresses shall not be exceeded
for materials used when a vertical or horizontal force of 250 pounds (1112 N)
is applied at any point on the grab bar, fastener, mounting device, or
supporting structure. |
4.26.3 Structural Strength. The
structural strength of grab bars, tub and shower seats, fasteners, and
mounting devices shall meet the following specification: (1) Bending stress in a grab bar or seat induced by the maximum
bending moment from the application of 250 lbf (1112N) shall be less than the
allowable stress for the material of the grab bar or seat. (2) Shear stress induced in a grab bar or seat by the application of
250 lbf (1112N) shall be less than the allowable shear stress for the
material of the grab bar or seat. If the connection between the grab bar or
seat and its mounting bracket or other support is considered to be fully
restrained, then direct and torsional shear stresses shall be totaled for the
combined shear stress, which shall not exceed the allowable shear stress. (3) Shear force induced in a fastener or mounting device from the
application of 250 lbf (1112N) shall be less than the allowable lateral load
of either the fastener or mounting device or the supporting structure,
whichever is the smaller allowable load. (4) Tensile force induced in a fastener by a direct tension force of
250 lbf (1112N) plus the maximum moment from the application of 250 lbf
(1112N) shall be less than the allowable withdrawal load between the fastener
and the supporting structure. |
ANSI
609.8 Structural Strength. Allowable stresses shall not
be exceeded for materials used where a vertical or horizontal force of 250
pounds (1112 N) is applied at any point on the grab bar, fastener mounting
device, or supporting structure. |
||
610
Seats |
|
ANSI
610 Seats |
||
610.1
General. Seats in bathtubs and shower compartments shall
comply with 610. |
|
ANSI
610.1 General. Seats in accessible bathtubs and shower
compartments shall comply with Section 610. |
||
610.2
Bathtub Seats. The top of bathtub seats shall be 17 inches (430
mm) minimum and 19 inches (485 mm) maximum above the bathroom finish floor.
The depth of a removable in-tub seat shall be 15 inches (380 mm) minimum and
16 inches (405 mm) maximum. The seat shall be capable of secure placement.
Permanent seats at the head end of the bathtub shall be 15 inches (380 mm)
deep minimum and shall extend from the back wall to or beyond the outer edge
of the bathtub. |
|
ANSI
610.2 Bathtub Seats. The height of bathtub seats shall be 17
inches (430 mm) minimum to 19 inches (485 mm) maximum above the bathroom
floor, measured to the top of the seat. Removable in–tub seats shall be 15
inches (380 mm) minimum and 16 inches (405 mm) maximum in depth. Removable
in–tub seats shall be capable of secure placement. Permanent seats shall be
15 inches (380 mm) minimum in depth and shall extend from the back wall to or
beyond the outer edge of the bathtub. Permanent seats shall be positioned at
the head end of the bathtub. |
||
610.3
Shower Compartment Seats. Where a seat is provided in a standard
roll-in shower compartment, it shall be a folding type, shall be installed on
the side wall adjacent to the controls, and shall extend from the back wall
to a point within 3 inches (75 mm) of the compartment entry. Where a seat is
provided in an alternate roll-in type shower compartment, it shall be a
folding type, shall be installed on the front wall opposite the back wall,
and shall extend from the adjacent side wall to a point within 3 inches (75
mm) of the compartment entry. In transfer-type showers, the seat shall extend
from the back wall to a point within 3 inches (75 mm) of the compartment
entry. The top of the seat shall be 17 inches (430 mm) minimum and 19 inches
(485 mm) maximum above the bathroom finish floor. Seats shall comply with
610.3.1 or 610.3.2. |
|
ANSI
610.3 Shower Compartment Seats. Where a seat is provided in
a standard roll–in shower compartment, it shall be a folding type and shall
be on the wall adjacent to the controls. The height of the seat shall be 17
inches (430 mm) minimum and 19 inches (485 mm) maximum above the bathroom
floor, measured to the top of the seat. In transfer–type and alternate
roll–in–type showers, the seat shall extend along the seat wall to a point
within 3 inches (75 mm) of the compartment entry. In standard roll–in–type showers,
the seat shall extend from the control wall to a point within 3 inches (75
mm) of the compartment entry. Seats shall comply with Section 610.3.1 or
610.3.2. |
||
610.3.1
Rectangular Seats. The rear edge of a rectangular seat shall be 2
1/2 inches (64 mm) maximum and the front edge 15 inches (380 mm) minimum and
16 inches (405 mm) maximum from the seat wall. The side edge of the seat
shall be 1 1/2 inches (38 mm) maximum from the adjacent wall. |
|
ANSI
610.3.1 Rectangular Seats. The rear edge of a
rectangular seat shall be 2 1/2 inches (64 mm) maximum and the front edge 15
inches (380 mm) minimum to 16 inches (405 mm) maximum from the seat wall. The
side edge of the seat shall be 1 1/2 inches (38 mm) maximum from the back
wall of a transfer–type shower and 1 1/2 inches (38 mm) maximum from the
control wall of a roll–in–type shower. |
||
610.3.2
L-Shaped Seats. The rear edge of an L-shaped seat shall be 2 1/2
inches (64 mm) maximum and the front edge 15 inches (380 mm) minimum and 16
inches (405 mm) maximum from the seat wall. The rear edge of the
"L" portion of the seat shall be 1 1/2 inches (38 mm) maximum from
the wall and the front edge shall be 14 inches (355 mm) minimum and 15 inches
(380 mm) maximum from the wall. The end of the "L" shall be 22
inches (560 mm) minimum and 23 inches maximum (585 mm) from the main seat
wall. |
NOTE: In
Figure 36, the diagram illustrates an L-shaped shower seat extending the full
depth of the stall. The seat shall be located 1-1/2 inches (38 mm) maximum
from the wall. The front of the seat (nearest to the opening) shall extend a
maximum 16 inches (330 mm) from the wall. The back of the seat (against the
back wall) shall extend a maximum of 23 inches (582 mm) from the side wall
and shall be a maximum of 15 inches (305 mm) deep. |
ANSI
610.3.2 L–Shaped Seats.
The rear edge of an L–shaped seat shall be 2 1/2 inches (64 mm)
maximum and the front edge 15 inches (380 mm) minimum to 16 inches (405 mm)
maximum from the seat wall. The rear edge of the “L” portion of the seat
shall be 1 1/2 inches (38 mm) maximum from the wall and the front edge shall
be 14 inches (355 mm) minimum and 15 inches (380 mm) maximum from the wall.
The end of the “L” shall be 22 inches (560 mm) minimum and 23 inches (585 mm)
maximum from the main seat wall. |
||
610.4
Structural Strength. Allowable stresses shall not be exceeded
for materials used when a vertical or horizontal force of 250 pounds (1112 N)
is applied at any point on the seat, fastener, mounting device, or supporting
structure. |
See 4.26.3 |
ANSI 610.4 Structural Strength.
Allowable stresses shall not be exceeded for materials used where a vertical
or horizontal force of 250 pounds (1112 N) is applied at any point on the
seat, fastener mounting device, or supporting structure. |
||
611
Washing Machines and Clothes Dryers |
|
ANSI
611 Washing Machines and Clothes Dryers |
||
611.1
General. Washing machines and clothes dryers shall comply
with 611. |
|
ANSI
611.1 General. Accessible washing machines and clothes dryers
shall comply with Section 611. |
||
611.2
Clear Floor Space. A clear floor or ground space complying with 305
positioned for parallel approach shall be provided. The clear floor or ground
space shall be centered on the appliance |
|
ANSI
611.2 Clear Floor Space. A clear floor space complying with
Section 305, positioned for parallel approach, shall be provided. The clear
floor space shall be centered on the appliance. |
||
611.3
Operable Parts. Operable parts, including doors, lint screens,
and detergent and bleach compartments shall comply with 309. |
|
ANSI
611.3 Operable Parts. Operable parts, including doors, lint
screens, detergent and bleach compartments, shall comply with Section 309. |
||
611.4
Height. Top loading machines shall have the door to the
laundry compartment located 36 inches (915 mm) maximum above the finish
floor. Front loading machines shall have the bottom of the opening to the
laundry compartment located 15 inches (380 mm) minimum and 36 inches (915 mm)
maximum above the finish floor. |
|
ANSI
611.4 Height. Top loading machines shall have the door to the
laundry compartment 36 inches (915 mm) maximum above the floor. Front loading
machines shall have the bottom of the opening to the laundry compartment 15
inches (380 mm) minimum and 34 inches (865 mm) maximum above the floor. |
||
612
Saunas and Steam Rooms |
See Appendix 4.36 |
|
||
612.1
General. Saunas and steam rooms shall comply with 612. |
|
|||
612.2
Bench. Where seating is provided in saunas and steam
rooms, at least one bench shall comply with 903. Doors shall not swing into
the clear floor space required by 903.2. EXCEPTION: A
readily removable bench shall be permitted to obstruct the turning space
required by 612.3 and the clear floor or ground space required by 903.2. |
|
|||
612.3
Turning Space. A turning space complying with 304 shall be
provided within saunas and steam rooms. |
|
|||