Guidance Manual for Operators of Small Natural Gas Systems (June 2002 Edition)

Cover, To The Reader, Acknowledgements, TOC
Guidance Manual for Operators of Small Natural Gas Systems

June 2002

US Department of Transportation
Research and Special Programs Administration
Office of Pipeline Safety

 

To The Reader

The U.S. Office of Pipeline Safety promotes the safe transportation of natural gas by pipeline. This guidance manual for operators of small natural gas systems is part of our commitment to pipeline safety. This manual was developed to provide an overview of pipeline compliance responsibilities under the federal pipeline safety regulations. It is designed for the nontechnically trained person who operates a master meter system, a small municipal system, or small independent system.

The federal government recognizes that most operators of small natural gas systems have not had extensive qualification in operation and maintenance of a gas system. In addition, many of the safety regulations are in technical language that addresses generic requirements for both large and small natural gas systems. This manual attempts to simplify the technical language of the regulations.

For certain critical regulations, this manual provides details of methods of operation and selection of materials that will satisfy the pipeline safety regulations. However, this is often only one of several allowable options. This manual provides a set of examples that operators of small natural gas systems can use to meet the minimum requirements of the pipeline safety regulations. For example, requirements for pressure testing vary throughout the pipeline safety regulations. The test pressure used in this manual is usually 100 pounds per square inch to provide clarity and consistency to small operators unfamiliar with the intricacies of natural gas pipeline operations. The operator is referred to 49 CFR Part 192 for additional details and other options for reaching and maintaining compliance.

Our aim is to provide basic information to operators of small natural gas distribution and master meter systems to ensure compliance with the federal gas pipeline safety regulations. It is hoped that this document will assist operators in achieving and maintaining a safe and efficient natural gas system. The result will enhance public safety – the essential goal of the Office of Pipeline Safety.

Stacey Gerard
Associate Administrator for Pipeline Safety

 

Acknowledgements

The Office of Pipeline Safety (OPS) gratefully acknowledges the contributions of the many individuals and organizations who contributed their time and expertise to this manual. Most especially, it is a product of close cooperation with the Small Operators Manual Committee of the National Association of Pipeline Safety Representatives (NAPSR). OPS extends special thanks to RSPA's Transportation Safety Institute (TSI) for its exemplary efforts in the revision and publication of this manual.

The following organizations significantly contributed to the revised manual:

Aegis Loss Control Services, Inc.
American Gas Association (AGA)
American Petroleum Institute (API)
American Public Gas Association (APGA)
Dresser Industries, Inc.
Fisher Corporation
Heath Consultants
Louisiana One Call, Inc.
Midwest Energy Association (MEA)
Natural Gas Odorizing, Inc.
National Association of Corrosion Engineers (NACE)
Perfection Corporation

The revision and publication of this manual is an example of constructive partnership among government, the pipeline industry, and industry and professional organizations.

 

Table of Contents

CHAPTER I – INTRODUCTION AND OVERVIEW
Introduction
Overview

CHAPTER II – REGULATOR AND RELIEF DEVICES
Basic Concept
Pressure and Force
Flow and Throttling
Basic Names and Terms
Overpressure Protection
Pressure Relief
Monitoring
Automatic Shutoff

CHAPTER III – CORROSION CONTROL
Federal Requirements
Principles and Practices of Cathodic Protection
Fundamental Corrosion Theory
Types of Cathodic Protection
Initial Steps in Determining the Need to Cathodically Protect a Small Gas Distribution System
Criteria for Cathodic Protection
Coatings
Common Causes of Corrosion in Gas Piping Systems

CHAPTER IV – LEAK DETECTION
Methods of Detecting a Leak
Description of Leak Detection Equipment
Recommended Method for Surface Gas Detection Survey with FI Unit (Natural Gas System Only)
Odorization Equipment
Records
GPTC – Guide Material for "Leak Classification and Action Criteria"
Follow-up Inspection

CHAPTER V – UNACCOUNTED FOR GAS

CHAPTER VI – REPAIRS AND NEW CONSTRUCTION
Planning Ahead
Excavation
Emergency Excavation
Precautions to Avoid Damage
Excavation: Repair of Damage
Recommendation
Pipe Installation, Repair, and Replacement: General Comments
Metallic Pipe Installation
Plastic Pipe Installation
Repair Methods – Plastic and Metal
Materials and Equipment Qualified for Use in Natural Gas Systems
Pipe
Valves
Flanges and Flange Accessories
Regulators and Overpressure Protection Equipment
Other Equipment
Welding Requirements
Common Construction Practices

CHAPTER VII – PROPER LOCATION AND DESIGN OF CUSTOMER METER AND REGULATOR SETS
Customer Meters and Regulators: Location
Customer Meters and Regulators: Protection From Damage
Customer Meters Installations: Operating Pressure
Service Lines: Location of Valves
Common Problems at Service Riser and House Regulators

CHAPTER VIII – PLANS AND REPORTS REQUIRED BY THE FEDERAL GOVERNMENT
Plans Required by the Federal Government
Operations and Maintenance Plans
Operations and Maintenance Plans Must Contain the Following Components:
Emergency Plans
Reports Required by the Federal Government
Incident Report
Safety-Related and Condition Reports
Annual Reports

APPENDIX A – GLOSSARY AND ACRONYMS

APPENDIX B – SAMPLE FORMS

APPENDIX C – STATE AND FEDERAL REGULATORY AGENCIES

 

Chapter 1 - Introduction and Overview

This chapter contains a simplified description of the pipeline safety requirements. The complete text can be found in 49 CFR Part 192.

INTRODUCTION

Public Law 104-304 requires the U.S. Department of Transportation (DOT) to develop and enforce minimum safety regulations for the transportation of gases by pipeline. The safety regulations became effective in 1970, and are published in Title 49 of the Code of Federal Regulations (CFR), Parts 190, 191, 192, and 199. The Office of Pipeline Safety of DOT’s Research and Special Programs Administration (RSPA) is charged with their enforcement.

The gas pipeline safety regulations apply to natural gas systems and operators of natural gas master meter systems. The pipeline safety regulations require operators of natural gas systems to: deliver gas safely and reliably to customers; provide training and written instruction for employees; establish written procedures to minimize the hazards resulting from natural gas pipeline emergencies; and, keep records of inspection and testing based on suggested forms found in Appendix B.

Additionally, operators of all natural gas systems, except master meter systems, must test employees in safety-sensitive positions for prohibited drugs and alcohol and provide an employee assistance program. The requirements for drug and alcohol testing of pipeline employees are found in 49 CFR Part 199, which incorporates the overall OPS drug testing requirements found in 49 CFR Part 40.

Natural gas operators who do not comply with the safety regulations may be subject to civil penalties, compliance orders, or both. If safety problems are severe, a "Corrective Action Order" may be issued by OPS. This could result in the shutdown of the system.

State agencies may enforce pipeline safety regulations under certification by OPS. The state agency is allowed to adopt additional or more stringent safety regulations for intrastate pipeline transportation as long as such regulations are compatible with the federal minimum regulations. However, if a state agency is not certified, the DOT retains jurisdiction over intrastate pipeline systems.

Operators should check with the pipeline safety agency in their state (Appendix C) to determine:

  • whether a state agency has safety jurisdiction;
  • whether the state agency has pipeline safety requirements that exceed the federal regulations;
  • the inspection and enforcement procedures of the state agency.
OVERVIEW

The natural gas pipeline industry consists of transmission and distribution companies. These pipeline systems can be simple or complicated. However, all gas pipeline companies are held to the same safety standards.

FIGURE I-1 [refer to PDF version for image] represents one of the many possible configurations of natural gas transmission and distribution systems. The natural gas:

  • Flows from the producing wells into gathering line(s).
  • Through gathering lines and compressors or compressor stations.
  • After the compressor(s), through transmission lines.
  • To a processing plant where the heavy ends, such as propane, butane, ethane or natural gasoline, which are initially components of the gas stream, are removed.
  • Through the transmission line and additional compressors.
  • From the compressors to underground storage or a liquefied natural gas (LNG) plant (where natural gas is liquefied by reducing its temperature to - 260°F), or directly to a city gate station or master meter system.

FIGURE I-2 [refer to PDF version for image] is an example of a distribution system that consists of mains and services operating at different pressures, which are controlled by regulators. Ordinarily, industrial customers receive gas service through high-pressure distribution mains. The small commercial and the residential gas systems can be either low- or high-pressure distribution systems.

Chapter 2 - Regulator and Relief Devices

This chapter contains a simplified description of the pipeline safety requirements. The complete text can be found in 49 CFR Part 192.

BASIC CONCEPT

In understanding the equipment used to regulate the pressure of natural gas, it is helpful to be familiar with some fundamental physical units and concepts. Four are particularly important. Taken in pairs they are:

PRESSURE and FORCE
FLOW and THROTTLING PRESSURE

In the natural gas business the commonly used pressure units are:

pounds per square inch ....…psi
ounces per square inch....….osi
inches water column... in. w.c

For convenience, the three units are usually referred to as pounds, ounces, and inches.

It is important to remember that "pounds," "ounces," and "inches" are the short form of expressing pressure units. There really is no such thing as a pound of pressure or an ounce of pressure. They are incomplete terms. Pressure is defined as force per unit area. Pounds and ounces express only the "force" portion of that definition. The fourth unit of "area" is missing. Thus, the complete terminology should be "pounds per square inch" and "ounces per square inch."

When gas is under pressure, it exerts a given force against each unit of exposed area. For example, gas at a pressure of 10 psi pushes with a force of 10 pounds against each square inch of surface exposed to the gas. Gas at a pressure of 5 ounces (remember... ounces per square inch) pushes with a force of 5 ounces against each square inch of surface exposed to the gas.

Such units as pounds or ounces per square foot, per square yard, or other unit area are quite correct. However, for the gas business the unit area used is the square inch. And, to repeat, the complete expressions are pounds per square inch (psi), and ounces per square inch (osi).

Returning to psi, there are some other terms to note as follows:

pounds per square inch absolute....psia
pounds per square inch gauge........psig

The relationship between the two is simple:

psia = psig + atmospheric pressure

Absolute pressure (psia) uses a perfect vacuum as the zero point. A perfect vacuum is 0 psia.

Gauge pressure (psig) uses the actual atmospheric pressure as the zero point. In Miami, sea level atmospheric pressure is 14.7 psia. Thus, 0 psig is 14.7 psia in Miami. In Denver (5,280 feet elevation), atmospheric pressure is 12.1 psia. And 0 psig for Denver is 12.1 psia.

Inches of water column (in. w.c.) are often used to express the pressure at which gas is delivered to residential customers. Pressure measurement in inches is usually done with an instrument called a manometer (see FIGURE II-1 [refer to PDF version page II-4 for image]). The important relationships to remember are these:

For inches of water column: 1 psig = 27.71 in. w.c. (at sea level)

Note the physical limitations to pressure measurement with the manometer. The highest pressure that could be measured with a "U" type manometer 5-feet high would be only a little over 2 psig (56 in. w.c.). However, note also that it offers a very precise way of measuring low pressures.

When expressing pressure in inches, it is necessary to identify the liquid. To put it another way, there really is no such thing as an inch of pressure. Instead, it is inches of a particular liquid, in the gas business generally water or mercury. Thus, the correct expression is inches water column (in. w.c. or in. H2O). Figure II-1 [refer to PDF version page II-4 for image] illustrates how to read a manometer.

PRESSURE AND FORCE

Force is simply a push or a pull. It is measured in pounds.

Note that pounds of pressure is incomplete (it should be pounds per square inch) whereas pounds of force is complete. Thus, it would be "x" pounds of pushing force or pulling force.

FIGURE II-2 [refer to PDF version page II-5 for image] shows the relationship between pressure and force. Note that pressure is used to create a total force. Also, note how much force (200 pounds) can be created with only a small amount of pressure (2 psig.) It is all a matter of diaphragm area or piston area. A diaphragm, of course, is simply a low friction, tightly sealed, short stroke piston (just the thing for use in regulators).

In FIGURE II-2, the effective area of the piston or diaphragm is 100 square inches (100 in.2).
Applying 2 psig pressure to the 100 in.2 area gives an upward pulling force of 200 pounds (100
in.2 x 2 lbs/in.2 = 200 pounds).

Note that the pressure above both the diaphragm and the piston is atmospheric (0 psig). The differential pressure across the diaphragm and across the piston is 2 psi (2 psig - 0 psig = 2 psi).

Note also that the effective diameter of the diaphragm and the piston is only about 11 inches. An 11 inch diaphragm is not very large. This is quite a common size for regulators, particularly on commercial and industrial applications. But an 11 inch diaphragm has a large area (100 in.2). It does not take much pressure (2 psig, for example) to develop a large total force (200 pounds).

FLOW AND THROTTLING

To throttle the flow of a fluid is to allow only a certain amount to flow and to hold back the remainder. A faucet provides a good example. How much water is wanted determines how far the faucet is opened. The faucet (a valve) is a throttling device. Depending on how far it is opened, it allows only a certain amount of water to flow and holds the rest back. It restricts flow to a certain amount.

Throttling is a basic function in a regulator. The part that throttles is a valve. It allows only a certain amount of gas to flow. The valve part of a regulator is a type of variable restrictor.

Not all valves can be used for throttling (i.e., used as a variable restrictor). Some (like many gate valves) are designed to be either wide open or fully closed. If used in an intermediate position (one-third open, half open, three-fourths open, etc.), they become unstable. They may chatter, rattle, hammer, etc. They are unsatisfactory.

For a regulator, the valve must be mechanically stable from wide open to as small a flow as possible. In addition, it must change the flow smoothly as it is opened or closed.

The most widely used valve for regulators is the single-port, unbalanced, globe valve. It is economical in construction yet provides good throttling. In addition, it has a smooth stroke, little friction, and good shut-off (lock-up) characteristics.

FIGURE II-3  [refer to PDF version page II-6 for image] shows a simple section of a standard spring regulator. The various parts are labeled. For most master meter operators this will be the only type of regulator in the system. Service regulators are this type of regulator. Referring to FIGURE II-3, the following is a simple explanation of how it works.

  1. Spring compression works to open the valve.

    The rule is: The PRIMARY VALVE OPENING FORCE in a spring regulator comes
    from the spring (usually, spring compression).

  2. The diaphragm works to close the valve.

    The rule is: The PRIMARY VALVE CLOSING FORCE in a spring regulator comes
    from other pressure acting against the effective area of the diaphragm.

  3. An increase in outlet pressure creates valve closing action. Conversely, a decrease creates opening action.
  4. Set point (the outlet pressure a regulator is adjusted to deliver) is determined by spring compression. Turning the set point adjustment clockwise increases spring compression which increases set point, and vice versa.

Pilot type regulators are used at city gate stations or for large industrial customers. These regulators are more complicated than spring regulators. These types of regulators will not be discussed in this manual. A consultant should be used to select the correct type and size regulator for most applications except for house regulators.

BASIC NAMES AND TERMS

Referring to FIGURE II-3 [refer to PDF version page II-6 for image], the inlet is the opening through which gas enters a regulator. The pressure of the entering gas is usually called the inlet pressure, although it could also be called the upstream or supply pressure.

The outlet is the opening by which gas leaves a regulator. The pressure of the exiting gas is usually called outlet pressure, although it could also be called downstream pressure.

In general, the more the inlet pressure exceeds the outlet pressure, the greater the amount of gas that can flow through the regulator, (to put it another way, the greater the capacity of the regulator). The difference between inlet and outlet pressures is sometimes called the differential across the regulator.

Piping on the inlet side is upstream and piping on the outlet side is downstream. As stated previously, a regulator takes higher pressure gas from the supply and reduces it to the pressure required by the load. To do this, something is needed on the regulator to adjust it for the specific pressure required. This adjustment is called the set point adjustment and on most of today's regulators it is a screw-type device of some kind, usually a simple adjustment screw. Set point is the pressure a regulator is adjusted to deliver. It is the pressure required by the load and, in general, is the same as the outlet pressure.

Note the control line referred to in FIGURE II-3A [refer to PDF version page II-6 for image]. It is also called a sensing line, impulse line, equalizing line or static line. The control line and the sensing point are vital parts of a regulator installation. They must be carefully planned and correctly installed if the regulator is to operate satisfactorily and safely.

Many regulators, particularly smaller ones, do not have the external control line shown in FIGURE II-3A. Instead, it is internal as represented by FIGURE II-3B [refer to PDF version page II-6 for image]. Called internal control, it is inside some form of open throat construction or venturi tube. However, whether located internally or externally, every regulator has a control line or the equivalent.

Control lines must be adequately protected against breakage. If they are broken, the regulator opens wide and this could result in the full upstream line pressure (that is high) being dumped into the low-pressure system. This can lead to a catastrophic situation.

The next item is the vent. While often appearing insignificant, the vent is important to a regulator. Regulators breathe. As the internals move in the work of controlling pressure, a regulator will inhale or exhale through the vent. Therefore, the vent must be adequately protected from obstructions such as dirt, insects, ice, etc. If an obstructed vent prevents a regulator from breathing, the diaphragm will not work properly.

In the event that the regulator fails to open, the higher pressure gas dissipates thru the vent.

Also, water can get inside a regulator through an improperly positioned and unprotected vent. Water inside a regulator can cause problems. Therefore, vents must be positioned and protected to keep the water out. This is particularly important on outdoor installations.

The last item is the stop valve (FIGURE II-4 [refer to PDF version page II-9 for image]). A simple installation (such as at a house) usually has only one. A more complex installation such as a regulator station would have several stop valves (inlet stop valve, outlet stop valve, control line valve, bypass valve, and perhaps others).

The most important of all is the inlet stop valve. The inlet stop valve should be used with extra care, particularly when being opened. Do not open it until everything is correct and safe. Then open it slowly. Allow the inlet gas to enter slowly, and the pressure to build up slowly.

Stop valves make it possible to put a regulator into service or take it out of service. They make it possible to isolate a regulator for testing and servicing. Correct opening and closing sequences should be adequately understood (these are often specified in gas company standards and procedures). Understanding usage in case of an emergency is also important.

In most cases operators of small natural gas systems need to rely on a consultant for major repair work on regulator stations. The operations and maintenance plan must name the person who is responsible for determining when a regulator needs to be serviced. The operations and maintenance plan should also list those consultant(s) capable of working on regulator stations.

There are three basic methods of providing overpressure protection:

  • Pressure Relief
  • Monitoring
  • Automatic Shutoff

Pressure relief is simply a dumping of excess gas safely into the atmosphere. The excess gas is that which would cause pressure to exceed the safety limit. The relief valve is the most widely used piece of equipment in this category. However, liquid seals and rupture discs may also be used.

There are two basic kinds of relief valves – self-operated and relay-operated. The spring-type relief valve is the most widely used. The pilot-operated type is also frequently used, and it offers more precise operation. The pilot operated type is more frequently used as pressures become higher and capacities greater. Monitoring involves a standby regulator. The standby prevents pressure from exceeding the safety limit.

The most widely used form of monitoring is standby monitoring. It is also called passive monitoring. It consists of two regulators in series, one of which is operating to control pressure while the other is a standby. The standby unit is normally further open than necessary, usually wide open. It takes that position because it is adjusted to a higher set point than the operating regulator. If an operating regulator failure causes outlet pressure to rise, the monitor takes over and holds pressure at its set point.

Two other forms of monitoring are sometimes used. One simply consists of two-stage regulation which, when designed for the purpose, can provide monitoring protection. The other is called override monitoring or working monitoring. With it, the upstream regulator must be pilot operated and have an extra pilot. During normal operation, the set provides two-stage regulation. In an overpressure emergency it protects in the same way as standby monitoring.

Automatic shutoff involves a valve that normally remains in the wide open position and allows the gas to flow freely. It is located in series with the regulator, either upstream or downstream, depending on whether it uses a control line or internal control.

If a regulator failure results in a rising outlet pressure, the shutoff closes automatically when pressure reaches its set point. It protects by shutting off the gas and remains closed until manually opened and reset.

In general, there are three things to consider in choosing overpressure protection systems:

  1. Continuity of service – does the user, or the load, need to be continuously supplied with gas?
  2. Containment – is gas released into the atmosphere or does it remain contained within the gas system?
  3. Alerting – is there provision for notification or warning that an emergency has occurred and that the overpressure protection equipment has gone into operation?

The following is a comparison of the three basic overpressure protection methods (based on the foregoing three considerations).

Pressure Relief

  • Continuity of Service. In general, pressure relief valves do not interrupt gas service. They protect, while allowing gas to flow at a safe pressure. Customers continue to receive gas.
  • Containment. Relief valves do not contain the gas. They protect by dumping the excess gas into the atmosphere.
  • Alerting. Relief valves are usually good in this respect. They are noisy, particularly at full or near full blow. In addition, because the gas is odorized, the smell usually attracts attention. Another indication of overpressure is the rise in outlet pressure above normal, but this is probably the least effective notification.

Monitoring

  • Continuity of Service. Monitoring does not interrupt service. Like the relief valve, the monitor protects while allowing gas to continue flowing.
  • Containment. Monitoring contains the gas. It prevents the gas from blowing into the atmosphere and keeps it inside the piping.
  • Alerting. This is probably the main disadvantage of monitoring. Generally speaking, the only warning or notification is the rise in outlet pressure to monitor set point.

Automatic Shutoff

  • Continuity of Service. Automatic shutoff stops the flow of gas. It protects because it interrupts gas service by shutting off the gas.
  • Containment. Automatic shutoff contains the gas. Like monitoring, it does not allow gas to blow into the atmosphere. It contains the gas within the piping.
  • Alerting. In general, shutting the gas off results in good notification. Usually it is quickly noticed. However, there could be situations where it is not detected immediately and the lack of gas has undesirable or even serious results.

The next sections cover the three basic methods of overpressure protection in more detail.

PRESSURE RELIEF

FIGURE II-4 [refer to PDF version page II-9 for image] is a diagram of a typical relief valve installation. The purpose of the relief valve is to prevent outlet pressure from rising to an unsafe level when there is a regulator failure.

In general, regulator failure would result in either too much or too little pressure downstream. The failure would leave the regulator in what could be called a "failed-open" condition (regulator too far open, even fully open – too much gas flow) or a "failed-closed" condition (regulator too far closed, even fully closed – not enough gas flow). A relief valve is only useful in a "failed-open" regulator condition – too much gas flow, resulting in downstream pressure above normal.

Relief valves do nothing for a "failed-closed" regulator condition – too little gas. A relief valve protects by discharging the excess gas into the atmosphere. As long as a regulator operates correctly and downstream pressure is normal, a relief valve remains closed. If the regulator fails and allows too much gas to flow (a "failed-open" condition for the regulator), downstream pressure will increase. The relief valve will remain closed until pressure reaches its set point. At that point it will begin opening and will continue to do so as the pressure continues to rise. It will open far enough to discharge all of the excess gas into the atmosphere. When it reaches that point, there will be no further rise in the downstream pressure and, if the relief valve and its installation are correctly sized, the pressure downstream will not be high enough to be unsafe.

Keep in mind that the relief valve does not discharge all of the gas into the atmosphere. It only discharges the excess. There is still a normal flow for the load. Customers continue to recieve gas.

Relief Valve Sizing

Sizing is vitally important. This applies not only to the relief valve itself, but also to the piping of the entire installation. A relief valve must be big enough to handle the maximum emergency. When properly installed and maintained, relief valves are very dependable. The question is not so much whether it will work, but rather whether it is large enough to provide full protection during a maximum emergency. When a relief valve is in full operation, it can discharge an enormous volume of gas into the atmosphere. For that reason they cannot be used everywhere.

This must be carefully considered when a relief valve installation is being planned and engineered. The vital questions are these: What happens to the gas after it leaves the relief valve? Will it disperse harmlessly? Or, could it create another emergency? This matter is addressed in 49 CFR §192.199(e).

FIGURE II-4 shows a stop valve ahead of a relief valve. This stop valve is required to allow for system maintenance and testing. However, there can be serious consequences if it is closed during an emergency because this would cut the relief valve out of the pipeline system. Closure could be an innocent act or it could be malicious. Nonetheless, certain cautions are essential.

Only authorized personnel may use the stop valve. Likewise, it must be adequately protected against unauthorized closure. Most important, it should be locked in an open position.

MONITORING

This section deals with the most widely used form of monitoring, standby or passive monitoring. FIGURE II-5 [refer to PDF version page II-13 for image] shows standby monitoring in four basic arrangements using regulators with control lines and with internal control. Note the following:

  • Either the upstream or the downstream regulator can be the monitor.
  • The downstream regulator can have either a control line or internal control.

The upstream regulator must have a control line.

Standby monitoring is sometimes confused with two-stage or double-cut regulation. The big
difference is in the control line for the upstream regulator. In standby monitoring, the control
line for the upstream regulator goes all the way downstream. It does not connect between the
regulators as in two-stage regulation. To repeat, the control line for the upstream regulator in
standby monitoring goes on beyond the downstream regulator to a point somewhere in the outlet
piping. That is the reason the upstream regulator in standby monitoring must have a control line,
whereas in two-stage regulation the upstream, as well as the downstream, regulator can have
either a control line or internal control.

Two-stage regulation can be used as a form of monitoring provided the following conditions are
met:

  • The system downstream of the second stage regulator (including the regulator) must have an MAOP equal to or greater than the outlet pressure of the first stage regulator.
  • The second stage regulator must be rated for an inlet pressure as high as the maximum inlet pressure of the first stage regulator, and the diaphragm case of the first stage regulator must be able to safely withstand this maximum inlet pressure.

As shown in FIGURE II-5, the set point for the operating regulator is the normal outlet pressure, that is, the pressure normally required for the load.

The set point for the monitor is higher. Because it is higher, the monitor is further open than the operating regulator (usually the monitor is wide open) and allows the gas to flow normally.

If the operating regulator "fails-open" the outlet pressure will rise. It will rise until the pressure reaches the set point of the monitor. Then, the monitor will become the operating regulator and will hold outlet pressure at its set point.

The monitor set point, of course, must not exceed the MAOP of the downstream piping system. The difference between the set points of the monitor and the operating regulator is not critical. However, the two should not be so close as to cause the monitor to interfere with the operating regulator. Other than this, monitor set point is largely determined by the requirements of the installation and applicable practices and standards.

AUTOMATIC SHUTOFF

In an automatic shutoff installation, a special valve is used to shut off the gas completely if pressure reaches a preset level. During normal operation the valve remains fully open and allows gas to flow freely.

If a regulator failure ("fail-open") or another factor causes outlet pressure to rise, the automatic shutoff valve closes when pressure reaches its set point.

The normal outlet pressure is the regulator's set point. The set point of the automatic shutoff valve will, of course, be higher. How much higher must be decided when planning and engineering the installation. It must not exceed the MAOP (the maximum safe limit) of the downstream piping.

Automatic shutoff valves close automatically, but must be manually reset. This has the advantage of preventing an emergency from passing unnoticed.

Shutting the gas off at times of emergency is imperative. However, in the natural gas business, continuity of service is also important. This is probably why automatic shutoff has found only limited use in the gas industry. Pressure relief and monitoring are preferred because they offer full protection while allowing a safe flow of gas to continue.

Automatic shutoff valves are available with control line or with internal control. Both are shown in FIGURE II-6 [refer to PDF version page II-16 for image].

Control Line

Because an automatic shutoff valve with a control line is located upstream of the regulator, the foregoing hazards from exposure to inlet pressure are eliminated. The entire regulator, as well as everything downstream, is isolated from exposure to inlet pressure.

Care should be used in installing the control line. It should be strong, and be protected and routed to minimize any possibility of breakage. If broken, the automatic shutoff valve becomes inoperative. If an emergency occurs, it will not close, as it should.

Some automatic shutoff valves are available with a temperature option. They close not only from excess pressure, but also excess temperature. If properly located, they can help in case of fire. Automatic shutoff is also available for closure in case of underpressuring (a "failed-closed" regulator failure).

Relief valves, monitors, and automatic shutoff valves are all effective, dependable devices for protection against the hazard of excess pressure. However, to be sure of this protection, they must be correctly engineered, installed, and maintained. They must be used in conformance with manufacturer's ratings and recommendations. Whenever any doubts or questions arise, it is always a good idea to ask the manufacturer.

Internal Control

This offers a simpler installation because there is no control line. However, due to its internal control, it must be located downstream of the regulator. Therefore, upon closure, everything upstream of the shutoff valve will be pressured to full inlet pressure.

This means that if the regulator has internal control, its main diaphragm will be exposed to full inlet pressure. This could result in severe damage, even to the extent of a burst regulator. The same applies to a regulator with a control line if the control line is connected (the sensing point) between the regulator and the automatic shutoff valve. If an automatic shutoff valve with internal control is used, everything between it and the regulator, including the regulator itself, must be carefully checked for exposure to full maximum inlet pressure.

Moreover, if the piping for the regulator is larger than the inlet piping, an internal control type automatic shutoff valve will need to be a larger size than one with a control line.

Chapter 3 - Corrosion Control
FEDERAL REQUIREMENTS

This chapter contains a simplified description of the corrosion control requirements contained in the pipeline safety regulations. The complete text of the corrosion control requirements can be found in 49 CFR Part 192.

Procedures and Qualifications

Operators must establish procedures to implement and maintain a corrosion control program for their piping system. These procedures should include design, installation, operation, and maintenance activities on a cathodic protection system. A person qualified in pipeline corrosion control methods must carry out these procedures.

Techniques for Compliance

The following is a list of sources where operators of small natural gas systems can find qualified personnel to develop and carry out a corrosion control program:

  • There are many consultants and experts who specialize in cathodic protection. Many advertise in gas trade journals.
  • Another source, especially for master meter operators, is an experienced corrosion engineer or technician working for a local gas utility company. Such experts may be able to implement cathodic protection for small operators, or refer them to local qualified corrosion engineers.
  • Operators of small municipal systems can contact the transmission company that supplies their gas. A municipal corrosion engineer or technician may be able to supply information as to where to find local qualified corrosion engineers.
  • OPS suggests that operators of small natural gas systems encourage their respective trade associations (such as state and local mobile home associations or municipal associations) to gather and maintain records of available consultants or contractors who are qualified in their specific region.
  • The local chapter of "NACE International" (National Association of Corrosion Engineers) may be able to provide useful information.
  • Operators who are unsure of a consultant's qualification in corrosion control should contact operators who have hired the consultant in the past.

Corrosion Control Requirements for Pipelines Installed After July 31, 1971

All buried metallic pipe installed after July 31, 1971, must be properly coated and have a cathodic protection system designed to protect the pipe in its entirety.

Newly constructed metallic pipelines must be coated before installation and must have a cathodic protection system installed and placed in operation in its entirety within one year after construction of the pipeline. However, the operator must make tests no later than six months after installation to demonstrate that no corrosion control measures are necessary. If tests indicate that corrosion control is necessary, the pipeline must be cathodically protected.

OPS recommends that all operators of small natural gas systems coat and cathodically protect all new metallic pipe. It is extremely difficult and costly to prove that a noncorrosive environment exists.

Cathodic protection requirements do not apply to electrically isolated, metal alloy fittings in plastic pipelines if the alloyage of the fitting provides corrosion control, and if corrosion pitting will not cause leakage.

Corrosion Control Requirements for Pipelines Installed Before August 1, 1971

For Pipelines installed before August 1, 1971, (bare pipe or coated pipe), must be cathodically protected in areas that are determined to be active corrosion. All underground natural gas distribution systems, including underground piping related to regulating and measuring stations, must be cathodically protected in areas of active corrosion.

The operator must determine areas of active corrosion by (a) electrical survey, (b) where electrical survey is impractical, by the study of corrosion and leak history records, or (c) by leak detection surveys.

Active corrosion means continuing corrosion, which, unless controlled, could result in a condition that is detrimental to public safety.

As a guideline for operators when determining corrosion to be detrimental to public safety (active corrosion), OPS recommends the following:

  • For master meter operators, all continuing corrosion occurring on metallic pipes (other than cast iron or ductile iron pipes) should be considered active and pipes should be cathodically protected, repaired, or replaced.
  • For operators of small municipal gas systems, all continuing corrosion occurring on the distribution system in city limits (within 100 yards of a building intended for human occupancy, regulator stations, and at highway and railroad crossings) should be considered active and pipes should be cathodically protected, repaired, or replaced. Need to clarify what's needed.
  • OPS recommends that operators of small gas systems and their consultants use these following guidelines in determining where it is impractical to do electrical surveys to find areas of active corrosion:
    1. Where the pipeline is more than 2 feet from the edge of a paved street or within wall to wall pavement areas.
    2. Pipelines in a common trench with other metallic structures.

Electrical surveys may prove to be impractical due to conditions other than those listed above. The operator must demonstrate the impracticability of an electrical survey.

In areas where electrical surveys cannot be run to determine corrosion, the operator should run leakage surveys on a more frequent basis. OPS recommends that these surveys be run at least once a year.

Electrical surveys to find active corrosion must be run by a person qualified in pipeline corrosion control methods.

Coating Requirements

All metallic pipe installed below ground, as a new or replacement pipeline system, should be coated in its entirety (APPENDIX B, FORM 1). Types of coatings and handling practices are discussed later in this chapter.

Examination of Exposed Pipe

Whenever buried pipe is exposed or dug up, the operator is required to examine the exposed portion of the pipe for evidence of corrosion on bare pipe or for deterioration of the coating on coated pipe. A record of this examination must be maintained. If the coating has deteriorated or the bare pipe has evidence of corrosion, remedial action must be taken (APPENDIX B, FORM 1).

Criteria for Cathodic Protection

Operators must meet one of five criteria listed in Appendix D of 49 CFR Part 192, to comply with the pipeline safety regulations for cathodic protection.

The criteria that most operators of small natural gas systems will choose to meet will be a (cathodic) voltage of at least -0.85 volt with reference to a saturated copper-copper sulphate half-cell (Appendix B, Form 14). NOTE: IR drop must be considered.

Monitoring

A piping system that is under cathodic protection must be systematically monitored. Tests for effectiveness of cathodic protection must be done at least once every year. Records of this monitoring must be maintained (APPENDIX B, FORM 14).

Short, separately protected service lines or short, protected mains may be surveyed on a sampling basis. At least 10 percent of these short sections and services must be checked each year so that all short sections in the system are tested in a 10-year period. Examples of short, separately protected pipe in a small natural gas system would be:

  • Steel service lines connected to, but electrically isolated from, cast iron mains.
  • Steel service risers that have cathodic protection provided by an anode attached to a riser that is installed on plastic service lines.

OPS recommends, if a small number of isolated protection sections of pipeline exist in the system, that the operator include all sections in the annual survey.

When using rectifiers to provide cathodic protection, each rectifier must be inspected six times every year. The intervals must not exceed 2½ months, to ensure that the rectifier(s) is properly operating. Records must be maintained (APPENDIX B, FORM 15).

Operators must take prompt action to correct any deficiencies indicated by the monitoring.

Electrical Isolation

Pipelines must be electrically isolated from other underground metallic structures (unless electrically interconnected and cathodically protected as a single unit). For illustrations of where meter sets are commonly electrically insulated, see FIGURES 8, 13, and 14 in this chapter.  [refer to PDF version page III-13 and III-20 for images]

Test Points

Each pipeline under cathodic protection must have sufficient test points for electrical measurement to determine the adequacy of cathodic protection. Test points should be shown on a cathodic protection system map.

Internal Corrosion Inspection

Whenever a section of pipe is removed from the system, the internal surface must be inspected for evidence of corrosion. Remedial steps must be taken if internal corrosion is found. Be sure to keep records of this inspection (APPENDIX B, FORM 1).

Atmospheric Corrosion

Newly installed above ground pipelines must be cleaned and coated or jacketed with a material suitable for the prevention of atmospheric corrosion. Above ground pipe, including meters, regulators, and measuring stations, must be inspected for atmospheric corrosion once every year. Remedial action must be taken if atmospheric corrosion is found (APPENDIX B, FORM 13).

Remedial Measures

All steel pipe used to replace an existing pipe must be coated and cathodically protected. Each segment of pipe that is repaired because of corrosion leaks must be cathodically protected.

Graphitization of Cast Iron

Graphitization is the process by which the cast iron pipe corrodes, leaving a brittle sponge-like structure of graphite flakes. There may be no appearance of damage, but the affected area of the pipe becomes brittle. For example, a completely graphitized buried cast iron pipe may hold gas under pressure but will fracture under a minor impact, such as being hit by a workman's shovel. Cast iron is a metallurgical combination of iron and carbon (graphite).

Each segment of cast iron or ductile iron pipe with Graphitization (to a degree where a fracture or any leakage might result) must be replaced.

Records

Operators must maintain records or maps of their cathodic protection system. Records of all tests, surveys, or inspections required by the pipeline safety code must be maintained. See APPENDIX B for samples of records/forms.

PRINCIPLES AND PRACTICES OF CATHODIC PROTECTION

This section gives operators with little or no experience in cathodic protection, a review of the general principles and practices of cathodic protection. Common causes of corrosion, types of pipe coatings, and criteria for cathodic protection are among the topics. A checklist of steps which an operator of a small natural gas system may use to determine the need for cathodic protection is included. Basic definitions and illustrations are used to clarify the subject. This section does not go into great depth. Therefore, reading this section alone will not qualify an operator to design and implement cathodic protection systems.

Basic Terms

Corrosion is the deterioration of metal pipe. Corrosion is caused by a reaction between the metallic pipe and its surroundings. As a result, the pipe deteriorates and may eventually leak. Although corrosion cannot be eliminated, it can be substantially reduced with cathodic protection (see FIGURE III-1 [refer to PDF version page III-6 for image]).

An example of bare steel pipe installed for gas service. Note the deep corrosion pits that have formed. Operators should never install bare steel pipe underground. Operators should use either polyethylene pipe manufactured according to ASTM D2513 or coated steel pipe as new or replacement pipe. If steel pipe is installed, that pipe must be coated and cathodically protected.

Cathodic protection is a procedure by which an underground metallic pipe is protected against corrosion. A direct current is impressed onto the pipe by means of a sacrificial anode or a rectifier. Corrosion will be reduced where sufficient current flows onto the pipe.

Anode (sacrificial) is an assembly consisting of a bag usually containing a magnesium or zinc ingot and other chemicals, which is connected by wire to an underground metal piping system. It functions as a battery that impresses a direct current on the piping system to retard corrosion (see FIGURE III-2 [refer to PDF version page III-7 for image]).

Sacrificial protection means the reduction of corrosion of a metal (usually steel in a gas system) in an electrolyte (soil) by galvanically coupling the metal (steel) to a more anodic metal (magnesium or zinc) (see FIGURE III-3 [refer to PDF version page III-8 for image]). The magnesium or zinc will sacrifice itself (corrode) to retard corrosion in steel the pipe.

Zinc and magnesium are more anodic than steel. Therefore, they will corrode to provide cathodic protection for steel pipe.

Rectifier is an electrical device that changes alternating current (a.c.) into direct current (d.c.). This current is then impressed on an underground metallic piping system to protect it against corrosion (see FIGURE III-4 [refer to PDF version page III-9 for image]).

This illustrates how cathodic protection can be achieved by use of a rectifier. Make certain the negative terminal of the rectifier is connected to the pipe. NOTE: If the reverse occurs (positive terminal to pipe), the pipe will corrode much faster.

Potential means the difference in voltage between two points of measurement (see FIGURE III-5 [refer to PDF version page III-10 for image]).

The voltage potential in this example is the difference between points 1 and 2. Therefore, the current flow is from the anodic area (1) of the pipe to the cathodic area (2). The half-cell is an electrode made up of copper immersed in copper-copper sulphate (Cu-CuSO4).

Pipe-to-soil potential is the potential difference (voltage reading) between a buried metallic structure (piping system) and the soil surface. The difference is measured with a half-cell reference electrode (see definition of reference electrode that follows) in contact with the soil (see FIGURE III-6 [refer to PDF version page III-11 for image]).

If the voltmeter reads at least –0.85 volt, the operator can usually consider that the steel pipe has cathodic protection. NOTE: Be sure to take into consideration the voltage (IR) drop that is the difference between the voltage at the top of the pipe and the voltage at the surface of the earth.

Reference electrode (commonly called a half-cell) is a device which usually has copper immersed in a copper sulphate solution. The open circuit potential is constant under similar conditions of measurement (see FIGURE III-7 [refer to PDF version page III-12 for image]).

Short or corrosion fault means an accidental or incidental contact between a cathodically protected section of a piping system and other metallic structures (water pipes, buried tanks, or unprotected section of a gas piping system) (see FIGURE III-8 [refer to PDF version page III-13 for image]).

Unshaded piping shows Operators piping from service entry to meter insulator at location shown on sketch above. Shaded areas show house piping, electrical cables, etc.

The circled locations are typical points where the Operators piping (unshaded) can come in metallic contact with house piping. This causes shorting out or "bypassing" of the meter insulator.

The only way to clear these contacts permanently is to move the piping that is in contact. (The use of wedges, etc., to separate the piping is not acceptable). If the above ground piping cannot be moved, install a new insulator between the accidental contact and the service entry.

Stray current means current flowing through paths other than the intended circuit (see FIGURE III-9 [refer to PDF version page III-14 for image]). If your pipe-to-soil readings fluctuate, stray current may be present.

This drawing illustrates an example of stray d.c. current getting onto a pipeline from an outside source. This can cause severe corrosion in the area where the current eventually leaves the pipe. Expert help is needed to correct this type of problem.

Stray current corrosion means metal destruction or deterioration caused primarily by stray d.c. affecting the pipeline.

Galvanic series is a list of metals and alloys arranged according to their relative potentials in a given environment.

Galvanic corrosion occurs when any two of the metals in TABLE 1  [refer to PDF version page III-15 for table] are connected in an electrolyte (soil). Galvanic corrosion is caused by the different potentials of the two metals.

When electrically connected in an electrolyte, any metal in the table will be anodic (corrode relative to) to any metal below it. That is, the more anodic metal sacrifices itself to protect the metal (pipe) lower in the table.)

FUNDAMENTAL CORROSION THEORY

In order for corrosion to occur there must be four parts: An electrolyte, anode, cathode, and a metallic return path. A metal will corrode at the point where current leaves the anode (see FIGURE III-10 [refer to PDF version page III-16 for image]). NOTE: Dissimilar soils may create an environment that enhances corrosion.

  • Current flows through the electrolyte from the anode to the cathode. It returns to the anode through the return circuit.
  • Corrosion occurs whenever current leaves the metal (pipe, fitting, etc.) and enters the soil (electrolyte). The area where current leaves is said to be anodic. Corrosion, therefore, occurs in the anodic area.
  • Current is picked up at the cathode. No corrosion occurs here. The cathode is protected against corrosion. Polarization (hydrogen film buildup) occurs at the cathode. When the film of hydrogen remains on the cathode surface, it acts as an insulator and reduces the corrosion current flow.
  • The flow of current is caused by a potential (voltage) difference between the anode and the cathode.
TYPES OF CATHODIC PROTECTION

There are two basic methods of cathodic protection: the galvanic anode system and the impressed current system.

Galvanic anodes are commonly used to provide cathodic protection on gas distribution systems. Impressed current systems are normally used for transmission lines. However, if properly designed, impressed current can be used on a distribution system (see FIGURE III-11 [refer to PDF version page III-17 for image]).

Any current, whether galvanic or stray, that leaves the pipeline causes corrosion. In general, corrosion control is obtained as follows:

Galvanic Anode System. Anodes are "sized" to meet current requirements of the resistivity of the environment (soil). The surface area of the buried steel and estimated anode life determines the size and number of anodes required. Anodes are made of materials such as magnesium (Mg), zinc (Zn), or aluminum (Al). They are usually installed near the pipe and connected to the pipe with an insulated conductor. They are sacrificed (corroded) instead of the pipe (see FIGURES III-3, III-11, AND III-12 [refer to PDF version page III-8, III-17, and III-18 for images]).

Impressed Current Systems. Anodes are connected to a direct current source, such as a rectifier or generator. These systems are normally used along transmission pipelines where there is less likelihood of interference with other pipelines. The principle is the same except that the anodes are made of materials such as graphite, high silicon cast iron, lead-silver alloy, platinum, or scrap steel.

INITIAL STEPS IN DETERMINING THE NEED TO CATHODICALLY PROTECT A SMALL GAS DISTRIBUTION SYSTEM
  1. Determine type(s) of pipe in system: bare steel, coated steel, cast iron, plastic, galvanized steel, ductile iron, or other.

  2. Date gas system was installed:

    Year pipe was installed (steel pipe installed after July 1, 1971, must be cathodically protected in its entirety).

    Who installed pipe? By contacting the contractor and other operators who had pipe installed by same contractor, operators may be able to obtain valuable information, such as:

    • Type of pipe in ground.
    • If pipe is electrically isolated.
    • If gas pipe is in common trench with other utilities.

  3. Pipe location - map/drawing. Locate old construction drawings or current system maps. If drawings are unavailable, a metallic pipe locator may be used.

  4. Before the corrosion engineer arrives, it is a good idea to make sure that customer meters are electrically insulated. If system has no meter, check to see if gas pipe is electrically insulated from house or mobile home pipe (see FIGURE III-13 [refer to PDF version page III-20 for image]).

  5. Contact an experienced corrosion engineer or consulting firm. Try to complete steps 1 through 4 before contracting a consultant.

  6. Use of Consultant

    A sample method, which may be used by a consultant to determine cathodic protection needs, is provided below:

    • An initial pipe-to-soil reading will be taken to determine whether the system is under cathodic protection.
    • If the system is not under cathodic protection, the consultant should clear underground shorts or any missed meter shorts. (The consultant will probably use a tone test.)
    • After the shorts are cleared, another pipe-to-soil test should be taken. If the system is not under cathodic protection, a current requirement test should be run to determine how much electrical current is needed to protect the system.
    • Additional tests, such as a soil resistivity test, bar hole examination, and other electrical tests, may be needed. The types of tests needed will vary for each gas system.

      Remember to retain copies of all tests run by the corrosion engineer.

  7. Cathodic Protection Design

    The experienced corrosion engineer or gas consultant, will design a cathodic protection system based on the results of testing, that best suits the gas piping system.
INSULATION TESTER

This insulation tester consists of a magnetic transducer mounted in a single earphone headset with connecting needlepoint contact probes. It is a "go" or "no go" type tester which operates from low voltage current present on all underground piping systems thus eliminating the necessity of outside power sources or costly instrumentation and complex connections. By placing the test probes on the metallic surface on either side of the insulator a distinct audible tone will be heard if the insulator is performing properly. Absence of audible tone indicates faulty insulator. Insulator effectiveness can be determined quickly using this simple, easy-to-operate tester.

CRITERIA FOR CATHODIC PROTECTION

There are five criteria listed in Appendix D of Part 192, to qualify a pipeline as being cathodic protected. Operators can meet the requirements of any one of the five to be in compliance with the pipeline safety regulations. Most systems will be designed to Criterion 1.

Criterion 1: With the protective current applied, a voltage of at least -0.85 volt measured between the pipeline and a saturated copper-copper sulfate half-cell. This measurement is called the pipe-to-soil potential reading (see FIGURE III-16 [refer to PDF version page III-22 for image]).

COATINGS

There are many different types of coating on the market. The better the coating application, the less electrical current is needed to cathodically protect the pipe.

Mill Coated Pipe

When purchasing steel pipe for underground gas services, operators should purchase mill coated pipe (i.e., pipe coated during manufacturing process). Some examples of mill coatings are:

  • Extruded polyethylene or polypropylene plastic coatings,
  • Coal tar coatings,
  • Enamels,
  • Mastics,
  • Epoxy.

A qualified (corrosion) person can help select the best coating for a natural gas system. A local natural gas utility may be able to give master meter operators the name and location of nearby suppliers of mill coated gas pipe. When purchasing steel pipe, remember to verify that the pipe was manufactured according to one of the specifications listed in Chapter VI of this manual. This can be verified by a bill of lading or by the markings on mill coated pipe.

Patching

Tape material is a good choice for external repair of mill coated pipe. Tape material is also a good coating for both welded and mechanical joints made in the field. Some tapes in use today are:

  • PE and PVC tapes with self-adhesive backing applied to a primed pipe surface,
  • Plastic films with butyl rubber backing applied to a primed surface,
  • Plastic films with various bituminous backings.

Consult a pipe supplier before purchasing tapes. Tapes must be compatible with the mill coating on the pipe.

Coating Application Procedures

When repairing and installing metal pipe, be sure to coat bare pipes, fittings, etc. It is absolutely essential that the instructions (supplied by the manufacturer of the coating) be followed precisely. Time and money is wasted if the instructions are not followed.

Some general guidelines for installation of pipe coatings:

  • Properly clean pipe surface (remove soil, oil, grease, and any moisture),
  • Use careful priming techniques (avoid moisture, follow manufacturer's recommendations),
  • Properly apply the coating materials (be sure pipe surface is dry - follow manufacturer's recommendations). Make sure soil or other foreign material does not get under coating during installation,
  • Only backfill with material that is free of objects capable of damaging the coating. Severe coating damage can be caused by careless backfilling when rocks and debris strike and break the coating.

[refer to PDF version page III-18 through 21 for images 12, 13, 14, and 15 which describe several important procedures.  In addition, pages III-25 through 29 include images and descriptions of additional tools and procedures which supplement the text above but are not directly referenced.]

Chapter 4 - Leak Detection

This chapter contains a simplified description of the leak detection requirements contained in the pipeline safety regulations. The complete text section 192.723 can be found in 49 CFR Part 192.

METHODS OF DETECTING A LEAK
  1. Odor. Gas is intentionally odorized so that the average person can perceive it at a concentration well below the explosive range. That odorant concentration is generally between 0.5 to 1.0 percent by volume or as local applicable codes dictate. Gas odor is a common and effective indication of a leak. A report of gas odor should be investigated immediately. If a leak is found, the migration pattern of the gas should be determined. If an immediate hazard is determined to exist, the hazard potential should be eliminated and the leak repaired immediately. Appendix 11 of the Gas Piping Technology Committee's "Guide for Gas Transmission and Distribution Piping Systems" (published by the American Gas Association), contains detailed information on leak classification and action criteria. The odor of gas may be filtered out as the odorized gas passes through certain types of soil. It may also be modified by passing through soil and into a sewer system containing vapors or fumes from other combustibles as well as the sewer odor itself. Therefore, odor is not always totally reliable as an indicator of the presence or absence of gas leaks. For this reason all gas leak reports should be investigated using a leak detection instrument such as a Combustible Gas Indicator (CGI) or a Flame Ionization Detector (FI). Gas personnel should remember that the primary purpose of the gas odor is to provide a warning to the public, who do not have gas detection instruments.

  2. Vegetation. Vegetation in an area of gas leakage may improve or deteriorate, depending on the soil, the type of vegetation, the environment, the climate, and the volume and duration of the leak. Changes in vegetation may indicate slow below ground leaks. A vegetation survey by itself is not an acceptable method of complying with the pipeline safety regulations (see 49 CFR §192.723). Leak surveys should be conducted with leak detection equipment.

  3. Insects (flies, roaches, spiders). Insects migrate to points or areas of leakage due to microbial breakdown of some components of gas. Some insects like the smell of the gas odorant. Heavy insect activity, particularly near the riser, the gas meter, or the regulator, can sometimes indicate a gas leak.

  4. Fungus-like Growth. Such growth in valve boxes, manholes, etc., may indicate gas leakage. These fungi grow best where there is a lack of oxygen, such as in a gas leak area. The color of the growth is generally white or grayish-white similar to a coating of frost. All such indications should be investigated with a leak detection instrument. Personnel should never enter manholes or other confined spaces without first testing oxygen levels and gas concentrations. Check Occupational Safety and Health Administration (OSHA) regulations concerning confined space entry for further details on this subject.

  5. Sound. Listen for leaks. A hissing sound at a bad connection, a fractured pipe, or a corrosion pit is the usual indication of a gas leak. Using a soap solution directly on the pipe or fitting will indicate the presence of a leak. If a strong gas odor is in the air, care should be taken to turn on and zero gas detection equipment away from the area where the odor is present.

  6. Unaccounted for Gas. A possible leak is indicated when an off-peak reading of a master meter with a known average seasonal utilization rate, shows unaccountably high usages rate. Periodic off-peak checks (preferably in the summer months from midnight to 3 or 4 a.m.) can be averaged to provide data for comparison in future checks. This method may indicate a leak on the system, but will not provide a location for the leak. It is also most effective if consumption figures are known for a time period before the leak(s) occurred. A comparison of bills from the gas supplier showing gas consumption may also indicate leakage on the system. This procedure is also most effective when comparing consumption during summer months over a period of several years. If excess consumption is suspected, the system should be leak surveyed using gas detection equipment.

    Gas leaks in residential areas (served by a master meter as well as by customer meters) can be detected by comparing the total consumption registered on the customer meters with that registered on the master meter. If the master meter reading is greater than that recorded by adding all the unit meter readings, then a leak probably exists in the distribution system. This condition may also indicate gas theft or a malfunctioning meter problem. If this method is used, the individual or customer meters should be read on the same day as the master meter. This will allow a more accurate comparison of gas volumes.

    For a municipal system, an unexpected increase in the amount of natural gas purchased from the transmission company for a given month, as compared to past gas consumption for the same month, may indicate a leak in the system. The operator is cautioned that changes in load factors and weather must be considered when using this method. The operator should be sure to compare similar time periods, as a change in the meter reading cycle will affect this process. Dividing the gas purchased by the number of days in the billing cycle will give an average per day consumption, which would be more accurate to use in comparing bills. Low load periods such as the summer months would provide the best data.

  7. Soap Solutions. A soap solution can pinpoint the location of a leak on an exposed pipe, on the riser, or on the meter. The solution is brushed or sprayed on and the location of bubbling indicates leakage. When excavating underground piping to investigate a suspected leak location, the pipe should be brushed clean and completely expose the top, sides and bottom. Many leaks are found on the bottom of the pipe. A mirror may be used to observe the underside of the pipe. NOTE: It is recommended that a soap solution specifically designed for pipelines be used.

  8. Leak Detection Instruments. Gas leak indicators are sophisticated instruments that require regular care, maintenance, and calibration, and should be used by trained personnel. Two types are commonly used by the gas industry for surveying and pinpointing leaks:
    • Combustible gas indicator (CGI),
    • Flame ionization (FI) gas detector.

      A third type of instrument, called a bead sensor type detector, is most often used for inspecting exposed piping and appliances to pinpoint leaks on those facilities. Bead sensor instruments are not generally used for leak surveys of underground piping.
DESCRIPTION OF LEAK DETECTION EQUIPMENT

Combustible gas indicator. The CGI (FIGURE IV-3 [refer to PDF version page IV-3 for image]) consists of a meter, a probe, and an aspirator bulb. The bulb is pumped by hand to bring a sample of air into the probe and the instrument. The dial on the instrument indicates the percentage of flammable gas in air (percent gas scale) or percent of the lower explosive limit (LEL) scale. These instruments must be calibrated for the type of gas in the system. The CGI should be calibrated for natural gas for use on a natural gas system.

[refer to PDF version page IV-4 for Figure IV-3a and IV-4]

The CGI is not suitable for above ground surveys. The CGI was designed primarily for use in a confined space. Its two main applications for outside surveys are termed "available openings" and "bar holing." A bar hole is a small diameter hole made in the ground in the vicinity of gas piping to extract a sample of the ground atmosphere for leak analysis. NOTE: Use extra caution when bar holing in the area of polyethylene pipe.

The CGI instruments are also useful in building surveys and in areas within a building, such as heater closets, and other confined areas. The bead sensor unit is also used in these locations. However, it does not give readings in percent of gas or percent of LEL, and must not be used for determining if a hazard exists. A CGI should always be used first when entering a building to determine if a hazardous atmosphere is present. Once the atmosphere has been determined to be non-hazardous (no LEL or gas readings), a bead sensor may be used for an inside leak survey.

One person can operate the CGI. Leak location is accurate and minimal training is necessary to use the instrument. The cost of a CGI is substantially lower than an FI unit.

The Flame Ionization (FI) detector uses a hydrogen fuel to power a small flame in a detector cell. A pump or venturi system is used to pass continuous air samples through the detector cell. If the air contains hydrocarbons such as natural gas, they will be burned or ionized in the hydrogen flame. This is detected electronically and displayed on a meter readout. FI units are equipped with meters that indicate gas concentrations from 1 part per million (PPM) to 10,000 PPM (which is the same as one- percent gas in air). They are also equipped with audible alarms to alert the operator when there is a meter deflection.

Leak survey can be done more rapidly with an FI unit than with a CGI using the bar hole method. FI units can be carried by hand for a walking survey or mounted on a vehicle for a mobile survey. Any gas indications detected by the FI should be confirmed using a combustible gas indicator. Leak pinpointing is also done with a CGI.

Leak survey technicians must be trained and qualified in the operation of the FI and CGI. Additional training is required on leak survey procedures, leak classification, recognition of hazards and pinpointing. All gas personnel should also receive training on "make safe" actions. Gas operators are not required to own FI equipment or to conduct their own leak surveys. They may choose to hire a leak survey consultant to conduct inspections. Consultants should also be trained in these topics and are required to be in a drug and alcohol-testing program, the same as gas personnel.

[refer to PDF version page IV-6 and 7 for Figure IV-5 and 6]

RECOMMENDED METHOD FOR SURFACE GAS DETECTION SURVEY WITH FI UNIT (NATURAL GAS SYSTEM ONLY)

The ability of the gas to vent at the ground surface is critical for the success of a surface survey with an FI unit (FI is not to be used when the ground is frozen). A continuous sampling of the atmosphere at buried main and services should be made at ground level or at no more than 2 inches above the ground surface. In areas where the gas piping is under pavement, samplings should also be at curb line(s), available ground surface openings (such as manholes, catch basins, sewers, power, telephone duct openings, fire and traffic signal boxes, or cracks in the pavement or sidewalk), or other interfaces where the venting of gas is likely to occur. For exposed piping, sampling should be adjacent to the piping.

In wet, frozen, or windy conditions the gas may be restricted from venting or be rapidly diluted below FI detection levels. One method to determine if conditions are appropriate for leak survey is to re-survey a known small leak on the system. If it can be detected at normal walking or driving speeds, the survey can continue.

[refer to PDF version page IV-8 for Figure IV-7]

This figure shows leaking gas following the sewer line into the home, after leaking at the service tee. Natural gas can migrate in this manner.

[refer to PDF version page IV-8 for Figure IV-8]

This is an example of how a gas leak can get into a sewer system. This is why it is essential when conducting a leakage survey to check all available openings, including manholes, sewers, vaults, etc. Any indication of gas in a confined space or in a building should be considered a hazardous situation. Persons should be removed from the area, and ignition sources eliminated. Once this is done, the leak investigation should begin, and the leak repaired when found. The facilities affected should be monitored, and the gas migration pattern determined. Gas should be vented from the soil and structure before allowing persons to return to the area.

ODORIZATION EQUIPMENT

This chapter provides information for natural gas system operators who odorize their own gas. All of the equipment and illustrations refer to natural gas systems.

The following are some illustrations and brief discussions of odorization equipment used by operators of small natural gas systems.

[refer to PDF version page IV-9 for Figure IV-9]

The figure shows equipment which odorizes the gas by having natural gas flow across a wick saturated with odorant (generally used for individually odorized lines such as farm taps).

NOTE: Pitot tube version eliminates wick and lessens summer problems with odorization process.

[refer to PDF version page IV-10 for Figure IV-10]

Equipment in which a portion of the main gas stream is diverted, by an orifice plate or partially closed valve in the line, through a tank provided with baffles or wicking. The odorant-saturated portion of the bypass gas is then returned to the main stream. Generally used for low, more uniform flows.

Odorization equipment may need seasonal adjustments. Valves that regulate the amount of gas diverted into the odorizer need to be adjusted between seasons of high flow and low flow of gas (winter vs. summer). Based on the equipment manufacturer's recommendation, operational instructions for specific systems can be developed. These instructions should be included in the operations and maintenance plan.

Equipment Selection Considerations

Selection of the appropriate odorant and odorizing equipment may require professional advice. Operators should consult with an odorant and/or equipment supplier who can help guide odorant selection. These persons can evaluate an operator's unique pipeline situation and advise on the best odorant and the best equipment. Operators are encouraged to consult with more than one of these organizations to obtain the best odorant and equipment for the best price.

Types of Odorants

Most odorants used in the United States are mercaptans or mercaptan sulfide blends, both of which contain tertiary butyl mercaptans as their main component. The only other odorant in wide use is cyclic sulfide (thiophane), which is mainly used in gas systems containing natural odorants. It is also used in farm tap odorizers.

The human sense of smell is very discerning and can detect mercaptans at a concentration of only 1 part per billion (ppb), which is currently beyond the capabilities of most instruments. The sulfur content of the odorants in the gas stream can be measured by gas analysis, which may then be used to determine if there is sufficient odorant.

The main types of detectors are odor concentration meters, titrators, and gas chromatographs dedicated to sulphur analysis. Of these instruments, the most common is the odor concentration meter. The pipeline safety regulations require operators to odorize a combustible gas in a distribution pipeline. The operator is referred to 49 CFR §192.625 for the existing requirements regarding odorization of gas.

Discussion of Odor Testing Instruments

Odor testing instruments are used to determine the lowest concentration at which gas can be detected through odor (see FIGURE IV-11 [refer to PDF version page IV-13 for image]). The unit is actually a measuring device that indicates the percent of gas by volume in a sample when an odor is detected. To determine the odor threshold level, the unit is used in an area where it can draw in fresh air and be connected to a gas source. A blower in the unit draws ambient air through the analyzer and out the exhaust chamber. The procedure for running a test is as follows: After the instrument is connected to gas and running, quickly open the gas valve fully to make certain that gas is entering the instrument and then shut the valve quickly. Wait for any odor to dissipate and then proceed with the test. With just air coming from the exhaust port, inhale or "sniff" at the opening. There are two important points to remember when running a test. First, put the nose as close to the opening as possible (see FIGURE IV-12 [refer to PDF version page IV-13 for image]), as this is the location at which the instrument is calibrated. If the operator does not put his or her nose close to the opening, the sample will be diluted by surrounding air and not representative of the percent gas shown by the odor testing instrument. Second, after sniffing at the opening, immediately withdraw the nose to fresh air and take a breath. If the nose is left at the opening, the mercaptan odor will temporarily deaden the
operator's sense of smell.

To repeat, take a sniff or two of only air at the opening, getting a breath of fresh air between sniffs, and become familiar with the smell of the air coming from the instrument. The operator does this because each instrument has its own unique background odor. After a couple of sniffs of air at the opening, slowly open the gas valve and sniff. Continue to open and sniff, getting a breath of fresh air between sniffs. Repeat this procedure until a change in odor can be detected. At that point record the percentage of gas and mark it "threshold." Threshold, as used here, is the minimum concentration of a gas in air at which one can detect a change in odor. The odor cannot be readily identified at that concentration, but a change in odor is barely detectable. Do not shut the valve but continue to open and sniff (getting a fresh breath in between, and remembering to put the nose as close as possible) until there is a sufficient odor for the operator to decide that the odor is a readily detectable gas odor. Record that reading and mark it "readily detectable." Turn off the gas valve at this point.

Do not skip the threshold part of the test. This part of the test is very important because it slows the operator's decision process and prevents him from making a premature decision. Manufacturers recommend that odor testing instruments be recalibrated on an annual basis, and are currently offering to update old instruments.

Monitoring Techniques

  • Operators of master meter or small natural gas systems should periodically verify the odor level with the gas company or have a consultant run an odor test using some type of odor testing instrument on the gas in the system to determine if it is properly odorized. The best time would be when there is a low usage of gas by customers. Operators should check with their respective state regulatory agencies to see whether there are additional requirements.
  • Operators should include as an operating procedure the requirement that "sniff tests" be made whenever a meter set, repair to system, or leak check is made. A sniff test is when one or more observers smell gas from an open valve, or gas burner. The name of the person, the date, and location of the test must be kept on file.
  • Operators should make a sniff test at extremities of the system at least once a month.
RECORDS

Operators must record all leakage surveys, leaks found, and all repair data. The sample form in Appendix B may be used. Remember that operators can develop their own forms (see APPENDIX B, FORM 2).

Records must include leak reports received from customers or tenants. A sample form for the recording of these leak reports is in APPENDIX B, FORMS 2 AND 3.

GPTC – GUIDE MATERIAL FOR "LEAK CLASSIFICATION AND ACTION CRITERIA"

GPTC has developed guidance material for "Leak Classification and Action Criteria" (see FIGURE IV-13 [This image has not been located in the PDF version], TABLES 3A, 3B AND 3C [refer to PDF version page IV-15 through 17 for these tables]).

FOLLOW-UP INSPECTION

The adequacy of leak repairs should be checked before backfilling. The perimeter of the leak area should be checked with a CGI. Where there is residual gas in the ground after the repair of a Class 1 leak, a follow-up inspection should be made as soon as practical after allowing the soil atmosphere to vent and stabilize. OPS suggests follow-up inspection within 24 to 48 hours, but in no case later than 1 month following the repair. In the case of other leak repairs, qualified personnel should determine the need for a follow-up inspection.

A method to remember when investigating gas leaks and determining the classification is to ask, "WHERE is the Gas?" as follows:

  • Where is the gas? (Use a detector to confirm gas is present)
  • How much is there? (Take readings on the CGI)
  • Extent of the spread? (Determine the migration pattern)
  • Relation to other structures? (Is gas detected in or near buildings or in manholes?)
  • Evaluate/evacuate? (Classify the leak and take appropriate action)
Chapter 5 - Unaccounted for Gas

Unaccounted-for gas is the difference between the amount of gas purchased and the quantity of gas sold, whether it is more or less.

The term, "unaccounted-for gas," does not always indicate a leak. Leakage is only one of a number of factors contributing to unaccounted-for gas. There are 17 or more conditions that may contribute to unaccounted-for gas. For a given gas leak, each system will be affected differently by these conditions because there are no two systems exactly the same as to piping and customer mix.

The causes for unaccounted-for gas can be grouped into two categories. One is leaks and the other gas measurement. Leaks are defined as gas escaping to the atmosphere at a given rate at an unknown location. The rate of gas loss is dependent on the pressure and the size of the hole. Normally, gas leakage will be at a fairly constant rate and will increase gradually with time if not located and repaired. Gas lost through measurement or the lack of measurement is very deceptive and at times very difficult to detect. Gas measurement is defined as the accounting of all gas bought and sold.

Let's start with the gas purchase station. This station is normally owned and maintained by the seller of the gas to the gas utility and is normally called a gate station. Very few small utilities have check meters to monitor the accuracy of these gate stations to ensure the accuracy of the measurement. It is important to know what size cubic foot of gas is being purchased. Normally the gas volume at a gate station is corrected to a temperature of 60°F at a base pressure of 4 oz. If the gas being sold is not corrected to the same conditions, there will be unaccounted-for gas.

Let's see how temperature can affect accuracy. The purchased gas volume was calculated at 60°F. At what temperature is the gas being sold? Naturally the ambient temperature affects the gas temperature. The amount of the effect is determined by the depth of the pipeline in the ground. The deeper the pipe, the more insulation the ground offers and the closer the gas temperature will be to 60°F. If the gas mains and services are aboveground or close to the surface, the gas temperature is relatively close to the air temperature on any given day.

For every 5°F above or below 60°F, the gas volume will change by about 1 percent. This may not sound like much; however, if the average winter temperature for a 3-month period is 30°F, 6 percent unaccounted-for gas can be expected for this period. This loss can only be corrected by the use of temperature compensated meters. No temperature multiplier can be used to correct the volume unless a temperature volume instrument is used on the sales meter. Gas utilities sell the majority of their gas during the winter months so the small amount of gas sold during the hot summer will offset the losses.

How does metering pressure affect unaccounted-for gas? Gas is purchased at a 4-oz. pressure or at least the volume is corrected to 4 oz. As the pressure increases above the 4-oz. base, the volume of gas becomes smaller. For every 2-oz. change above the 4 oz., there is an expected loss of about 1 percent. Therefore, if the service regulators are delivering 8-oz. gas through the meters, approximately 2 percent unaccounted-for gas can be expected. For delivery at 10 oz., approximately 3 percent unaccounted-for gas can be expected. Pressure compensated indexes are not normally used for domestic house meters. However, they are available for the large commercial and industrial meters. If a pressure compensated index is used, care must be taken to ensure that the meter pressure is the same as the index pressure. The pressure compensated index will only correct for a constant pressure.

Pressure and temperature errors in gas measurement are second only to leaks as a contributing factor to unaccounted-for gas. By calculating unaccounted-for gas as a percentage of the total gas purchased, it can be determined whether the loss is due to leaks or gas measurement. If all the loss is due to leaks, there will be a higher percentage of unaccounted-for gas during the summer months. The percentage due to leaks may be slightly higher in the winter if the gas system pressure is raised, but it will not normally be very noticeable. Gas loss due to pressure differences will, if the pressure at the meter is the same in the summer and winter, show the same percentage of unaccounted-for gas throughout the entire year.

Loss due to temperature will show a higher percentage during the cold months, and, after leaks, can be the most costly. In summary, if the percent of unaccounted-for gas is up during the summer months, look for leaks. If it increases during the winter months, look for measurement errors probably caused by temperatures.

There are many other causes for unaccounted-for gas, one being inaccurate gas meters. To determine the overall accuracy of the meters, take a random sample of meters of all ages and test them. By averaging the accuracy of the sample meters, the overall accuracy of the meters in the entire distribution system can be estimated. Taking the average of the meters brought in during a regular changeout will only indicate the accuracy of the meters that have been installed for a long period. If the overall accuracy is poor, it may indicate that the changeout period should be shortened to improve accuracy.

Gas theft, bad meters, or dead meters will normally show up in the monthly billing, so always be on the lookout for unexplained reductions in gas usage for a particular customer. Remember that fill comparisons, supplemented by an alert meter reader, are the best way to detect gas thefts. The hardest theft to detect is when only a small amount of gas is stolen each month. This can be accomplished by reversing the meter in the line for a few days a month or with a meter bypass. Gas theft, accomplished via bypass or by other methods, will cause hazardous conditions that warrant a safety investigation. The thief in some cases is nearly impossible to catch unless elaborate means are taken to seal the meter, the meter nuts, stopcocks, regulators, and other related equipment. The old adage, "if there is a will, there is a way," applies to the gas thief.

Unaccounted-for gas is a serious problem. By taking a positive approach, the majority of the causes can be determined and corrected.

Chapter 6 - Repairs and New Construction

This chapter is designed to help the operators of small natural gas systems meet the construction and repair requirements set by the pipeline safety regulations. It outlines construction, pipe handling, and pressure testing requirements for installation of safe natural gas systems. It explains the procedures to qualify a person to make a pipe joint. It gives directions for locating "qualified persons" to do construction and repair work on a gas system. Remember, it is always the operator's responsibility to see that a contractor follows all requirements.

Manufacturers of pipe, valves, fittings, and other gas system components must design and test them to mandatory industry specifications. The specifications are incorporated by reference into 49 CFR Part 192, the gas pipeline safety regulations. Components meeting the requirements are qualified for gas service and marked with the "approved" markings. In addition, manufacturers usually develop procedures for joining their products and joining other materials to their products. Manufacturers produce manuals and provide procedures for installation and operation that must be incorporated in the operator's operations and maintenance plans.

PLANNING AHEAD

It is essential that a natural gas operator know the types of material and various elements of its gas piping system. A piping system consists of pipes, valves, fittings, regulators, relief devices, and meters. The operator must select components for the system that meet all applicable standards and that comply with the pipeline safety regulations. For example, to develop a cathodic protection program, it is necessary to know the type of metal piping in the system.

Records of the type and location of system components are critical for planning purposes. Operators who are uncertain of the type of material in their gas piping system must identify the materials. This may be done in one of the following ways:

  • Contact previous owners of the system.
  • Contact the contractor who installed and/or maintained the system.
  • Check state, city or county permits.
  • Carefully expose the pipe in certain locations to determine the type of materials and components.

Operators unfamiliar with the types of material must rely on a qualified person to identify the components. These investigations may require the operator to engage a consultant if in-house expertise is lacking.

EXCAVATION

Excavation must not be conducted in and near the location of an underground facility without first ascertaining the location of all underground facilities which could be affected by the excavation.

Prior to any excavation, each excavator must serve notice of intent to excavate to the One-Call Center serving the area in which the proposed excavation will occur. Notice must be given to the local One-Call Center in accordance with local state regulations in advance of excavation. This requirement may vary from 24-72 hours.

EMERGENCY EXCAVATION

An emergency excavation is an excavation which is performed to eliminate an imminent damage to life, health, or property. Oral notice of the emergency excavation must be given as soon as possible to the One-Call Center or to each operator having underground facilities in the area. If necessary, emergency assistance must be requested from each operator to locate and protect its underground facilities.

PRECAUTIONS TO AVOID DAMAGE

Each person responsible for an excavation or demolition operation must:

  • Plan the excavation to avoid damage to underground facilities in and near the construction area.
  • Maintain a safe clearance between the underground facilities and the cutting edge of any mechanized equipment, taking into account the known limit of control of the cutting edge to avoid damage to facilities.
  • Provide support for underground facilities in and near the construction area during excavation and backfilling operations to protect the facility.
  • Dig test pits to determine the actual location of gas facilities if these facilities or utilities are to be exposed or crossed.
EXCAVATION: REPAIR OF DAMAGE

Each person responsible for excavation operations which results in damage to an underground facility must, immediately upon discovery of that damage, notify the operator of the facility of the location and nature of the damage. The operator shall have reasonable time to accomplish necessary repairs before the excavation or backfilling in the immediate area of damage is continued.

Each person responsible for an excavation operation that damages an underground facility and permits the escape of any flammable or toxic gas shall, immediately upon discovery of that damage, notify the operator, local police, and the local fire department. Then take any actions necessary must be taken to protect persons and property and to minimize the hazards until arrival of the operator's personnel or police and fire departments.

RECOMMENDATION

It is in the public interest to promote the protection of citizens, workers, and property in the vicinity of underground facilities. Also, it is in the public interest to promote the health and well being of the community by preventing the interruption of essential services that may result from damage to underground facilities. It is recommended that all underground (gas) utility operators become members of, participate in, and share in the cost of their area's One Call Center.

PIPE INSTALLATION, REPAIR, AND REPLACEMENT: GENERAL COMMENTS

Gas service lines must be installed with at least 12 inches of cover in private property and at least 18 inches of cover in streets and roads. Gas mains must have at least 24 inches of cover.

Qualified personnel must conduct installation of gas pipes. Local gas utilities and local gas associations may be able to recommend qualified persons/contractors who have the necessary background for gas pipe installation. However, contractor work must be supervised carefully. The following sections list the minimum requirements for pipe joining and construction activities.

METALLIC PIPE INSTALLATION

All the conditions listed below must be met when installing metallic pipe.

  • Make each joint in accordance with written procedures that have been proven by test or experience to produce strong, gas-tight joints.
  • Obtain and follow the manufacturer's recommendations for each specific fitting used. See FIGURE VI-1 for examples of manufacturer's instructions for a mechanical coupling. Include the manufacturer's procedures in the operations and maintenance plans.
  • Handle pipe without damaging the outside coating. If the coating is damaged, accelerated corrosion can occur in that area.
  • Coat or wrap steel pipe at all welded and mechanical joints before backfilling.
  • Pressure test new pipe for leaks before backfilling. Mains and services to be operated at 60 psig or less must be tested to 100 psig. This test must be maintained for at least 1 hour. When performing maintenance, short sections of pipe may be pre-tested prior to installation.
  • Support the pipe along its length with proper backfill. Make certain that backfill material does not contain any large or sharp rocks, broken glass, or other objects that could scrape the coating or dent the pipe.
  • Cathodically protect steel pipes.
  • Electrically insulate dissimilar metals (see CHAPTER III for illustrations).

If welding steel is necessary in a pipeline, review the pipeline safety regulations in Subpart E of 49 CFR Part 192. Remember: welding must be performed in accordance with established written welding procedures that have been qualified and tested to produce sound ductile welds, and must be performed by welders who are qualified for that welding procedure. Some states have special welding certification programs.

Welding of steel pipe is difficult. Both the procedures and the personnel must be qualified for the type of weld performed. If welding is done on a gas system, qualified welders can be referred by:

  • the local gas utility;
  • local gas associations;
  • consultants.

PLASTIC PIPE INSTALLATION

Plastic pipe is commonly used for distribution mains and services by the gas industry. Polyethylene (PE) pipe is recommended as the most suitable plastic pipe for natural gas piping. Acceptable PE plastic pipe is manufactured according to standard ASTM D2513 and is marked with that number.

Plastic pipe is unsuitable for aboveground installation. Plastic pipe must be buried or inserted. The operator must include written joining procedures in its operations and maintenance plan. Each joint must be made in accordance with written procedures that have been proven by test or experience to produce strong gas-tight joints. Plastic pipe joining procedures can be obtained from qualified manufacturers. Do not purchase a product if the manufacturer or supplier does not certify it for qualified joining procedures.

If a contractor installs PE plastic pipe, the operator is responsible to ensure that only PE pipe manufactured according to ASTM D2513 is installed. In addition, the operator must verify that the contractor follows written joining procedures that meet the manufacturers' recommended joining procedures for each type of pipe and fitting used. No person may make a plastic pipe joint unless that person has been qualified under the applicable joining procedure by making a specimen joint that passes inspection and test.

The specimen joint must be visually examined during and after joining and found to have the same appearance as a joint or photograph of a joint that is acceptable under the procedure. In the case of heat fusion, the specimen must be cut into at least three longitudinal straps, each of which is:

  • Visually examined and found not to contain voids or discontinuities on the cut surfaces of
    the joint area;
  • Deformed by bending, torque, or impact, and if failure occurs, it must not initiate in the
    joint area.

A person must be requalified under an applicable procedure, if during any 12-month period that
person:

  • Does not make any joints under the procedure;
  • Has 3 joints or 3 percent of the joints made, whichever is greater, that are found unacceptable by testing.

[Figures VI-1 through VI-8 can be viewed on PDF pages VI-6 through VI-11]


The general guidelines to follow when installing plastic pipe are listed below:

  1. Install plastic pipe manufactured under the ASTM D2513 specification. The pipe must have ASTM D2513 marked on it.

[Figure VI-9 can be viewed on PDF page VI-12]

  1. Make each joint in accordance with written procedures that have been proven by test to produce strong gas-tight joints.

    The manufacturer of the pipe or fitting should supply the operator with the procedures for each product in the manufacturer's manual. When installing the pipe, make certain that these procedures are followed. A qualified person must make all joints.

  2. Install properly designed valves in a manner that will protect the plastic material. Protect the pipe from excessive twisting, shearing, or cutting loads when the valve is operated. Protect from any secondary stresses that might be induced through the valve or its enclosure.

  3. Prevent pullout and joint separation. Plastic pipe must be installed in such a manner that expansion and contraction of the pipe will not cause pullout or separation of the joint. Operators unfamiliar with plastic pipe should have a qualified person perform all joining procedures.

  4. When inserting plastic pipe in a metal pipe, make allowance for thermal expansion and contraction. Make an allowance at lateral and end connections on inserted plastic pipes, particularly those over 50 feet in length. End connections must be designed to prevent pullout caused by thermal contraction. Fittings must be able to restrain a force equal to or greater than the strength of the pipe. To minimize the stress caused by thermal contraction, pipes inserted in the summer should be allowed to cool to ground temperature before tie-ins are made. Inserted pipes, especially those pulled in, should be relaxed, mechanically compressed, or cooled to avoid initial tensile stress. Operators unfamiliar with proper insertion techniques must have a qualified person develop the procedures.

  5. Repair or replace imperfections or damages before placing the pipe in service.

  6. Install all plastic mains and service lines below ground level. Where the pipe is installed in a vault or other below-grade enclosure, it must be completely encased in gas-tight metal pipe with fittings that are protected from corrosion. Plastic pipe installation must minimize shear and other stresses. Plastic mains and service lines that are not encased must have an electrically conductive wire or other means of locating the pipe. Plastic lines must not be used to support external loads.

[View Figure VI-11 through VI-13 on PDF pages VI-14 through VI-16]

  1. Test installed plastic pipe to 100 psig for at least 1 hour.

  2. Ensure that plastic pipe is continually supported along its entire length by properly tamped and compacted soil. To prevent any shear or other stress concentrations use external stiffeners at connections to main, valves, meter risers, and other places where compression fittings might be used.

  3. In laying of plastic pipe, ensure adequate slack (snaking) in the pipe to prevent pullout due to thermal contraction.

  4. Lay plastic pipe and backfill with material that does not contain any large or sharp rocks, broken glass, or other objects that could cut or puncture the pipe. Where such conditions exist, suitable bedding (sand) and backfill must be provided.

  5. Take special care to prevent coal tar type coatings or petroleum base tape from contacting the plastic pipe. It can cause plastic pipe to deteriorate.

  6. Static electricity can ignite a flammable gas-air atmosphere. When working with plastic pipe of any kind where there is (or there may be) the possibility of a flammable gas-air atmosphere, take the following precautions:
    • Use a grounded wet tape conductor wound around, or laid in contact with, the entire section of the exposed piping.
    • If gas is already present, wet the pipe starting from the ground end with a very dilute water and detergent solution. Apply tape immediately and leave it in place.
    • Wet the tape occasionally with water. Where temperatures are below freezing (0°C/32°F) add glycol to the water to maintain tape flexibility. Ground the tape with a metal pin driven into the ground.
    • Do not vent gas using an ungrounded plastic pipe or tubing. Even with grounded metal piping, venting gas with high scale or dust content could generate an electric charge in the gas resulting in an arc from the dusty gas cloud back to the pipe which could ignite the gas. Vent gas only at a downwind location remote from people or flammable material.
      • NOTE: Dissipating the static charge buildup with wet rags, a bare copper wire, or other similar techniques may not be as effective as the above procedure. In all cases, use appropriate safety equipment such as flame resistant and static free clothing, breathing apparatus, etc.

  7. Ensure that adequate and appropriate maps and records are retained after system installation.

 

REPAIR METHODS: PLASTIC AND METAL

Replacement of gas lines and repair of leaks are highly specialized and potentially hazardous operations. A qualified person must only conduct them.

Leaks in service lines or mains may be repaired by cutting out a short length of pipe containing the leak and replacing it with a new, pretested segment of pipe. Mechanical couplings are commonly used for this purpose (see FIGURE VI-2). Remember that written procedures must be followed for each joint. The procedures can be obtained from the manufacturer of the mechanical coupling. If the operator intends to make the repair with a mechanical coupling, the written procedures must be incorporated into the operations and maintenance plan.

Small leaks in steel service lines or mains, such as those resulting from corrosion pitting, must be repaired with an appropriate leak clamp applied directly over the leak. All bare metal pipe and fittings installed below ground must be properly coated and cathodically protected before backfilling.

If several leaks are found and extensive corrosion has taken place, the most effective solution is to replace the entire length of deteriorated pipe. Normal installation practices must be followed. They include priming and wrapping of all bare metallic piping and fittings, proper grading of lines to the main, cathodic protection, etc.

Leaking metal pipe can often be replaced by inserting PE pipe manufactured according to ASTM D2513 in the existing line and making the appropriate connections at both ends. Again, operators are cautioned that allowance for thermal expansion and contraction must be made at lateral and end connections. Operators unfamiliar with insertion techniques, including proper anchoring and offset connections, should have a qualified contractor perform this work. Some PE pipe manufacturers provide procedures for installation of their products by insertion.

One source of failures in plastic pipe is breaks associated with the transitions between plastic and metal pipes at mechanical fittings. The primary source of the problem is inadequate support of the plastic pipe. It is critical to firmly compact soil under plastic pipe to provide proper support. In practice, however, it is laborious, time consuming, and difficult to achieve adequate compaction under such joints. Further, as the soil settles, stress may build and the insert sleeve will cut through the pipe. For example, an insert sleeve must be used in the plastic pipe to provide proper resistance to the clamping pressure of mechanical fittings. This internal tubular sleeve must extend beyond the end of the mechanical fitting. If the pipe is not properly supported at that point, the end of the insert sleeve may sheer off the plastic pipe. This source of failure in plastic pipe can be reduced or eliminated by using a properly designed outer sleeve to prevent stress concentrations at the point where the plastic pipe leaves the mechanical fitting.

The most prevalent cause of breaks or leaks in plastic pipe is "third-party" damage, usually by an excavator breaking or cutting the pipe. Plastic pipe is more vulnerable to such breaks than steel pipe. The lower strength of plastic pipe, however, is not necessarily a disadvantage. For example, if digging equipment hooks and pulls a steel pipe it may not break, but may be pulled loose from a connection at some distance from the digging. The resulting leaks could go undetected for a period of time and may result in a serious incident. Although there is no assurance that the plastic pipe will not also pull out, it is more likely to break at the point of digging, where the break can be detected and repaired. After a leak has been repaired with a coupling or a clamp, a soap-bubble test must be conducted to ensure the leak is repaired.

ALL SOURCES OF IGNITION SHOULD BE KEPT AWAY FROM THE LEAK REPAIR AREA. OPEN FLAMES SHOULD NEVER BE USED TO DETECT A GAS LEAK OR TO TEST THE ADEQUACY OF A REPAIR JOB.

 

MATERIALS AND EQUIPMENT QUALIFIED FOR USE IN NATURAL GAS SYSTEMS

The pipeline safety regulations list many different materials that are qualified for gas service. The materials and specifications listed in this manual are those most commonly used in natural gas distribution systems. Not all qualified materials or specifications are included in this section. The operator of a small natural gas system is referred to 49 CFR Part 192 for further information.

It is important for an operator to know the material make-up and operating pressure of an existing gas pipeline system. The operator must develop, or have a consultant develop, a list of qualified materials for construction and repair of the system. Installation procedures must be included for each type of material used in the system. This can be accomplished by including or referencing manufacturers' "gas product installation manuals" in the operations and maintenance plan.

When purchasing material for use in a natural gas pipeline system, it is important to check the marking of the material. The marking on the material will help identify whether the material is qualified for gas service. Of course, a natural gas pipeline system consists of both pipe and fittings. Therefore, an operator must select materials that are compatible with each other. This chapter will cover the most common specifications and standards used by manufacturers for pipes, valves, flanges, regulators, and other equipment commonly used in natural gas distribution systems.

PIPE

Steel and plastic pipe specifications applicable to operators of small natural gas systems are included in this manual. Pipe specifications are listed below. Be sure to check Appendix A of 49 CFR Part 192 for the current specifications and standards.

API 5L - Steel pipe
ASTM A53 - Steel pipe
ASTM D2513 - Thermoplastic pipe and tubing

Operators are cautioned that the actual maximum allowable operating pressure (MAOP) of a new or replacement pipe in a natural gas system is determined by a pressure test performed on the pipeline system by the operator before it is put in service. It is also recommended that threaded pipe not be installed underground.

When purchasing PE plastic pipe, the pipe must be marked ASTM D2513. Plastic pipe with this marking is the only PE pipe suitable for gas service.

Plastic pipe and tubing should be protected at all times from damage by crushing, piercing, or extended exposure to direct sunlight. As a rule of thumb, never store plastic pipe outdoors for more than six months. It should be placed inside or covered to protect it from exposure to direct sunlight. It is a good idea to obtain the manufacturer's recommendation on how long the pipe can be exposed to sunlight before it loses physical strength (see 49 CFR §192.321 for more information).

In recent years, the vast majority of natural gas companies and operators of natural gas system have been installing ASTM D2513, PE pipe. Some of the reasons PE pipe is being installed are flexibility, good joining characteristics, durability, ease of installation, and cost. The PE type designations most often used are PE 2406, and PE 3408 (see FIGURE VI-14).

[View Figure VI-14 on PDF page VI-20]

An anodeless riser is a transition fitting that permits plastic service lines to be brought above ground in compliance with 49 CFR §192.375. The regulations require plastic services to be installed below ground level, except that it may terminate above ground, outside of buildings, if the plastic pipe is protected from deterioration and damage and it is not used to support external loads. Anodeless risers are readily available from various manufacturers and suppliers and are either fully fabricated from the manufacturer, or are field-fabricated by the installer, as is the case with service head adapter risers. Typically, the external protective casing is pre-bent, epoxy coated or galvanized, schedule 40 steel pipe. The plastic gas piping (inside the casing) must extend to an aboveground point for the riser to qualify as anodeless. Otherwise, the riser casing becomes a buried steel pipe gas carrier and is required to comply with Subpart I of 49 CFR Part 192. In most cases there is a grade level or "do not bury" label to indicate the bury depth to the installer. The outlet typically is provided with tapered pipe threads, or in the case of commercial or industrial risers, a bolted flange for attachment to the meter valve. The PE piping inlet, designated as the "pigtail," is provided ready for connection to the service line. This service connection is accomplished either by heat fusion or, if so specified, with a mechanical coupling already attached to the pigtail for additional installation convenience.

[View Figure VI-15 on PDF page VI-21]

Examples of anodeless service risers. There are many different manufacturers of anodeless risers. The primary advantage of an anodeless riser is that it does not have to be cathodically protected because the outside steel casing is not the gas carrier. The plastic inside the steel casing is the gas carrier. When purchasing anodeless risers, make sure that they meet all DOT requirements. When installing steel risers connected to plastic pipe by a transition fitting, make sure that the steel riser is coated and cathodically protected.

Most PE pipe manufacturers subscribe to the "Standard Dimension Ratio" (SDR) method of rating pressure piping. The SDR is the ratio of pipe diameter to wall thickness. An SDR 11 means the outside diameter (O.D.) of the pipe is eleven times the thickness of the wall.

For high SDR ratios the pipe wall is thin in comparison to the pipe O.D. For low SDR ratios the
wall is thick in comparison to the pipe O.D. Given two pipes of the same O.D., the pipe with the
thicker wall will be stronger than the one with the thinner wall. High SDR pipe has a low pressure rating; low SDR pipe has a high-pressure rating. The operator should check the
manufacturer's specific pressure rating for each specific pipe. Do not use pipe with SDR values
greater than 11.

PE pipe must be joined by either the heat fusion method (butt, socket, or electrofusion) or by a mechanical coupling. Each joining procedure and each person making joints must be qualified. For information about local suppliers of plastic gas pipe, contact the local gas utility.

VALVES

A valve may not be used under operating conditions that exceed the applicable pressure-temperature rating. The valve will be stamped with the maximum working pressure rating (psig). Never operate valves at pressures that exceed their rating. The maximum working ratings are applicable at temperatures from -20°F to 100°F. Metal valves will often be stamped with the symbols "WOG." This means that they are suitable for service for water, oil, or gas. Sometimes just the letter "G" (for gas) appears. The valves must be rated for at least 100 psig.

The manufacturer's name or trademark must be included on a valve. Operators must maintain manufacturers' manuals, which include installation, operation, and maintenance procedures, for each type valve in the gas system. These manuals and procedures should be incorporated or referenced in the operations and maintenance plan.

Plastic valves purchased for gas service must comply with the appropriate industry standard. The valves must be compatible with the plastic pipe used in the natural gas system. It is important that operators buy plastic valves only from suppliers who are knowledgeable about gas piping. Supplier information can be obtained from trade journals, local gas associations (state or regional), or local gas utilities (see enclosed handout).

FLANGES AND FLANGE ACCESSORIES

Each flange or flange accessory must meet the minimum requirements found in 49 CFR §192.147. Operators must verify that metal flanges purchased for their system meet these requirements. This can be done by checking the markings on the flange. The markings are similar to those on the valves.

REGULATORS AND OVERPRESSURE PROTECTION EQUIPMENT

There are many different manufacturers and models of gas regulators and overpressure equipment (relief valves) for use in gas pipeline systems.

Regulators and overpressure protection equipment must be sized to ensure that overpressure or low-pressure conditions do not occur in the gas system. Manufacturers of gas regulators and relief valves have manuals that contain formulas and charts for each of their models or types of equipment. These formulas and charts are necessary to properly size regulators and relief valves. A qualified person must install the equipment. Operators who do not have a technical background should rely on a consultant or the equipment manufacturer representative to size the equipment. Check with the state for additional local requirements. See the enclosed handout for further information.

It is important to obtain the manufacturer's operation and maintenance instructions for each type of regulator and relief valve used in the gas pipeline system. The instructions must be incorporated into the operations and maintenance plan. CHAPTER II is a primer on basic concepts on pressure regulation, regulators, and relief devices.

OTHER EQUIPMENT

A natural gas operator may need additional equipment to operate a natural gas system. This
additional equipment may include:

  • pipe-to-soil meters;
  • pipe locators;
  • gas leak detection equipment;
  • industry publications.

An illustration of a pipe-to-soil meter is in CHAPTER III. Additional information on gas leak
detection equipment and pipe locators is found in CHAPTER IV. The local gas utility or gas
association is a good source of assistance.

WELDING REQUIREMENTS

How can an operator determine whether pipeline welding is performed as required?

  1. Welding must be performed in accordance with written welding procedures qualified to
    produce acceptable welds. For typical pipeline welding, standard API 1104 is most often
    relied on. The welding procedures should include:
    1. Records of the complete results of the procedural qualification test
    2. Procedural specification
      1. Identifying the process
      2. Identifying the materials
      3. Identifying the wall thickness groups
      4. Identifying the pipe diameter groups
      5. Showing a joint design sketch
      6. Designating filler metal and number of beads
      7. Designating electrical characteristics
      8. Designating flame characteristics
      9. Designating positions or roll welding
      10. Designating direction of welding
      11. Designating maximum time lapse between passes
      12. Designating type of line-up clamp and removal criteria
      13. Designating type of cleaning tool used
      14. Specifying preheat and post heat practices
      15. Designating composition of gas and range of flow rate
      16. Designating type and size of shielding flux
      17. Designating range of speed of travel for each pass
    3. Essential variables
      Most changes in b. require requalification of the welding procedure. (Refer to API 1104,
      paragraph 2.4.)
    4. Welding and testing of test joint
      1. Preparation of specimen
      2. Destructive tests - butt welds
        1. Tensile strength test
        2. Nick break test
        3. Root and face bend test
        4. Side bend test
      3. Destructive test - fillet welds: Break in weld as specified
  2. Welders who are qualified for the welding procedure to be used must perform welding.
    1. The welder shall be qualified under one of the applicable requirements specified.
      1. Transmission pipelines
        1. API 1104, Section 3; or
        2. ASME Boiler and Pressure Vessel Code, Section IX
      2. Distribution pipeline
        1. API 1104, Section 3;
        2. ASME Boiler and Pressure Vessel Code, Section IX; or
        3. 49 CFR Part 192, Appendix C, Section I (not acceptable for service line to main
          connection welding).
      3. Service line to main connections
        1. API 1104, Section 3;
        2. ASME Boiler and Pressure Vessel Code, Section IX; or
        3. 49 CFR Part 192, Appendix C, Sections I and II.
    2. Welder qualification under API 1104, Section 3.
      1. Perform qualification test as specified in the written welding procedure in the
        presence of the company's representative.
      2. Essential variables (certain changes require re-qualification).
        1. For single qualification refer to API 1104, paragraph 3.11; or
        2. For multiple qualification refer to API 1104, paragraph 3.21.
      3. Welding and testing of test joint
        1. Preparation of specimen(s)
        2. Visual examination
        3. Destructive test - butt welds
          Determine if all or part of these tests is required:
          1. Tensile strength test (optional)
          2. Nick break test
          3. Root and face bend test
          4. Side bend test
        4. Destructive tests - fillet welds: Break in weld as specified.
        5. Visual inspection

          NOTE: Nondestructive radiographic inspection of butt welds only can be done in lieu of (3)(c) above. This is the operator's option. The standards of acceptability for radiographic inspection are specified in API 1104, paragraph 6.0.

      4. Keep the following records:
        1. Detailed test results for each welder
        2. List of qualified welders and the procedures(s) for which they are qualified.
    3. Welder qualification under 49 CFR Part 192, Appendix C, Section I
      1. Perform qualification test on pipe 12 inches or less in diameter
      2. Use position welding
      3. Preparation must conform to written welding procedure
      4. Destructive test. - root bend test
      5. Visually inspect
      6. Keep the following records:
        1. Detailed test results for each welder
        2. List of qualified welders under this procedure
    4. Welder qualification under of 49 CFR Part 192, Appendix C, Sections I and II
      1. Perform c. above
      2. Weld service line connection fitting to a pipe typical of the main using similar position as one would in actual production welding
      3. Destructive test - break, or attempt to break, the fitting off the run pipe
      4. Keep the following records:
        1. Detailed test results for each welder
        2. List of qualified welders under this procedure
    5. Remain qualified under API 1104, Section 3 or ASME Boiler and Pressure Vessel Code,
      Section IX, if:
      1. Within the preceding six months, welder has welded with the particular welding
        process (either test or production welding is acceptable), and welder has made a
        weld and had it tested satisfactorily either destructively or nondestructively. (Refer
        to 2b(3) for required procedure.)
    6. Remain qualified under either 49 CFR Part 192, Appendix C, Section I or II, if:
      1. Within the preceding 7½ months but at least twice each year, welder has had one
        production weld cut out, tested, and found acceptable in accordance with the initial
        qualification test; or,

        NOTE: Welders who work only on service lines 2 inches or smaller in diameter may be tested in each 6-month period under 49 CFR Part 192, Section III, Appendix C in lieu of f(1) above, but at the same intervals.

      2. Within the preceding 15 months, but at least once each year, welder has requalified
        under 49 CFR Part 192 Appendix C
  3. Production welding
    1. Use a welder qualified in a qualified welding procedure.
    2. The following items should be part of the written welding procedure:
      1. Weather protection - 49 CFR §192.231
      2. Preparation - 49 CFR §192.235
      3. Visual Inspection - 49 CFR §192.241
      4. Nondestructive Testing (under specified conditions) - 49 CFR §192.243. Must meet standards of acceptability in API 1104, Section 6.
    3. Miter joint restrictions
      The use of miter joints is restricted as follows:
      1. If MAOP produces a hoop stress of 30 percent or more SMYS, the joint cannot deflect the pipe more than 3 degrees.
      2. If MAOP produces a hoop stress of more than 10 percent SMYS but less than 30 percent, the joint cannot deflect the pipe more than 12.5 degrees and must have at least one pipe diameter separation from another miter joint.
      3. If MAOP produces a hoop stress of 10 percent of SMYS or less, the joint cannot deflect the pipe more than 90 degrees.
    4. Repair or removal of defect requirements is as follows:
      1. Remove or repair all welds that fail to pass the nondestructive test requirements
        (standards of acceptability in API 1104, Section 6).
      2. Remove all welds that contain cracks that are more than 8 percent of the weld
        length.
      3. Repairs must have the defect removed down to clean metal and the segment to be
        repaired must be preheated if conditions exist which would adversely affect the
        quality of the weld repair. Inspect the repaired weld.
      4. Repair of a crack, or any defect in a previously repaired area, must be in accordance
        with written weld repair procedures that have been qualified under this guidance
        manual.

[Web Editor's Note: The following is Addendum 1 approved by NAPSR on June 26, 2003. Page VI-28 has been inserted in the PDF for Section 6]

PLASTIC PIPE INSTALLATION CONCERNS – BRITTLE LIKE FRACTURES

FIGURES VI-16 through VI-19 illustrate plastic service line connections to gas mains. There have been accidents due to the failure of the plastic pipe in certain types of installations. These installations are associated with older polyethylene pipe (1960s through early 1980s), which may be vulnerable to fractures and brittle-like cracking. The key areas of concern are where the pipe may not be properly supported in a transition area, which may cause excessive bending of the pipe.

The transition area is where the plastic pipe is connected to a fitting, valve, or riser. As the earth settles, inadequately supported plastic pipe may be subjected to high bending stresses and possible failure. Figures VI-16 through VI-19 show the use of protective sleeves in the transition areas. Protective sleeves, along with attention to adequate backfill and support, can help to distribute excessive stresses. The design of a protective sleeve is dependent on type of soil, size of pipe, composition of the backfill, and size of the access trench or bell hole. Therefore, it is imperative that pipeline operators review the specific sleeving and support instructions provided by the pipe manufacturer.

Excessive bending of pipe in non-transition areas can also result in excessive stresses that can lead to plastic pipe failure. If the pipe is installed with very tight bends, the pipe wall can be stressed beyond manufacturers recommendations. This can result in brittle-like fracture of the pipe wall. Every manufacturer has a recommended maximum bending radius for each type and size of pipe. The maximum bending radius is reduced for pipe spans that contain a fusion or mechanical joint. Therefore, it is imperative that pipeline operators review the maximum bending limits for each type of pipe.

Backfill material should consist of sand or native soil containing no sharp rocks or other foreign objects. Backfill material containing sharp rocks has caused several accidents. Proper backfill and support are essential to the installation and safe, long-term performance of plastic pipe.

[View Figures VI-16 through VI-19 on PDF pages VI-28 through VI-32.]

COMMON CONSTRUCTION PRACTICES

The following (FIGURES VI-16 AND VI-17) illustrate a steel to plastic pipe connection using a mechanical coupling. There are other sizes of connections. Refer to specific manufacturer's instructions for the proper couplings and coupling procedures.

[View Figures VI-16 and VI-17 on PDF pages VI-28 and VI-29.]

[Figure VI-20 is an example of non-welded 1" service line from a cast iron main (for illustration purposes only) and is viewed on PDF page VI-33].

[Figure VI-21 is an example of a welded 1" steel service line from a cast iron main (for illustration purposes only) and is viewed on PDF page VI-34].

[Figure VI-22 is an example of a welded ¾" service line from a steel main (for illustration purposes
only) and is viewed on PDF page VI-35
.]

The following two pages (FIGURES VI-23A AND 23B) illustrate a steel to plastic connection using a coupling. There are other sizes of connections. Refer to specific manufacture's instructions for the proper couplings and coupling procedures.

[View figures on PDF pages VI-36]

[Web Editor's Note: Figure VI-23B is not included in PDF].

Chapter 7 - Proper Location and Design of Customer Meter and Regulator Sets

Before locating customer meters and regulators, three points must be considered: accessibility, protection of meter sets from damage, and protection of people from release of gas at the meter set.

CUSTOMER METERS AND REGULATORS: LOCATION

Install meters and service regulators in a readily accessible location. Protect the meters and regulators from corrosion and other damage. Whenever a vehicle could damage meter sets, a suitable barricade must be installed. Always ensure that the meter sets are properly supported. Install meters outside wherever possible (see FIGURE VII-1).

[View Figure VII-1 on PDF page VII-1]

Service regulators installed inside a building must be placed as close as practical to the point of service entering the building. The operator must vent the regulator to the outside.

Meters installed inside a building must be located in a ventilated place. A meter must be more than 3 feet from any source of ignition or any source of heat that might damage the meter.

It is best to locate the upstream regulator (in a series) outside the building. However, the operator may locate regulators in a separate metering or regulating building.

CUSTOMER METERS AND REGULATORS: PROTECTION FROM DAMAGE

Protection from vacuum or backpressure. If customer equipment might create either a vacuum or a backpressure, protection devices must be installed on the gas system.

Service regulator vents and relief vents. The outside terminal of each service regulator vent and
relief vent must be:

  • rain, snow, ice and insect resistant;
  • located where gas from the vent can escape freely into the atmosphere (vent it 3 feet or more away from any opening into the building);
  • protected from water damage in areas where flooding may occur (put it where it will not be underwater in a flood).

The meters and regulators must be installed to minimize stresses on connecting piping.

Each pit or vault in a road, driveway, or parking area that houses a customer's meter or regulator must be able to support the vehicle traffic that could use that road, driveway, or parking area.

CUSTOMER METERS INSTALLATIONS: OPERATING PRESSURE

A meter may not be used at a pressure that is more than 67 percent of the manufacturer's shell test pressure (0.67 x shell test pressure).

The operator must ensure that each newly installed meter has been tested to a minimum of 10
psig.

SERVICE LINES: LOCATION OF VALVES
  • Relation to regulator or meter. Each service line valve must be installed upstream of the regulator. If there is no regulator, install the valve upstream of the meter (see FIGURES VII-2 through VII-5).
  • Outside valves. Each service line must have a shut-off valve in a readily accessible location outside of the building (see FIGURE VII-2).
  • Underground valves. Each underground service line valve must be located in a covered, durable curb box or standpipe that allows ready operation of the valve. The box or standpipe must not put stress on the service line (see FIGURES VII-3 and VII-4).

Services should not be installed under buildings or mobile homes. If a service is installed under a building, it must be encased in a gas-tight conduit. This conduit must vent to the outside at a point where gas would not be a hazard and must terminate aboveground in a rain, snow, ice and insect resistant fitting.

[View Figures VII-2 through VII-5 on PDF pages VII-3 through VII-6]

COMMON PROBLEMS AT SERVICE RISER AND HOUSE REGULATORS
  • Regulator vandalism or damage. This can be very hazardous. If the regulator fails to
    function for any reason, high-pressure gas may enter the appliances. Tall flames at the
    burner or escape of gas could cause a fire or explosion.
  • Obstructed vents. The vent on the regulator should be free of any obstructions. A wire
    screen installed at the vent should prevent the accumulation of dirt, the intentional
    insertion of foreign objects by children, or the build up of insect nests (e.g., wasp nests).
    If the screen is removed, a new one must be inserted in its place. A non-functioning vent
    could cause regulator failure and present a serious fire hazard. The vent should be away
    from windows and air intakes and protected from the elements.
  • Tenants move out. The valve on the meter riser should be equipped with a locking
    device to be controlled by authorized personnel only. When tenants move out, the gas
    must be shut off and the valve locked until new tenants move in. The locking device on
    the shutoff valve also allows the repair of appliances without the gas being accidentally
    turned on.
  • Riser misuse. The tenants or customers should not be allowed to use the riser and its
    components for other purposes. Never use the riser as an anchor for laundry lines, plant
    supports, or bicycle racks (see CHAPTER III, FIGURE 17).
  • Corrosion. Check for corrosion on the service riser at ground level (see CHAPTER III,
    FIGURE 24).
  • Flex Lines. Flex Lines should be UL approved and must be installed aboveground.
Chapter 8 - Plans and Reports Required by the Federal Government
PLANS REQUIRED BY THE FEDERAL GOVERNMENT

All operators of natural gas systems are required to maintain plans for operations and maintenance and emergency response activities. Most operators comply with this requirement by developing and maintaining a manual that incorporates both plans. The manual must be prepared before operations of a natural gas system commence and must be reviewed and updated annually. The manual must be kept at locations where operations and maintenance activities are conducted. This manual fulfills the requirements of 49 CFR Part 192.605.

OPERATIONS AND MAINTENANCE PLANS

An operations and maintenance plan is required of all natural gas operators by the pipeline safety regulations. The operations and maintenance plan must be written and followed to help the operator comply with the pipeline safety regulations (see 49 CFR §192.603 for further information).

This chapter outlines the procedures that must be addressed in the operations and maintenance plan. For master meter operators, the first 18 of these procedures (lettered A-R) must usually be addressed in the operations and maintenance plan. Four additional procedures (lettered S-V) may apply to some operators of small natural gas systems, but most likely will apply only to larger or more complex systems such as those operated by a small municipality.

Some items addressed in this chapter may not be relevant to every natural gas system. However, a procedure required by the pipeline safety regulations must be included in the plan. Some of the key items that pipeline safety inspectors will look for during an audit are:

  • completeness of the operations and maintenance procedures;
  • omission or deficiency of an applicable portion of the plan;
  • not having a plan readily available for review;
  • not providing for an annual update and review of the procedures in the plan;
  • not having a plan at all.
OPERATIONS AND MAINTENANCE PLANS MUST CONTAIN THE FOLLOWING COMPONENTS:
  1. Determination of Class Location(s) - The operator must determine the Class location for each part of its system. More stringent safety requirements may apply in some locations (see 49 CFR §192.5 for further information).

  2. Public Education - Procedures for educating customers, the general public, local government officials, and excavators about natural gas safety issues must be included in the plan and the operator must retain records of the education program (see 49 CFR §192.16 and §192.616 for further information).

  3. Investigation of Failures - The operator must have procedures for analyzing accidents and failures to determine the cause(s) of the failure and to minimize the probability of a recurrence (see 49 CFR §192.617 for further information).

  4. Maximum Allowable Operating Pressure (MAOP) - This is the maximum pressure at which each segment of a natural gas system may operate. The operator establishes MAOP. If the pipeline is tested to the 100 psig recommended in this guidance manual, the MAOP of the system will be 60 psig (see 49 CFR §192.619 for further information).

  5. Tapping and/or Purging of Pipelines - If tapping and/or purging are performed on the pipeline system, any procedure that is utilized must be in the operations and maintenance plan. Necessary information includes type of equipment, qualified personnel, technique, and the applicable procedures for performing the operation (see 49 CFR §192.627 and §192.629 for further information).

  6. Odorization - (Master Meter Operators).
    The plan must contain a provision for the measurement of the odor of natural gas. A quarterly "sniff test" is sufficient if the natural gas company that supplies the gas provides proof of odorization. The operator should ask tenants, especially heavy smokers and the elderly, to smell the gas at an open valve or gas oven burner at various locations in the system. If they cannot detect an odor, the gas supplier should be notified. Make sure to keep records of these tests, including dates, names, and locations. Sample forms are in Appendix B (Form 11) (see 49 CFR §192.625 for further information).

    Odorization - (Other than Master Meter Operators).
    Operators who must odorize their own gas must ensure that there is enough odorant in the gas to provide a distinct odor when natural gas is present in air at a concentration of one-fifth of the lower explosive limit. The lower explosive limit for natural gas occurs at approximately 4 percent natural gas in air by volume; therefore, odorant must be detectable at approximately 0.8 percent gas in air by volume.

    The odorant and its products of combustion must not be toxic to humans or harmful to components of the natural gas system. The odorant must not be soluble in water more than 2.5 to 100 parts by weight.

    All operators must follow these basic rules:
    • Ensure that all natural gas in distribution mains and service lines is odorized.
    • Specify or determine the type of odorant used in the system.
    • Specify in the operations and maintenance plan the manufacturer's recommended amount of odorant per million cubic feet (mmcf) of gas.
    • Include any maintenance procedures recommended by the manufacturer of the odorization equipment. Odorization equipment must introduce the odorant without wide variation in the amount of odorant per mmcf of natural gas.
    • A periodic sampling procedure must be part of the written operations and maintenance plan. This must include periodic testing of the odorant injection rate and testing at various locations, including the outer extremities of the pipeline system, to verify that the odor is distinctive at all locations in all seasons.
    • Maintain records of odorant injection rate and odorant sampling. For sample record, see Appendix B, Form 10.

      See 49 CFR §192.625 for further information.

  7. Patrolling - Operators must include in the plan provisions for patrolling mains located in places or on structures where anticipated physical movement or external loading (e.g., weight and traffic) could cause failure or leakage. These places include bridges, waterways, landslide areas, areas susceptible to earth subsidence (cave ins), or areas of construction activity.

    Patrolling of these mains must be conducted at least four times each year in business districts and twice a year outside business districts (Appendix B, Form 4). Patrolling can be done by walking along the pipeline and observing factors affecting safe operation (see 49 CFR §192.705 for further information).

    [View Figure VIII-1 on PDF page VIII-4]

  8. Leak Surveys - A survey of a natural gas distribution system with leak detector equipment (FI or CGI) must be made as frequently as necessary, but at least annually.

    Most master meter operators use contractors to leak survey their systems. It is the responsibility of the operator to ensure that the survey is conducted in accordance with the pipeline safety regulations. The operator must retain a report describing the results of each survey.

    Leak surveys are the most important way in which a gas system operator protects the safety
    of the community; therefore, these directions need to be carefully followed:

    1. A leak survey must be conducted over an entire residential pipeline system at intervals not exceeding five years. Operators should increase the frequency of surveys based on factors such as:
      1. Material makeup of system. Certain materials, not all of which are approved for use with natural gas, may develop a higher than average leakage rate (e.g., unprotected bare steel, PVC plastic pipe, extruded tubing, cast iron with lead joints, and coated steel pipe not cathodically protected).
      2. Age of pipe (over 20 years) and corrosive soil environment.
      3. Operating pressures.
      4. Pipe having a previous history of excessive leakage for which the cause has not been determined or eliminated.
      5. Pipelines in or near buildings, especially schools, churches, hospitals, or other buildings with high occupancy (see APPENDIX B, FORM 3).
      6. Pipelines located in areas of construction, blasting, or heavy traffic.
      7. Pipe located in crawl spaces under apartment buildings or mobile homes.
      8. Service lines and meters inside buildings.

        Operators should designate areas that require more frequent surveys.

        Available openings should be used to find gas leaks. These include water, sewer, electric, and telephone systems, manholes, cracks in the pavement, and hollow walls (cinder block construction) in areas near natural gas piping. When conducting leak surveys, it is a good policy to check for leaks near the gas pipe entrance, both inside and outside the building. See CHAPTER 4 for details about gas indicator equipment and types of leak surveys.

    2. Heavily populated areas require more frequent leak surveys. If the natural gas system is in a business district, a leak survey (utilizing FI or CGI equipment) must be conducted at least once every year (see FIGURE VIII-3). All leaks must be recorded no matter how minor. Sample forms are in Appendix B (Forms 2 and 3).

    3. ALL leaks found must be classified as soon as located. All leaks must be investigated to determine if a hazard exists. If a hazardous condition is found, immediate action must be taken. The operator must take action to protect life and property until the hazardous condition is eliminated. Operators may want to include the Gas Piping Technology Committee's (GPTC) "Leak Classification Guide and Action Criteria" in their operations and maintenance plan. See Chapter IV for further information.

    4. Although vegetation surveys do not fulfill the requirements of the pipeline safety regulations, they may be used as a supplementary leak detection measure. CHAPTER 4 contains some details about what to look for in vegetation surveys. All leaks must be recorded. Sample forms are in APPENDIX B (FORMS 2 and 3).

    5. A map of the distribution system must be marked annually to show leak surveys conducted and the areas tested. Indicate the approximate location of each leak found. Annotations may be made in accordance with FIGURE VIII-2.

      [View Figure VIII-2 on PDF page VIII-6]

  9. Line Markers - The operations and maintenance plan must specify locations for pipeline markers. The following are the federal requirements:

    Buried distribution pipelines. A line marker must be placed and maintained as close as possible over each buried distribution main at each crossing of a highway, street, or railroad. A line marker must also be placed wherever necessary to identify the location of the main to reduce the possibility of damage or interference. Line markers are not required for buried mains in Class 3 or 4 locations where it can be shown to be impractical, or where the pipeline system operator participates in a damage prevention program (such as "one-call" or "call before you dig" system).

    Distribution pipelines above ground. Line markers must be placed and maintained along each section of a main that is located above ground in an area accessible to the public. A typical example is an unsecured pressure regulating station.

    Markers. The following must be written legibly on a background of sharply contrasting color on each line marker:

    1. The word "Warning," "Caution," or "Danger" followed by the words "Gas (or name of gas transported) Pipeline." Letters must be at least one inch high with an approximate stroke of one-quarter inch.

    2. The name of the operator and the telephone number (including area code) where the operator can be reached at all times (see FIGURE VIII-3).

      [View Figure VIII-3 on PDF page VIII-7]

  10. Testing for Reinstating a Service Line - The plan must contain a provision for testing each disconnected service line from a main before placing it back into service. For small distribution and master meter operators testing at 100 psig is suggested. See 49 CFR §192.511 for further information.

  11. Abandonment of Facilities - The plan must include provisions for shutdown, abandonment, or inactivation of facilities. When a gas main or service line is abandoned, it must be physically disconnected at both ends and the open ends must be sealed. In addition, the operator must determine if it is necessary to purge the line. This determination should take into consideration the location and size of the main or service. Pipe four inches and larger should always be purged. However, the pipeline need not be purged when the volume of gas is so small that there is no potential hazard (see 49 CFR §192.727 for further information).

    Records must be kept on all abandoned facilities. This includes location, date, and method of discontinuing service.

    When service to a customer is discontinued, one of the following must be done:

    1. The valve must be closed to prevent the flow of natural gas to the customer. This valve must be secured with a lock or some other device to prevent opening of the valve by unauthorized persons. There are numerous locking devices designed for this purpose (see FIGURES VIII-4 and VIII-5).
    2. A mechanical device or fitting that will prevent the flow of gas must be installed in the service line or in the meter assembly.
    3. The customer's piping must be physically disconnected from the gas supply and sealed at both ends (see FIGURE VIII-6).

      [View Figures VIII-4 through VIII-6 on PDF pages VIII-9 through VIII-11]

  12. Key Valve Maintenance - Key valves, or critical valves, are the valves needed to shut down the system, or part of the system, in case of an emergency. For most master meter systems, this may involve only one or two valves. Key valves must be checked at least once every year to ensure that they are operable. Procedures for key valve inspections and maintenance of records must be included in the plan. Sample forms are in APPENDIX B (FORMS 8 and 9). See 49 CFR §192.747 for further information.

  13. Accidental Ignition of Gas - The plan must include provisions to prevent the accidental ignition of gas. Gas alone is not explosive, but when mixed with air in a 4 to 15 percent concentration it can ignite or explode. Every precaution should be taken to prevent unintentional ignition of natural gas. When venting a hazardous amount of natural gas, a fire extinguisher must be available and ready for immediate use. See 49 CFR §192.751 for further information.

  14. Corrosion Protection - Provisions should be made in the operations and maintenance plan for corrosion protection if the system contains metal pipe. The plan should include procedures for the following:
    • Implementing a corrosion control program. This must be under the direction of a person qualified by experience and training in pipeline corrosion control methods.
    • Ensuring coating and cathodic protection of new steel pipe (APPENDIX B, FORM 14).
    • Ensuring cathodic protection of existing pipe (APPENDIX B, FORM 14).
    • Examining pipe when exposed (APPENDIX B, FORM 1).
    • Testing the effectiveness of cathodic protection every year (APPENDIX B, FORM 14).
    • Inspecting rectifiers, if used in an impressed current cathodic protection system, at least 6 times a year. (APPENDIX B, FORM 15).
    • Checking for atmospheric corrosion (APPENDIX B, FORM 13).
    • Maintaining records of all tests, surveys, and inspections.

      These requirements are discussed in more detail in CHAPTER III. Corrosion theory, practical concepts, and illustrations are contained in CHAPTER III. See 49 CFR §§192.451-192.491 for further information.

  15. Construction and Leak Repair - The operations and maintenance plan should contain procedures for construction and leak repair. CHAPTER VI of this manual gives some basic procedures and concepts.

  16. Construction Records, Maps and Operating History - The operator must have and follow procedures in the plan to make construction records, maps and operating history of the natural gas system readily available to operating personnel.

  17. Gathering of Data Needed for Reporting Incidents - The plan must include procedures to compile information on pipeline incidents and safety-related conditions. These procedures need to ensure accurate and timely reporting. This information must be readily available. See 49 CFR Part 191 for further information.

  18. Starting Up and Shutting Down any Part of the Pipeline - The plan must include step-by-step actions for start-up and shut-down of the pipeline system. This will ensure that the MAOP is not exceeded on any portion of the pipeline system. See 49 CFR §192.605 for further information.

NOTE: THE FOLLOWING SECTIONS WILL NOT USUALLY APPLY TO MASTER METER OPERATORS.

  1. Uprating - The operations and maintenance plan must contain uprating procedures only if uprating is contemplated. If a system requires uprating, contact the state regulatory agency or the OPS regional office for detailed instructions. See 49 CFR §§192.551-192.557 for further information.

  2. Inspection of Regulating Stations - If regulating stations are a part of the system, the plan must include provisions for their inspection and testing. Many master meter systems will not have a regulating station. This section does not apply if an operator does not lower the gas pressure from the local gas utility delivery pressure except at a customer service regulator.

    For operators with regulating stations, provisions must be made in the operations and maintenance plan to inspect and test both regulators and relief devices. These must be inspected every year to determine that they are:

    • in good mechanical condition;
    • adequate in capacity and reliability of operation;
    • set to function at the correct pressure;
    • properly installed and protected from vehicular traffic, dirt, liquids, icing, and other conditions that might prevent proper operation.

      A record of this annual inspection must be kept. Sample forms are in APPENDIX B (FORM 6). The operator must inspect visually, perform an operation check (stroke and lock up), and check the set pressure of the relief device and regulator. Problems may include:

    • low distribution system pressure;
    • unsatisfactory operating and maintenance history;
    • dirty or wet gas supply;
    • inoperative safety devices.

      The operator may need technical help to solve these problems, especially if regulator disassembly or station redesign is necessary. THE OPERATOR IS CAUTIONED NOT TO DISASSEMBLE REGULATORS WITHOUT THOROUGH TRAINING BY THE REGULATOR MANUFACTURER OR AN INDEPENDENT CONSULTANT.

      The operator should always keep and use the manufacturers' manuals, diagrams, and maintenance procedures for each type of regulator used in the system.

      CHAPTER II contains some basic concepts about pressure regulation and relief devices. See 49 CFR §192.739 and §192.743 for further information.

  3. Testing of Relief Devices at Regulating Stations - At a minimum, the operations and maintenance must include procedures for the inspection of relief devices. Relief devices should be inspected as follows:

    • Existing pressure limiting and regulating stations must be inspected and tested for operating condition at least once a year.
    • If the relief device has insufficient capacity, the operator must replace it.
    • The stations must be protected from damage from outside forces (cars, trucks, falling objects, etc.).

      Usually, the gas pipeline company or the local distribution company owns and maintains the relief devices at regulation stations. However, if an operator owns relief devices at regulation stations, provisions must be made in the plan for capacity testing. If not feasible, the calculations of capacity must be reviewed each year. The operator must maintain a copy of this calculation. The test must show that the relief valve capacity is adequate for the system's MAOP.

      The regulations recognize two types of distribution systems: low pressure and other-than-low pressure. The relief capacity for low pressure must protect the customer's gas utilization equipment from overpressure. The gas pressure in the main is approximately the same as the pressure provided the customer - usually 4 to 8 inches water column for natural gas.

      In an other than low pressure distribution system, the relief device must be set to operate such that if the MAOP is 60 psig or more, the pressure during an emergency may not exceed the MAOP plus 10 percent. If testing reveals that the relief devices do not have adequate capacity, then new or additional devices must be installed.

      Capacity must be checked for each separately controlled section of the natural gas system.
      The operator must ensure that the MAOP will not be exceeded at any point downstream of
      the regulator station if the worst condition occurred - that is, if the regulator fails when fully
      opened. Most small systems have only one MAOP for all piping in the distribution system.

      In summary, the combination of minimum customer usage and relief capacity must ensure
      the MAOP will not be exceeded (except to the extent described above).

      To comply with this requirement, many operators of small systems have a consultant
      analyze their gas system and make the required relief valve capacity calculations. If the analysis proves that the relief valve has adequate capacity, the operator must keep a copy of
      this calculation on file. If there have been no changes to upstream regulators, such as
      different pressure, orifice, or type of regulator, the calculation of capacity need only be
      reviewed (and initialed) on an annual basis. If a change is made, the new relief valve
      capacity calculations must be made and kept on file. It is a good idea to keep this capacity
      calculation with the annual inspection record. Sample forms are in APPENDIX B (FORM 7). For other considerations for relief and regulating stations (see CHAPTER II).

  4. Cast Iron Pipe - Operations and maintenance plans must address the unique safety issues of cast iron pipe. Each cast iron caulked bell-and-spigot joint that is subject to pressures of 25 psig or more must be sealed with either a mechanical leak clamp or device which:

    • Does not reduce flexibility of the joint;
    • Permanently bonds (either chemically, mechanically, or both) with the bell and spigot, metal surfaces, or adjacent pipe metal surfaces;
    • Seals and bonds in a manner that meets the strength, environmental, and chemical compatibility requirements of 49 CFR §192.53(a)(b) and §192.143.

      Each cast iron caulked bell or spigot joint that is subject to a pressure of less than 25 psig,
      must be sealed by a means other than caulking if it is exposed for any reason.

      If an operator has knowledge that the support for a segment of a buried cast iron pipeline has been disturbed, that segment of the pipeline must be protected as necessary. Examples of disturbances are:

    • Vibrations from heavy construction equipment, trains, trucks, buses, or blasting;
    • Impact forces by vehicles;
    • Earth movement;
    • Excavations near the pipeline;
    • Other known or foreseeable outside forces that may have or could subject that segment of
      the pipeline to bending stresses.

      Operators of cast iron pipe located in earthquake-prone areas should consider replacing the
      pipe as soon as practical. Experience has shown that cast iron is prone to failure from
      severe earth movement. See 49 CFR §192.753 and §192.755 for further information.
EMERGENCY PLANS

General information on developing an emergency plan. See 49 CFR §192.615 for further information.

Each operator is required to keep a written plan of procedures to cope with gas emergencies. The emergency plan should contain the following information:

    1. Emergency notification list.
    2. Map of key valve locations.
    3. Description and location of emergency equipment.
    4. How to respond to gas leak reports and interruptions of gas service.
    5. Check list for use in emergency situations.
    6. Reporting requirements (Telephone Reports).
    7. How to restore gas service after an outage.
    8. Accident investigation procedures.
    9. Education and training plan.

 

  1. Emergency Notification List - The telephone numbers of the operator, fire department, gas company and any other entity whose service may be necessary in an emergency must be readily accessible. For master meter operators, a copy of this list should be posted in a public area. It is recommended that the direct lines to emergency services such as the fire department are included in addition to the general emergency number (i.e., 911). These numbers must be kept up-to-date.

  2. Map of Key Valve Locations - A map of the gas pipeline showing the location of master meters and key valves must be included in the emergency plan.

  3. Description and Location of Emergency Equipment - Emergency equipment must be available. A description of this equipment and its location must be specified in the plan.

  4. Responding to Gas Leak Reports and Interruption of Gas Service - The operator must have written procedures to be followed in response to gas leaks reported by customers. It is the responsibility of the operator of the natural gas distribution system to ensure that all employees are familiar with procedures for responding to gas leak calls and reports.

    1. The employee receiving a report of a gas leak must get as much of the information as
      possible to fill out the leak report (APPENDIX B, FORM 2). Use common sense: saving
      human life is the first priority, then property.

    2. All reports of leaks on customer premises get priority. LEAKS INSIDE A BUILDING
      GET TOP PRIORITY.

    3. After determining that a hazardous leak exists inside a building, remind the customer of
      the following:

      • Do not turn on or off any electrical switches.
      • Do not ring door bells or use telephones.
      • Do not light matches, cigarettes, etc.
      • Do not start automobiles or other engines.
      • Do extinguish all open flames.
      • Do evacuate building to a safe distance (about a block).
      • Do turn off gas supply, if feasible.

    4. Dispatch necessary personnel to the location of the reported leak, including local emergency responders, such as the fire department and police.

    5. Duties of First Company Employee on the Scene:

      TAKE EVERY CORRECTIVE ACTION NECESSARY TO PROTECT LIFE AND
      PROPERTY FROM DANGER (IN THAT ORDER.) IT IS THE RESPONSIBILITY OF
      THE PERSON IN CHARGE TO:

      • Set up communications.
      • Coordinate the on-scene emergency response operation.
      • Make decisions concerning emergency valves, isolating areas, and use of emergency equipment.
      • Implement the checklist for emergency situations.

    6. Minimum Operator Response Actions for Leaks Near Buildings:
      • Assess danger to building occupants, to the public and to property.
      • Extinguish all open flames.
      • If necessary, notify fire, police, and gas company.
      • Block street and stop traffic.
      • Notify supervisor or other responsible persons.
      • Leak survey next to foundation of building including the use bar holes.
      • Check neighboring buildings for gas.
      • Implement checklist for emergency situations.
      • Repair leak.
      • Return occupants to buildings only when positively sure it is safe.

    7. Minimum Operator Response Actions for Leaks Inside a Building:
      • Evaluate immediately to determine concentration of gas and source of leak.
      • Evacuate if necessary.
      • Do not operate electrical switches.
      • Do not use telephone.
      • Shut off gas meter valve.
      • Perform a bar hole leak test of the area especially around foundation. Check water
        meter and other openings.
      • If ground and house are gas free, turn on meter valve. Check all gas piping and
        appliances for leaks. (Is meter hand turning normally or spinning?)
      • Conduct soap bubble test.
      • Implement checklist for emergency situations.
      • Repair leak.
      • If leak cannot be repaired, notify customer. Turn off meter, lock it and tag it.

    8. Gas Burning Inside a Building:
      • Call fire department.
      • Master meter operators should also call local natural gas utility.
      • If fire is at an appliance, shut gas off at appliance valve.
      • If not possible to shut gas off at appliance valve, shut gas off at meter or stop valve.
      • Implement checklist for emergency situations.

  5. Checklist for a Major Emergency

    _____ 1. Has fire department been called?
    _____ 2. Have persons been evacuated and area blockaded?
    _____ 3. Has police department been notified?
    _____ 4. Has repair crew been notified?
    _____ 5. Has company call list been executed?
    _____ 6. Has communication been established?
    _____ 7. Has outside help been requested?
    _____ 8. Have ambulances been called?
    _____ 9. Has leak been shut off or brought under control?
    _____ 10. Has civil defense been notified?
    _____ 11. Have emergency valves or proper valves to shut down or reroute gas been identified and located?
    _____ 12. If an area has been cut off from a supply of gas, has the individual service of each customer been cut off?
    _____ 13. Is the situation under control and has the possibility of recurrence been eliminated?
    _____ 14. Has surrounding area, including buildings adjacent to and across streets, been probed for the possibility of further leakage?
    _____ 15. Has proper tag been put on meter?
    _____ 16. Has telephonic report to the state been made?
    _____ 17. Has telephone report to OPS been made?
    _____ 18. Has radio station been given instructions (if necessary)?

    Date: ___________________________

  6. Reporting Requirements (Telephonic Report) - In case of an incident, a telephone report must be made immediately to the National Response Center (1-800-424-8802) or in Washington, D.C. (267-2675). An incident is an event involving release of gas from a pipeline and:

    1. Death or injury requiring in-patient hospitalization; or
    2. Estimated property damage of $50,000 or more.

  7. Restoration of Gas Service After an Outage - Qualified persons must follow proper procedures to safely restore gas service after an outage. These procedures must include details of appliance relighting procedures.

    Gas service must be restored on a building-to-building basis throughout the affected area. First, service to each customer must be turned off, either at the meter or at street service valves. If street service valves cannot be located, the gas flow can be shut off by squeeze-off, stoppering, etc.

    In restoring service to an affected area all gas piping and meters must be purged and appliances relighted. Never turn on gas at the meter unless access is available to ALL appliances on the customer piping. In the event that a customer is not present, notification must be left in a noticeable location requesting the customer to call the natural gas company to arrange for restoration of service. (See Figure VIII-7 for an example of cards.)

    The person in charge is to coordinate this operation and be responsible for it. A complete record of the incident, with drawings, etc., must be kept on file.

    [View Figure VIII-7 on PDF page VIII-20]

  8. Investigation Procedures
    Each operator must establish procedures for investigating incidents and failures including:

    • Evaluating the situation.
    • Protecting life and property.
    • Securing the area.
    • Conducting a leak survey.
    • Conducting pressure tests of piping.
    • Conducting meter and regulator checks.
    • Questioning persons on the scene.
    • Examining burn and debris patterns.
    • Testing odorization level.
    • Recording meter reading.
    • Recording weather conditions.
    • Selecting samples of the failed facility or equipment for laboratory examination for the
      purpose of determining the causes of the failure and minimizing the possibility of
      recurrence.

  9. Education and Training - Operating personnel must be qualified to ensure understanding of and competency in emergency procedures.

    Employee Training
    Employees must be qualified in emergency procedures, including:
    1. Updates of Emergency Plan.
    2. Review of responsibilities in an emergency.
    3. Review of locations and use of emergency equipment.
    4. Properties of natural gas.
    5. Review the locations and use of:
      • System maps.
      • Main records.
      • Service records.
      • Valve records.
      • Regulator station schematics.
    6. Review of hypothetical emergency situations to reinforce the step-by-step actions to be taken in emergency situations, including how to contact public officials, firefighters, police, gas company, etc.
    7. Recordkeeping requirements.
    8. Telephone reports (OPS, state agency, etc.)

Public Education
Each operator must have a continuing education program that enables customers, the public,
emergency response groups, and persons engaged in excavation activities, to recognize and
respond to an emergency situation.

Program material should include:

    • Information about gas properties.
    • Recognition of gas odors.
    • Actions to take when a strong gas odor is present.
    • Notification of the gas company prior to excavation.
    • Telephone numbers for customers to report gas leaks during both business and nonbusiness
      hours.

There are many excellent pamphlets published by state and regional gas associations and by the American Gas Association and the American Public Gas Association on the properties of gas and emergency information. This information can be obtained from these organizations at no cost or for a small nominal charge. See the enclosed handout for addresses and telephone numbers of these organizations.

This information may be conveyed to the public by a number of means:

    • Radio and television.
    • Newspapers.
    • Newsletters.
    • Meetings.
    • Bill stuffers.
    • Mailings.
    • Hand outs.
    • Bulletin board.

If residents do not speak English, the operator must pass the same information in a language they can understand. For examples of information that can be sent to the public, see FIGURES VIII-8, VIII-9, and VIII-10.

The operator must maintain a record of the public education program. See 49 CFR §192.615 for further information.

[View Figures VIII-8 through VIII-10 on PDF pages VIII-23 through VIII-25]

REPORTS REQUIRED BY THE FEDERAL GOVERNMENT

The federal government requires every gas operator to telephone a report of any "incident," and except, for master-meter operators, report by fax or mail of a "safety-related condition" and to file an annual report. This chapter briefly describes each of these reports. REMEMBER to check with your state agency for any additional state reporting requirements.

INCIDENT REPORT

It is required to telephone an incident report at the earliest possible moment, but in any case, within two hours of a release of natural gas from a pipeline which results in:

  • a death or personal injury requiring hospitalization or estimated property damage, including the cost of gas lost, of $50,000 or more;
  • an event that is significant in the judgment of the operator, even though it was not described above.

This telephone report of a serious incident should include:

  • identity of reporting operator;
  • name and phone number of individual reporting the incident
  • location of the incident (city, county, state, and street address);
  • time of the incident (date and hour);
  • number of fatalities and personal injuries, if any;
  • type and extent of property damage;
  • description of the incident.

The telephone incident report can be made at anytime to the National Response Center at:

TOLL FREE (800) 424-8802
IN WASHINGTON, D.C. (202) 267-2675

REMEMBER, WHEN IN DOUBT, MAKE THE CALL!
See 49 CFR §191.5 for further information.

An incident requiring a telephone report must be followed by a written report unless a master meter system operator makes the report.

[Web Editor's Note: ALL address information below has been updated since publication of this document.  Please click "Contact Us" from the top of any PHMSA web page for more information.]

Address for Incident Reports
All required reports must be submitted to:

Information Resources Manager
Office of Pipeline Safety
Research and Special Programs Administration
Nassif Building, Room 2335
400 Seventh Street, SW
Washington, DC 20590
See 49 CFR §191.9 for further information.

SAFETY-RELATED AND CONDITION REPORTS

NOTE: This rule does not apply to master meter operators.

OPS requires operators of natural gas pipelines to report certain safety-related conditions.

A written report must be filed within 5 working days after the operator first determines that a "safety-related condition" exists, but not later than 10 working days after the day the operator discovers the condition.

Each operator is also required to update its operations and maintenance plan to enable personnel who perform operation and maintenance activities to recognize conditions that may be safetyrelated conditions.

Typical conditions that need to be reported by operators of small natural gas systems include:

  • unintended movement or abnormal loading of pipeline facilities by environmental causes such as earthquakes, landslides, or floods, that impairs the serviceability of a pipeline;
  • any malfunction or operating error that causes the pressure of a pipeline to rise above its maximum allowable operating pressure plus the pressure build-up allowed for operation of pressure limiting or control devices;
  • a leak that constitutes an emergency and is not repaired within 5 days of determination;
  • a safety-related condition that could lead to imminent hazards and cause the operator to make a 20 percent or more reduction in operating pressure.

The above is only a summary. Refer to 49 CFR §191.23(a) for a complete listing of all safety-related conditions that must be reported.

Safety-related conditions that do not require a report include:

  • condition on a customer-owned service line;
  • a condition resulting in an incident, as defined in 49 CFR §191.3;
  • a condition on a pipeline more than 220 yards from any building or outdoor place of assembly, unless it is within the right-of-way of an active railroad, paved road, or highway;
  • a condition that is corrected before the report filing deadline, except for certain corrosion related conditions.

See 49 CFR §191.23(b) for further information.

Address for Safety-Related Condition Reports
All required written reports must be submitted to:

Information Resources Manager
Office of Pipeline Safety
Research and Special Programs Administration
Nassif Building, Room 2335
400 Seventh Street, SW
Washington, DC 20590
Fax: (202) 366-4566

In addition, an intrastate operator may be required to file a report with the state agency participating in the pipeline safety program. For further details on the filing requirements, refer to 49 CFR §191.7.

ANNUAL REPORTS

With the exception of master meter operators, each operator of a distribution pipeline system must submit an annual report for that system. This report must be submitted on DOT Form RSPA F7100.1-1. This report must be submitted each year, not later than March 15, for the preceding calendar year.

Address for Annual Reports
All required reports must be submitted to:

Information Resources Manager
Office of Pipeline Safety
Research and Special Programs Administration
Nassif Building, Room 2335
400 Seventh Street, SW
Washington, DC 20590

See 49 CFR §191.11 for further information.

Appendix A - Glossary
GLOSSARY

To understand this manual, operators of small natural gas systems need to know the meaning of some commonly used terms. The terms are defined below for the purpose of this guidance manual. The reader is referred to 49 CFR Parts 191 and 192 for additional definitions.

ANNUALLY – means at intervals not exceeding 15 months, but at least once each calendar year.

CATHODIC (CORROSION) PROTECTION – a procedure by which underground metallic pipe is protected against deterioration (rusting and pitting). Basic theory, concepts, and practical considerations for cathodic protection are contained in Chapter III.

CUSTOMER METER – a device that measures the volume of gas transferred from an operator to the consumer.

DOWNSTREAM – any point in the direction of flow of a gas from the reference point.

EMERGENCY PLAN – written procedures for responding to emergencies on the pipeline system.

GAS OPERATOR – a gas operator may be a gas utility company, a municipality, or an individual operating a housing project, apartment complex, condominium, or a mobile home park served by a master meter. The operator is ultimately responsible for complying with the pipeline safety regulations.

HIGH-PRESSURE DISTRIBUTION SYSTEM – a distribution system in which the gas pressure in the main is higher than the pressure provided to the customer; therefore, a pressure regulator is required on each service to control pressure to the customer.

INCIDENT – an event that involves a release of natural gas from a pipeline facility that results in: (1) a death or personal injury necessitating in-patient hospitalization; (2) estimated property damage of $50,000 or more; or (3) an event that the operator deems significant (check with your local state authorities for additional requirements, APPENDIX C).

LOW-PRESSURE DISTRIBUTION SYSTEM – a distribution system in which the gas pressure in the main is substantially the same as the pressure provided to the customer; normally a pressure regulator is not required on individual service lines.

MAIN – a natural gas distribution pipeline that serves as a common source of supply for more than one service line.

MASTER METER SYSTEM – a natural gas pipeline system for distributing natural gas for resale within, but not limited to, a distinct area, such as a mobile home park, housing project, or apartment complex, where the operator purchases metered gas from an outside source. The natural gas distribution pipeline system supplies the ultimate consumer who either purchases the gas directly through a meter or by other means such as by rent.

MAXIMUM ALLOWABLE OPERATING PRESSURE (MAOP) – the maximum pressure at which a pipeline may be operated in compliance with the gas pipeline safety regulations. It is established by design, past operating history, pressure testing, and pressure ratings of components.

MUNICIPALITY – a city, county, or any other political subdivision of a state.

NATURAL GAS – a non-toxic, colorless fuel, about one-third lighter than air. Natural gas burns only when mixed with air in certain proportions and ignited by a source of ignition (spark or flame) (Figure IV-4). Natural gas in its natural state may not have an odor.

OPERATING AND MAINTENANCE PLAN – written procedures for operations and maintenance on natural gas pipeline systems.

OVERPRESSURE PROTECTION EQUIPMENT – equipment installed to protect and prevent pressure in a system from exceeding the maximum allowable operating pressure (MAOP).

PIPELINE – all facilities through which gas moves in transportation. This includes pipes, valves, and other items attached to the pipe, meter stations, regulator stations, delivery stations, holders, and fabricated assemblies.

PRESSURE REGULATING/RELIEF STATION – a device to automatically reduce and control the gas pressure in a pipeline downstream from a higher pressure source of natural gas. It includes any enclosures, relief devices, ventilating equipment, and any piping and auxiliary equipment, such as valves, regulators, control instruments, or control lines.

PRETESTED PIPE – pipe that has been tested by the operator to 100 psig for at least one hour.

SERVICE LINE – a natural gas distribution line that transports gas from a common source of supply to a customer's meter, or to the connection to a customer's piping if the piping is farther downstream or if there is no meter.

SERVICE REGULATOR – a device designed to reduce and limit the gas pressure provided to a customer.

SERVICE RISER – the section of a service line which extends out of the ground and is often near the wall of a building. This usually includes a shut-off valve and a service regulator.

SHUT-OFF VALVE – a valve used to stop the flow of gas. The valve may be located upstream of the service regulator or below ground at the property line or where the service line connects to the main.

UPSTREAM – from a reference point, any point located nearest the origin of flow, that is, before the reference point is reached.

49 CFR – Title 49 of the Code of Federal Regulations (CFR). This document contains the actual safety regulations that must be complied with by the natural gas operator. Parts 190, 191, 192, and 199 of 49 CFR contain the federal pipeline safety regulations relevant to operators of natural gas pipeline systems.

COMMONLY ABBREVIATED ORGANIZATION/ACRONYMS

AGA – American Gas Association.

ANSI – American National Standards Institute, formerly the United States of America Standards Institute (USASI). All current standards issued by USASI and American Standard Association (ASA) have been redesignated as American National Standards Institute and continue in effect.

APGA – American Public Gas Association.

API – American Petroleum Institute.

ASME – American Society of Mechanical Engineers.

ASTM – American Society for Testing and Materials.

DOT – U.S. Department of Transportation.

GPTC – Gas Piping Technology Committee.

INGAA – Interstate Natural Gas Association of America.

MEA – Midwest Energy Association.

MSS – Manufacturers Standardization Society of the Valve and Fittings Industry.

NACE – National Association of Corrosion Engineers. (NACE International)

NFPA – National Fire Protection Association.

OPS – Office of Pipeline Safety. The pipeline safety division of the DOT’s Research and Special Programs Administration. For addresses of OPS regional offices, see the attached list of agencies and organizations.

RSPA – Research and Special Programs Administration. A major subdivision of the DOT, it includes the Office of Pipeline Safety. For addresses of regional offices, see the enclosed handout.

SGA – Southern Gas Association.

Appendix B - Sample Forms

[Web Editor's Note: Due to the graphical nature of the sample forms 1 through 16, please contact the Office of Training and Qualifications at 405-954-7219 or phmsa.pipeline-training@dot.gov if you have difficulties with the attached PDF documents.]

GENERAL MAINTENANCE SCHEDULE (#1)
  1. Patrol Pipeline Systems - 192.705, 192.721 - Use Form 4
  2. Patrol River Crossings, Railroad and Highway Crossings - 192.705, 192.721 - Use Form 4
  3. Gas Leak Detection Surveys - 192.723 - Use Form 3
    Downtown and Other Business Areas -192.723 - Use Form 3
    Distribution of Mains and Services - 192.723 - Use Forms 3 and 4
  4. Pressure Regulating Stations - 192.739 - Use Form 6
  5. Regulator Stations and Recording of Pressures - 192.741 - Maintain and Save all Recording Charts (Date
    Charts and File by Date)
  6. Pressure Relief Valves - 192.743 - Use Form 7
  7. Valve Maintenance on Distribution Lines - 192.747 - Use Forms 8 and 9
  8. Odorization of Gas - 192.625 - Use Forms 10 and 11
  9. Corrosion Control – External - 192.465 - Use Form 14
  10. Corrosion Control – Atmospheric - 192.481 - Use Form 13
  11. Corrosion Control – Examination - 192.459 - Use Form 1
  12. Corrosion Control – Rectifiers - 192.465 - Use Form 15
  13. Testing of Piping - 192.501 to 192.517 - Use Form 16

NOTE: Certain components of this maintenance schedule may not be applicable to some smaller "Master Meter Operators."

GENERAL MAINTENANCE SCHEDULE (#2)

[Web Editor's Note: Due to the graphical nature of the Maintenance Schedule (#2) form, please contact the Office of Training and Qualifications at 405-954-7219 or phmsa.pipeline-training@dot.gov if you have difficulties with the attached PDF documents.]

NOTE: Certain components of this maintenance schedule may not be applicable to some smaller "Master Meter Operators." Shade in the month you intend to perform the maintenance and post in a prominent location as a reminder.

Appendix C - State Listing

Last Updated: 10/27/2006

 

STATE

REGULATORY AGENCY

PIPELINE SAFETY CONTACT

PHONE NUMBER

FAX NUMBER

E-MAIL

EAST

CONNECTICUT

DEPT. OF PUBLIC UTILITY CONTROL

PHILIP SHER

(860) 827-2604

(860) 827-2613

ct@napsr.net

DELAWARE

PUBLIC SERVICE COMMISSION

MALAK MICHAEL

(302) 739-2613

(302) 739-4849

de@napsr.net

DISTRICT OF COLUMBIA

PUBLIC SERVICE COMMISSION

DELVONE NICHOLSON‑MEADE

(202) 626-9166

(202) 626-9174

dc@napsr.net

MAINE

PUBLIC UTILITIES COMMISSION

GARY FARMER

(207) 287-1385

(207) 287-1039

me@napsr.net

MARYLAND

PUBLIC SERVICE COMMISSION

JOHN CLEMENTSON

(410) 767-8111

(410) 333-0884

md@napsr.net

MASSACHUSETTS

DEPT. OF TELECOM. & ENERGY

CHRIS BOURNE (ACTING)

(617) 305-3721

(617) 478-2589

ma@napsr.net

NEW HAMPSHIRE

PUBLIC UTILITIES COMMISSION

RANDALL KNEPPER

(603) 271-6026

(603) 271-6048

nh@napsr.net

NEW JERSEY

BOARD OF PUBLIC UTILITIES

EDWARD LIHAN

(973) 648-4959

(908) 904-6552

nj@napsr.net

NEW YORK

DEPARTMENT OF PUBLIC SERVICE

GAVIN NICOLETTA

(518) 486-2496

(518) 473-5625

ny@napsr.net

PENNSYLVANIA

PUBLIC UTILITY COMMISSION

PAUL METRO

(717) 787-1063

(717) 787-3114

pa@napsr.net

RHODE ISLAND

DIV. OF PUBLIC UTILITIES & CARRIERS

DONALD LEDVERSIS

(401) 941-4500 x123

(401) 941-4885

ri@napsr.net

VERMONT

DEPARTMENT OF PUBLIC SERVICE

HANS MERTENS

(802) 828-4007

(802) 828-2342

vt@napsr.net

VIRGINIA

STATE CORPORATION COMMISSION

MASSOUD TAHAMTANI

(804) 371-9264

(804) 371-9350

va@napsr.net

WEST VIRGINIA

PUBLIC SERVICE COMMISSION

DARRELL A. MCKOWN

(304) 340-0473

(304) 340-3755

wv@napsr.net

SOUTH

ALABAMA

PUBLIC SERVICE COMMISSION

CHRIS J. HARVEY

(334) 242-5778

(334) 242-0687

al@napsr.net

ARKANSAS

PUBLIC SERVICE COMMISSION

DON E. MARTIN

(501) 682-5705

(501) 682-5340

ar@napsr.net

FLORIDA

PUBLIC SERVICE COMMISSION

C. EDWARD MILLS

(850) 413-6650

(850) 413-6651

flpuc@napsr.net

FLORIDA

DEPT. OF AGRI. & CONSUMER SERVICES

VICKI O’NEIL

(850) 921-8001

(850) 921-8079

fllpg@napsr.net

GEORGIA

PUBLIC SERVICE COMMISSION

DANNY L. MCGRIFF

(404) 463-6526

(404) 463-6532

ga@napsr.net

KENTUCKY

PUBLIC SERVICE COMMISSION

JASON BRANGERS

(502) 564-3940 x416

(502) 564-1582

ky@napsr.net

MISSISSIPPI

PUBLIC SERVICE COMMISSION

MARK MCCARVER

(601) 961-5475

(601) 961-5469

ms@napsr.net

NORTH CAROLINA

UTILITIES COMMISSION

JAMES D. ANDERSON

(919) 733-1249

(919) 733-7300

nc@napsr.net

PUERTO RICO

PUBLIC SERVICE COMMISSION

HECTOR TORRES‑CORREA

(787) 756-1418

(787) 767-3069

pr@napsr.net

SOUTH CAROLINA

PUBLIC SERVICE COMMISSION

VERNON GAINEY

(803) 737-0914 x1144

(803) 896-5199

sc@napsr.net

TENNESSEE

REGULATORY AUTHORITY

GLYNN BLANTON

(800) 342-8359 x185

(615) 741-1228

tn@napsr.net

CENTRAL

ILLINOIS

COMMERCE COMMISSION

DARIN BURK

(217) 785-1165

(217) 524-5516

il@napsr.net

INDIANA

UTILITY REGULATORY COMMISSION

ANNMARIE ROBERTSON

(317) 232-2717

(317) 232-6758

in@napsr.net

IOWA

UTILITIES BOARD

DONALD J. STURSMA

(515) 281-5546

(515) 281-5329

ia@napsr.net

KANSAS

CORPORATION COMMISSION

LEO HAYNOS

(785) 271-3278

(785) 271-3357

ks@napsr.net

MICHIGAN

PUBLIC SERVICE COMMISSION

PAUL PROUDFOOT

(517) 241-6142

(517) 241-6121

mi@napsr.net

MINNESOTA

DEPARTMENT OF PUBLIC SAFETY

CHARLES R. KENOW

(651) 296-9638

(651) 296-9641

mn@napsr.net

MISSOURI

PUBLIC SERVICE COMMISSION

ROBERT R. LEONBERGER

(573) 751-3456

(573) 522-1946

mo@napsr.net

NEBRASKA

STATE FIRE MARSHAL

CLARK CONKLIN

(402) 471-9467

(402) 471-3118

ne@napsr.net

NORTH DAKOTA

PUBLIC SERVICE COMMISSION

ALAN MOCH

(701) 328-2413

(701) 328-1506

nd@napsr.net

OHIO

PUBLIC UTILITIES COMMISSION

EDWARD M. STEELE

(614) 644-8983

(614) 728-4319

oh@napsr.net

SOUTH DAKOTA

PUBLIC UTILITIES COMMISSION

MARTIN C. BETTMANN

(605) 773-6347

(605) 773-3809

sd@napsr.net

WISCONSIN

PUBLIC SERVICE COMMISSION

TOM STEMRICH

(608) 266-2800

(608) 266-3957

wi@napsr.net

SO. WEST

ARIZONA

CORPORATION COMMISSION

ROBERT MILLER (ACTING)

(602) 262-5601

(602) 262-5620

az@napsr.net

LOUISIANA

DEPT. OF NATURAL RESOURCES

JAMES MERGIST

(225) 342-9137

(225) 342-5529

la@napsr.net

NEW MEXICO

PUBLIC REGULATION COMMISSION

BRUNO CARRARA

(505) 827-3772

(505) 827-3767

nm@napsr.net

OKLAHOMA

CORPORATION COMMISSION

DENNIS FOTHERGILL

(405) 521-2258

(405) 521-3455

ok@napsr.net

TEXAS

RAILROAD COMMISSION

MARY L. MCDANIEL

(512) 463-7058

(512) 463-7319

tx@napsr.net

WEST

CALIFORNIA

PUBLIC UTILITIES COMMISSION

RAFFY STEPANIAN

(213) 576-7019

(415) 703-1891

czw@cpuc.ca.gov

CALIFORNIA

OFFICE OF STATE FIRE MARSHAL

BOB GORHAM

(562) 497-9102

(916) 445-8526

casfm@napsr.net

COLORADO

PUBLIC UTILITIES COMMISSION

STEVE POTT

(303) 894-2851

(303) 894-2065

co@napsr.net

HAWAII (Not In Program)

PUBLIC UTILITIES COMMISSION

RICHARD VAN DRUNEN

(808) 586-2043

(808) 586-2066

 

IDAHO

PUBLIC UTILITIES COMMISSION

RON LAW

(208) 334-0330

(208) 334-3762

id@napsr.net

MONTANA

PUBLIC SERVICE COMMISSION

JOEL TIERNEY

(406) 444-6181

(406) 444-7618

mt@napsr.net

NEVADA

PUBLIC UTILITIES COMMISSION

CRAIG STEELE

(775) 684-6146

(775) 684-6142

nv@napsr.net

OREGON

PUBLIC UTILITY COMMISSION

MICHAEL THOMPSON

(503) 378-6760

(503) 373-7752

or@napsr.net

UTAH

DEPARTMENT OF COMMERCE

AL ZADEH

(801) 530-7622

(801) 530-6512

ut@napsr.net

WASHINGTON

UTILITIES TRANS. COMMISSION

ALAN E. RATHBUN

(360) 664-1254

(360) 586-1172

wa@napsr.net

WYOMING

PUBLIC SERVICE COMMISSION

DAVID PIROUTEK

(307) 777-7427

(307) 777-5700

wy@napsr.net

Careers  |  Contact Us  |  No Fear  |  Privacy Policy  |  FOIA  |  Accessibility  |  FAQs  |  Web Policies  |  Site Map  |  Download Acrobat