SUBJECT: Hazard Information Bulletin(1): Fire Hazard From Carbon Adsorption Deodorizing Systems


The Environmental Protection Agency (EPA) recently issued an Alert concerning the fire hazard from carbon adsorption deodorizing systems.

PROBLEM

Activated carbon systems used to adsorb vapors for control of offensive odors may pose a fire hazard when used for certain types of substances, if proper procedures are not followed. In particular, crude sulfate turpentine, commonly produced in the pulp and paper industry, can pose a fire hazard if the adsorption system is not properly designed and proper procedures are not implemented. Facilities should take precautions to minimize this fire hazard.

ACCIDENTS

In a 1995 accident at a chemical terminal facility, a fire and explosion occurred involving three tanks of crude sulfate turpentine. The tanks were connected to drums of activated carbon for deodorizing. The fire and explosion damaged other storage tanks, resulting in the release of toxic gases and forcing a large-scale evacuation of area residents.

Fires have occurred in the past in activated carbon systems used for deodorizing crude sulfate turpentine. In general, such fires have not had collateral effects on the scale as those reported in the 1995 fire. Large scale collateral effects would not be expected if fires are confined to the activated carbon containers and do not spread to tanks containing flammable or combustible substances.

HAZARD AWARENESS

Activated carbon is widely used to adsorb vapors to prevent their release to the air. For certain classes of chemicals, reaction or adsorption on the carbon surface is accompanied by release of a large amount of heat that may cause hot spots in the carbon bed. Such chemicals include organic sulfur compounds (e.g., mercaptans), which may be found as impurities in crude sulfate turpentine and other materials. Other classes of chemicals that may cause large thermal releases are ketones, aldehydes, and some organic acids. Adsorption of high vapor concentrations of organic compounds also can create hot spots. If flammable vapors are present, the heat released by adsorption or reaction on the surface of the carbon may pose a fire hazard (e.g., a fire may start if the temperature reaches the autoignition temperature of the vapor and oxygen is present to support ignition).

The potential for fire in carbon adsorption deodorizing systems may increase at night. At certain times (typically during the day), high temperatures may lead to the expansion of vapor in the systems, and vapor is likely to exit to the atmosphere. When temperatures drop (typically at night), a slight vacuum may be created, causing air to be drawn into the system. If the carbon surface is very hot, because of the heat generated by adsorption, air drawn in over the carbon may provide the oxygen to start a fire.

HAZARD REDUCTION

Facilities should be aware of the potential fire hazards of activated carbon systems for absorbing flammable vapors and take steps to minimize these hazards. Actions that may help to prevent fires include:

  • Follow the manufacturer's instructions for design and operation of activated carbon adsorption systems.

  • Ensure that a qualified engineer or technician supervises the design, construction, and operation of the carbon adsorption systems.

  • Evaluate the composition of the vapors that will contact the carbon and heed the manufacturer's warnings about potential hazardous interactions with the carbon. If the vapor may contain organic sulfur compounds (e.g., vapor from crude sulfate turpentine), ketones, aldehydes, or organic acids, or if the vapor contains high concentrations of organic compounds, consider the potential for development of hot spots on the carbon.

  • Test the action of the vapors on carbon for potential heat release before putting the carbon adsorption system into service, if possible reactions are not known.

  • If test results or known reactions with carbon indicate the potential for fires in the activated carbon system, design the system so that air does not enter the system over the carbon bed (e.g., install vacuum breakers on the storage tanks).

  • If the potential exists for fires in the activated carbon system, be sure the carbon containers are separated from containers of flammable or combustible substances and can be easily, rapidly and safely removed in case the container becomes hot or catches fire.

  • If high concentrations of organic compounds may cause development of high temperatures, take steps to control the heating. Such steps may include diluting inlet air, time weighting the inlet concentration to allow heat to dissipate, and prewetting the carbon.

  • Visually inspect activated carbon adsorption systems frequently for hot spots and fires.

  • Before using an activated carbon adsorption system, ensure that safety systems are in place for fire prevention and mitigation, including flame arrestors to prevent the spread of fire from the carbon containers to the flammable chemical containers.

  • Ensure that flammable and combustible chemicals connect to activated carbon adsorption systems are handled in accordance with applicable regulations, codes, and standards.

APPLICABLE OSHA STANDARDS
  • Flammable and combustible liquids, 29 CFR 1910.106.

  • Process safety management of highly hazardous chemicals, 29 CFR 1910.119 - which contains requirements for preventing or minimizing the consequences of catastrophic releases of toxic, reactive, flammable or explosive chemicals; these releases may result in toxic, fire or explosion hazards.

INFORMATION RESOURCES

For additional information about the fire hazards of activated carbon adsorption systems and methods of minimizing them consult the following.

  1. EPA, Chemical Emergency Preparedness and Prevention Office, at telephone number (202) 260-8600. "Alert-Fire Hazard From Carbon Adsorption Deodorizing Systems", EPA 550-F-97-002-e, May 1997.

  2. Information on carbon adsorption systems for crude sulfate turpentine can be found in W.A. Harrell, J.O. Sewall, and T.J. Walsh, "Control of Malodorous Compounds by Carbon Adsorption," American Institute of Chemical Engineers, Loss Prevention, Volume 12, 1979, pp 124-127;

  3. Manufacturers of activated carbon can provide product literature with information on properties, safe handling, and use.


Footnote(1)
The Directorate of Technical Support issues Hazard Information Bulletins (HIB) in accordance with OSHA Instruction CPL 2.65 to provide relevant information regarding unrecognized or misunderstood health hazards, inadequacies of materials, devices, techniques, and safety engineering controls. HIBs are initiated based on information provided by the field staff, studies, reports and concerns expressed by safety and health professionals, employers, and the public. Bulletins are developed based on a through evaluation of available facts and in coordination with appropriate parties.

 