[Code of Federal Regulations]
[Title 16, Volume 1]
[Revised as of January 1, 2005]
From the U.S. Government Printing Office via GPO Access
[CITE: 16CFR305.19]

[Page 270-316]
 
                     TITLE 16--COMMERCIAL PRACTICES
 
                   CHAPTER I--FEDERAL TRADE COMMISSION
 
 PART 305_RULE CONCERNING DISCLOSURES REGARDING ENERGY CONSUMPTION 
 
Sec. 305.19  Exemptions.

    The Commission has exempted manufacturers, private labelers, 
distributors, and/or retailers in some instances from specific 
requirements of this part. These exemptions are listed in this section. 
In some circumstances, use of the exemptions is conditioned on 
alternative performance by manufacturers, private labelers, 
distributors, and/or retailers.
    (a) Limited conditional exemption for manufacturers from the 
prohibition against the inclusion of non-required information on the 
label of covered products that qualify for inclusion in the ENERGY STAR 
Program maintained by the Department of Energy (``DOE'') and the 
Environmental Protection Agency (``EPA''). Those manufacturers 
participating in the DOE/EPA ENERGY STAR Program who wish to place the 
ENERGY STAR logo on EnergyGuides affixed to covered products they 
manufacture that qualify for inclusion in the ENERGY STAR Program are 
granted a conditional exemption from the prohibition against placing 
``information other than that specified'' by the Rule on the 
EnergyGuides they attach to their qualifying products. This exemption is 
based on several conditions:
    (1) The ENERGY STAR logo is permitted on the EnergyGuides of only 
those covered products that meet the ENERGY STAR Program qualification 
criteria that are current at the time the products are labeled.
    (2) Only manufacturers that have signed a Memorandum of 
Understanding with DOE or EPA may add the ENERGY STAR logo to labels on 
qualifying covered products; such manufacturers may add the ENERGY STAR 
logo to labels only on those covered products that are contemplated by 
the Memorandum of Understanding.
    (3) Manufacturers that choose to avail themselves of the conditional 
exemption may print the ENERGY STAR logo on EnergyGuides for qualified 
products as part of the usual label printing process or may place the 
logo on EnergyGuides for qualified products by whatever means is most 
efficient for them, provided such placement complies with the 
requirements of paragraph (a)(4), of this section.
    (4) Manufacturers must place the logo on the EnergyGuide above the 
comparability bar in the box that contains the applicable range of 
comparability. The precise location of the logo will vary depending on 
where the caret indicating the position of the labeled model on the 
scale appears (see the sample label). The required dimensions of the 
logo must be one and one-eighth inches (3 cm.) in width and three-
quarters of an inch (2 cm.) in height. Manufacturers are prohibited from 
placing the logo in a way that would obscure, detract from, alter the 
dimensions of, or touch any element of the EnergyGuide, which in all 
other respects must conform to the requirements of this part. The ENERGY 
STAR logo must be in process black ink to match the print specifications 
for the EnergyGuide. The background must remain in process yellow to 
match the rest of the label.
    (5) Manufacturers must add a sentence in process black ink that 
explains the significance of the ENERGY STAR logo in ten-point Helvetica 
Condensed Black typeface. The sentence must be next to the logo, above 
the comparability bar that shows the ``least'' and ``most'' numbers. The 
sentence must read:

    ENERGY STAR A symbol of energy efficiency.


[[Page 271]]


    (b) [Reserved]

[65 FR 17563, Apr. 3, 2000]

      Appendix A1 to Part 305--Refrigerators With Automatic Defrost

                           [Range Information]
------------------------------------------------------------------------
                                      Range of estimated annual energy
    Manufacturer's rated total              consumption (kWh/yr.)
 refrigerated volume in cubic feet -------------------------------------
                                           Low                High
------------------------------------------------------------------------
Less than 2.5.....................                318                338
2.5 to 4.4........................                319                385
4.5 to 6.4........................                383                436
6.5 to 8.4........................                (*)                (*)
8.5 to 10.4.......................                348                380
10.5 to 12.4......................                (*)                (*)
12.5 to 14.4......................                (*)                (*)
14.5 to 16.4......................                428                428
16.5 and over.....................                318               438
------------------------------------------------------------------------
* No data submitted for units meeting the Department of Energy's Energy
  Conservation Standards effective July 1, 2001.


[66 FR 57868, Nov. 19, 2001]

 Appendix A2 to Part 305--Refrigerators and Refrigerators-Freezers With 
                             Manual Defrost

                           [Range Information]
------------------------------------------------------------------------
                                      Range of estimated annual energy
    Manufacturer's rated total              consumption (kWh/yr.)
 refrigerated volume in cubic feet -------------------------------------
                                           Low                High
------------------------------------------------------------------------
Less than 2.5.....................                280                320
2.5 to 4.4........................                292                345
4.5 to 6.4........................                296                364
6.5 to 8.4........................                387                387
8.5 to 10.4.......................                273                379
10.5 to 12.4......................                286                286
12.5 to 14.4......................                (*)                (*)
14.5 to 16.4......................                (*)                (*)
16.5 to 18.4......................                396                438
18.5 to 20.4......................                (*)                (*)
20.5 to 22.4......................                (*)                (*)
22.5 to 24.4......................                (*)                (*)
24.5 to 26.4......................                (*)                (*)
26.5 to 28.4......................                (*)                (*)
28.5 and over.....................                (*)               (*)
------------------------------------------------------------------------
* No data submitted for units meeting the Department of Energy's Energy
  Conservation Standards effective July 1, 2001.


[66 FR 57868, Nov. 19, 2001; 66 FR 63749, Dec. 10, 2001]

 Appendix A3 to Part 305--Refrigerator-Freezers With Partial Automatic 
                                 Defrost

                            Range Information
------------------------------------------------------------------------
                                      Range of estimated annual energy
    Manufacturer's rated total              consumption (kWh/yr.)
 refrigerated volume in cubic feet -------------------------------------
                                           Low                High
------------------------------------------------------------------------
Less than 10.5....................                285                434
10.5 to 12.4......................                313                313
12.5 to 14.4......................                (*)                (*)
14.5 to 16.4......................                (*)                (*)
16.5 to 18.4......................                (*)                (*)
18.5 to 20.4......................                (*)                (*)
20.5 to 22.4......................                (*)                (*)
22.5 to 24.4......................                (*)                (*)
24.5 to 26.4......................                (*)                (*)
26.5 to 28.4......................                (*)                (*)

[[Page 272]]


28.5 and over.....................                (*)               (*)
------------------------------------------------------------------------
(*) No data submitted for units meeting the Department of Energy's
  Energy Conservation Standards effective July 1, 2001.


[66 FR 57869, Nov. 19, 2001]

 Appendix A4 to Part 305--Refrigerator-Freezers With Automatic Defrost 
      With Top-Mounted Freezer Without Through-the-Door Ice Service

                            Range Information
------------------------------------------------------------------------
                                      Range of estimated annual energy
    Manufacturer's rated total              consumption (kWh/yr.)
 refrigerated volume in cubic feet -------------------------------------
                                           Low                High
------------------------------------------------------------------------
Less than 10.5....................                356                356
10.5 to 12.4......................                408                409
12.5 to 14.4......................                394                440
14.5 to 16.4......................                372                460
16.5 to 18.4......................                414                489
18.5 to 20.4......................                416                509
20.5 to 22.4......................                457                530
22.5 to 24.4......................                499                558
24.5 to 26.4......................                523                560
26.5 to 28.4......................                (*)                (*)
28.5 and over.....................                (*)               (*)
------------------------------------------------------------------------
(*) No data submitted for units meeting the Department of Energy's
  Energy Conservation Standards effective1, 2001.


[66 FR 57869, Nov. 19, 2001]

 Appendix A5 to Part 305--Refrigerator-Freezers With Automatic Defrost 
     With Side-Mounted Freezer Without Through-the-Door Ice Service

                            Range Information
------------------------------------------------------------------------
                                      Range of estimated annual energy
    Manufacturer's rated total              consumption (kWh/yr.)
 refrigerated volume in cubic feet -------------------------------------
                                           Low                High
------------------------------------------------------------------------
Less than 10.5....................                (*)                (*)
10.5 to 12.4......................                (*)                (*)
12.5 to 14.4......................                (*)                (*)
14.5 to 16.4......................                (*)                (*)
16.5 to 18.4......................                (*)                (*)
18.5 to 20.4......................                623                624
20.5 to 22.4......................                568                640
22.5 to 24.4......................                605                643
24.5 to 26.4......................                591                659
26.5 to 28.4......................                (*)                (*)
28.5 and over.....................                614               679
------------------------------------------------------------------------
(*) No data submitted for units meeting the Department of Energy's
  Energy Conservation Standards effective July 1, 2001.


[66 FR 57869, Nov. 19, 2001]

 Appendix A6 to Part 305--Refrigerator-Freezers With Automatic Defrost 
    With Bottom-Mounted Freezer Without Through-the-Door Ice Service

                            Range Information
------------------------------------------------------------------------
                                      Range of estimated annual energy
    Manufacturer's rated total              consumption (kWh/yr.)
 refrigerated volume in cubic feet -------------------------------------
                                           Low                High
------------------------------------------------------------------------
Less than 10.5....................                447                500
10.5 to 12.4......................                (*)                (*)
12.5 to 14.4......................                (*)                (*)
14.5 to 16.4......................                544                544

[[Page 273]]


16.5 to 18.4......................                502                548
18.5 to 20.4......................                564                564
20.5 to 22.4......................                511                572
22.5 to 24.4......................                (*)                (*)
24.5 to 26.4......................                (*)                (*)
26.5 to 28.4......................                (*)                (*)
28.5 and over.....................                (*)               (*)
------------------------------------------------------------------------
(*) No data submitted for units meeting the Department of Energy's
  Energy Conservation Standards effective July 1, 2001.


[66 FR 57870, Nov. 19, 2001]

 Appendix A7 to Part 305--Refrigerator-freezers With Automatic Defrost 
       With Top-mounted Freezer With Through-the-door Ice Service

                          [Rangee Information]
------------------------------------------------------------------------
                                      Range of estimated annual energy
    Manufacturer's rated total              consumption (kWh/yr.)
 refrigerated volume in cubic feet -------------------------------------
                                           Low                High
------------------------------------------------------------------------
Less than 10.5....................                (*)                (*)
10.5 to 12.4......................                544                544
12.5 to 14.4......................                544                544
14.5 to 16.4......................                (*)                (*)
16.5 to 18.4......................                (*)                (*)
18.5 to 20.4......................                (*)                (*)
20.5 to 22.4......................                555                555
22.5 to 24.4......................                (*)                (*)
24.5 to 26.4......................                (*)                (*)
26.5 to 28.4......................                (*)                (*)
28.5 and over.....................                (*)               (*)
------------------------------------------------------------------------
* No data submitted for units meeting the Department of Energy's Energy
  Conservation Standards effectively July 1, 2001.


[66 FR 57870, Nov. 19, 2001]

 Appendix A8 to Part 305--Refrigerator-freezers With Automatic Defrost 
       With Side-mounted Freezer With Through-the-door Ice Service

                           [Range Information]
------------------------------------------------------------------------
                                      Range of estimated annual energy
    Manufacturer's rated total              consumption (kWh.yr.)
 refrigerated volume in cubic feet -------------------------------------
                                           Low                High
------------------------------------------------------------------------
Less than 10.5....................                (*)                (*)
10.5 to 12.4......................                (*)                (*)
12.5 to 14.4......................                (*)                (*)
14.5 to 16.4......................                (*)                (*)
16.5 to 18.4......................                (*)                (*)
18.5 to 20.4......................                647                650
20.5 to 22.4......................                597                686
22.5 to 24.4......................                617                698
24.5 to 26.4......................                618                727
26.5 to 28.4......................                647                751
28.5 and over.....................                691               765
------------------------------------------------------------------------
* No data submitted for units meeting the Department of Energy's Energy
  Conservation Standards effective July 1, 2001.

              Cost Information for Appendices A1 Through A8

    When the ranges of comparability in Appendices A1 through A8 are 
used on EnergyGuide labels for refrigerators and refrigerator-freezers, 
the estimated annual operating cost disclosure appearing in the box at 
the bottom of the labels must be derived using the 2001 Representative 
Average Unit Cost for electricity (8.29[cent] per kilowatt-hour), and 
the text below the box must identify the cost as such.

[66 FR 57871, Nov. 19, 2001]

[[Page 274]]

      Appendix B1 to Part 305--Upright Freezers With Manual Defrost

                           [Range information]
------------------------------------------------------------------------
                                      Range of estimated annual energy
    Manufacturer's rated total             consumption  (kWh/yr.)
 refrigerated volume in cubic feet -------------------------------------
                                           Low                High
------------------------------------------------------------------------
Less than 5.5.....................                (*)                (*)
5.5 to 7.4........................                354                354
7.5 to 9.4........................                372                372
9.5 to 11.4.......................                392                392
11.5 to 13.4......................                409                410
13.5 to 15.4......................                442                454
15.5 to 17.4......................                477                482
17.5 to 19.4......................                (*)                (*)
19.5 to 21.4......................                512                527
21.5 to 23.4......................                (*)                (*)
23.5 to 25.4......................                580                580
25.5 to 27.4......................                (*)                (*)
27.5 to 29.4......................                (*)                (*)
29.5 and over.....................              1,748             1,748
------------------------------------------------------------------------
* No data submitted for units meeting the Department of Energy's Energy
  Conservation Standards effective July 1, 2001.


[67 FR 4173, Jan. 29, 2002]

    Appendix B2 to Part 305--Upright Freezers With Automatic Defrost

                           [Range Information]
------------------------------------------------------------------------
                                      Range of estimated annual energy
    Manufacturer's rated total              consumption (kWh/yr.)
 refrigerated volume in cubic feet -------------------------------------
                                           Low                High
------------------------------------------------------------------------
Less than 5.5.....................                482                491
5.5 to 7.4........................                (*)                (*)
7.5 to 9.4........................                (*)                (*)
9.5 to 11.4.......................                564                564
11.5 to 13.4......................                (*)                (*)
13.5 to 15.4......................                621                655
15.5 to 17.4......................                682                683
17.5 to 19.4......................                742                742
19.5 to 21.4......................                745                763
21.5 to 23.4......................                796                796
23.5 to 25.4......................                (*)                (*)
25.5 to 27.4......................                (*)                (*)
27.5 to 29.4......................                (*)                (*)
29.5 and over.....................              2,003             2,033
------------------------------------------------------------------------
* No data submitted for units meeting the Department of Energy's Energy
  Conservation Standards effective July 1, 2001.


[66 FR 57871, Nov. 19, 2001]

     Appendix B3 to Part 305--Chest Freezers and All Other Freezers

                           [Range Information]
------------------------------------------------------------------------
                                      Range of estimated annual energy
    Manufacturer's rated total              consumption (kWh/yr.)
 refrigerated volume in cubic feet -------------------------------------
                                           Low                High
------------------------------------------------------------------------
Less than 5.5.....................                166                245
5.5 to 7.4........................                276                280
7.5 to 9.4........................                294                294
9.5 to 11.4.......................                312                312
11.5 to 13.4......................                350                362
13.5 to 15.4......................                394                397
15.5 to 17.4......................                (*)                (*)
17.5 to 19.4......................                445                445
19.5 to 21.4......................                480                480
21.5 to 23.4......................                512                532
23.5 to 25.4......................                569                570
25.5 to 27.4......................                (*)                (*)
27.5 to 29.4......................                (*)                (*)

[[Page 275]]


29.5 and over.....................                (*)               (*)
------------------------------------------------------------------------
* No data submitted for units meeting the Department of Energy's Energy
  Conservation Standards effective July 1, 2001.

              Cost Information for Appendices B1 Through B3

    When the ranges of comparability in Appendices B1 through B3 are 
used on EnergyGuide labels for freezers, the estimated annual operating 
cost disclosure appearing in the box at the bottom of the labels must be 
derived using the 2001 Representative Average Unit Cost for electricity 
(8.29[cent] per kilowatt-hour), and the text below the box must identify 
the cost as such.

[66 FR 57872, Nov. 19, 2001]

              Appendix C1 to Part 305--Compact Dishwashers

                            Range Information

    ``Compact'' includes countertop dishwasher models with a capacity of 
fewer than eight (8) place settings. Place settings shall be in 
accordance with appendix C to 10 CFR part 430, subpart B. Load patterns 
shall conform to the operating normal for the model being tested.

------------------------------------------------------------------------
                                             Range of estimated annual
                                           energy consumption (kWh/yr.)
                Capacity                 -------------------------------
                                                Low            High
------------------------------------------------------------------------
Compact.................................             176             247
------------------------------------------------------------------------

                            Cost Information

    When the above ranges of comparability are used on EnergyGuide 
labels for compact-sized dishwashers, the estimated annual operating 
cost disclosure appearing in the box at the bottom of the labels must be 
derived using the 2004 Representative Average Unit Costs for electricity 
(8.60[cent] per kiloWatt-hour) and natural gas (91.0[cent] per therm), 
and the text below the box must identify the costs as such.

[69 FR 54560, Sept. 9, 2004]

              Appendix C2 to Part 305--Standard Dishwashers

                            Range Information

    ``Standard'' includes portable or built-in dishwasher models with a 
capacity of eight (8) or more place settings. Place settings shall be in 
accordance with appendix C to 10 CFR part 430, subpart B. Load patterns 
shall conform to the operating normal for the model being tested.

------------------------------------------------------------------------
                                             Range of estimated annual
                                           energy consumption (kWh/yr.)
                Capacity                 -------------------------------
                                                Low            High
------------------------------------------------------------------------
Standard................................             194             531
------------------------------------------------------------------------

                            Cost Information

    When the above ranges of comparability are used on EnergyGuide 
labels for standard-sized dishwashers, the estimated annual operating 
cost disclosure appearing in the box at the bottom of the labels must be 
derived using the 2004 Representative Average Unit Costs for electricity 
(8.60[cent] per kiloWatt-hour) and natural gas (91.0[cent] per therm), 
and the text below the box must identify the costs as such.

[69 FR 54560, Sept. 9, 2004]

[[Page 276]]

               Appendix D1 to Part 305--Water Heaters--Gas

                                               [Range information]
----------------------------------------------------------------------------------------------------------------
                    Capacity                       Range of estimated annual energy consumption  (therms/yr. and
-------------------------------------------------                          gallons/yr.)
                                                 ---------------------------------------------------------------
                                                      Natural gas therms/yr.            Propane gallons/yr.
                First hour rating                ---------------------------------------------------------------
                                                        Low            High             Low            High
----------------------------------------------------------------------------------------------------------------
Less than 21....................................             (*)             (*)             (*)             (*)
21 to 24........................................             (*)             (*)             (*)             (*)
25 to 29........................................             (*)             (*)             (*)             (*)
30 to 34........................................             (*)             (*)             (*)             (*)
35 to 40........................................             (*)             (*)             (*)             (*)
41 to 47........................................             (*)             (*)             (*)             (*)
48 to 55........................................             234             254             256             278
56 to 64........................................             246             254             269             278
65 to 74........................................             234             258             256             283
75 to 86........................................             230             272             256             288
87 to 99........................................             242             272             265             288
100 to 114......................................             230             283             252             298
115 to 131......................................             242             312             265             309
Over 131........................................             254             312             278            342
----------------------------------------------------------------------------------------------------------------
* No data submitted.


[69 FR 42108, Oct. 12, 2004]

            Appendix D2 to Part 305--Water Heaters--Electric

                           [Range information]
------------------------------------------------------------------------
                Capacity                     Range of estimated annual
-----------------------------------------  energy consumption  (KWh/yr.)
                                         -------------------------------
            First hour rating                   Low            High
------------------------------------------------------------------------
Less than 21............................             (*)             (*)
21 to 24................................             (*)             (*)
25 to 29................................            4721            4721
30 to 34................................            4721            4773
35 to 40................................            4671            4934
41 to 47................................            4671            4990
48 to 55................................            4622            4879
56 to 64................................            4622            4879
65 to 74................................            4671            4934
75 to 86................................            4622            5106
87 to 99................................            4773            5166
100 to 114..............................            4825            5421
115 to 131..............................            5106            5355
Over 131................................             (*)            (*)
------------------------------------------------------------------------
* No data submitted.


[69 FR 42108, Oct. 12, 2004]

               Appendix D3 to Part 305--Water Heaters--Oil

                           [Range information]
------------------------------------------------------------------------
                Capacity                     Range of estimated annual
-----------------------------------------  energy consumption  (gallons/
                                                       yr.)
            First hour rating            -------------------------------
                                                Low             High
------------------------------------------------------------------------
Less than 65............................             (*)             (*)
65 to 74................................             (*)             (*)
75 to 86................................             (*)             (*)
87 to 99................................             (*)             (*)
100 to 114..............................             174             200
115 to 131..............................             159             200
Over 131................................             164            212
------------------------------------------------------------------------
* No data submitted.


[69 FR 42108, Oct. 12, 2004]

[[Page 277]]

        Appendix D4 to Part 305--Water Heaters-Instantaneous-Gas

                            Range Information

----------------------------------------------------------------------------------------------------------------
                                                   Range of estimated annual energy consumption  (therms/yr. and
                                                                           gallons/ yr.)
Capacity (maximum flow rate); gallons per minute ---------------------------------------------------------------
                      (gpm)                           Natural gas therms/yr.            Propane gallons/yr.
                                                 ---------------------------------------------------------------
                                                        Low            High             Low            High
----------------------------------------------------------------------------------------------------------------
Under 1.00......................................             235             235             256             256
1.00 to 2.00....................................             230             230             252             252
2.01 to 3.00....................................             185             220             196             239
Over 3.00.......................................             177             238             187             260
----------------------------------------------------------------------------------------------------------------


[69 FR 54560, Sept. 9, 2004]

            Appendix D5 to Part 305--Water Heaters--Heat Pump

                           [Range information]
------------------------------------------------------------------------
                Capacity                     Range of estimated annual
-----------------------------------------  energy consumption  (KWh/Yr.)
                                         -------------------------------
            First hour rating                   Low            High
------------------------------------------------------------------------
Less than 21............................             (*)             (*)
21 to 24................................             (*)             (*)
25 to 29................................             (*)             (*)
30 to 34................................             (*)             (*)
35 to 40................................             (*)             (*)
41 to 47................................             (*)             (*)
48 to 55................................             (*)             (*)
56 to 64................................            1830            1830
65 to 74................................             (*)             (*)
75 to 86................................             (*)             (*)
87 to 99................................             (*)             (*)
100 to 114..............................             (*)             (*)
115 to 131..............................             (*)             (*)
Over 131................................             (*)            (*)
------------------------------------------------------------------------
* No data submitted.

                            Cost Information

    When the above ranges of comparability in Appendices D1 through D5 
are used on EnergyGuide labels for water heaters, the estimated annual 
operating cost disclosure appearing in the box at the bottom of the 
labels must be derived using the 2004 Representative Average Unit Costs 
for electricity (8.60[cent] per kiloWatt-hour), natural gas (91.0[cent] 
per therm), propane ($1.23 per gallon, and heating oil ($1.28 per 
gallon) and the text below the box must identify the costs as such.

[69 FR 42108, Oct. 12, 2004]

              Appendix E to Part 305--Room Air Conditioners

                           [Range Information]
------------------------------------------------------------------------
                                      Range of Energy Efficiency Ratios
   Manufacturer's rated cooling                    (EERs)
       capacity in Btu's/yr.       -------------------------------------
                                           Low                High
------------------------------------------------------------------------
Without Reverse Cycle and with
 Louvered Sides:
    Less than 6,000 Btu...........                8.0               10.0
    6,000 to 7,999 Btu............                8.5               10.3
    8,000 to 13,999 Btu...........                9.0               12.0
    14,000 to 19,999 Btu..........                8.8               10.7
    20,000 and more Btu...........                8.2               10.0
Without Reverse Cycle and without
 Louvered Sides:
    Less than 6,000 Btu...........                (*)                (*)
    6,000 to 7,999................                8.5                9.6
    8,000 to 13,999 Btu...........                8.5                9.2
    14,000 to 19,999 Btu..........                (*)                (*)

[[Page 278]]


    20,000 and more Btu...........                (*)                (*)
With Reverse Cycle and with                       8.5               11.5
 Louvered Sides...................
With Reverse Cycle, without                       8.0                9.0
 Louvered Sides...................
------------------------------------------------------------------------
* No data submitted for units meeting Federal Minimum Efficiency
  Standards effective January 1, 1990.


[60 FR 56949, Nov. 13, 1995]

            Appendix F1 to Part 305--Standard Clothes Washers

                            Range Information

    ``Standard'' includes all household clothes washers with a tub 
capacity of 1.6 cu. ft or 13 gallons of water or more.

------------------------------------------------------------------------
                                                            Range of
                                                        estimated annual
                                                             energy
                       Capacity                            consumption
                                                            (kWh/yr.)
                                                       -----------------
                                                          Low      High
------------------------------------------------------------------------
Standard..............................................      177     1298
------------------------------------------------------------------------

                            Cost Information

    When the above range of comparability is used on EnergyGuide labels 
for standard clothes washers, the estimated annual operating cost 
disclosure appearing in the box at the bottom of the labels must be 
derived using the 2000 Representative Average Unit Costs for electricity 
(8.03[cent] per kiloWatt-hour) and natural gas (68.8.6[cent] per therm), 
and the text below the box must identify the costs as such.

            Appendix F2 to Part 305--Compact Clothes Washers

                            Range Information

    ``Compact'' includes all household clothes washers with a tub 
capacity of less than 1.6 cu. ft. or 13 gallons of water.

------------------------------------------------------------------------
                                                            Range of
                                                        estimated annual
                                                             energy
                       Capacity                            consumption
                                                            (kWh/yr.)
                                                       -----------------
                                                          Low      High
------------------------------------------------------------------------
Compact...............................................      350      653
------------------------------------------------------------------------

                            Cost Information

    When the above range of comparability is used on EnergyGuide labels 
for compact clothes washers, the estimated annual operating cost 
disclosure appearing in the box at the bottom of the labels must be 
derived using the 2003 Representative Average Unit Costs for electricity 
(8.41[cent] per kiloWatt-hour) and natural gas (81.6[cent] per therm), 
and the text below the box must identify the costs as such.

[[Page 279]]

                 Appendix G1 to Part 305--Furnaces--Gas

                         [1. Range Information]
------------------------------------------------------------------------
                                      Range of annual fuel utilization
   Manufacturer's rated heating             efficiencies (AFUE's)
      capacities (Btu's/hr.)       -------------------------------------
                                           Low                High
------------------------------------------------------------------------
All Capacities....................                 78               96.6
------------------------------------------------------------------------


                 [2. Yearly Cost Information: Cost Grid]
------------------------------------------------------------------------
                                                        Btu heat loss of
              Cost per kilowatt hour \1\                home (see chart
                                                             below)
------------------------------------------------------------------------
 4[cent].............................................
 6[cent].............................................
 8[cent].............................................
10[cent].............................................
12[cent].............................................
14[cent].............................................
------------------------------------------------------------------------
\1\ For charts on natural gas, oil and propane gas, substitute the
  following cost figures:
a. Cost per therm--10[cent], 20[cent], 30[cent], 40[cent], 50[cent],
  60[cent].
b. Cost per gallon (oil)--76[cent], 79[cent], 82[cent], 85[cent],
  88[cent], 91[cent], 94[cent], 97[cent], $1.00.
c. Cost per gallon (propane)--35[cent], 40[cent], 45[cent], 50[cent],
  55[cent], 60[cent].

    The following table shows the heat loss values (in thousand Btu's/
hr.) to be used in the cost grid:

                                                [Heat Loss Table]
----------------------------------------------------------------------------------------------------------------
                                                                      Design heat loss
 Manufacturers rated heat output of model to be labeled (Btu's per     of model to be    Heat loss values to be
                               hour)                                   labeled (1,000    used on the grid (1,000
                                                                      Btu's per hour)        Btu's per hour)
----------------------------------------------------------------------------------------------------------------
 5,000 to 10,000...................................................                  5                         5
 11,000 to 16,000..................................................                 10                     5, 10
 17,000 to 25,000..................................................                 15                    10, 15
 26,000 to 42,000..................................................                 20                15, 20, 25
 43,000 to 59,000..................................................                 30            25, 30, 35, 40
 60,000 to 76,000..................................................                 40            35, 40, 45, 50
 77,000 to 93,000..................................................                 50            40, 45, 50, 60
 94,000 to 110,000.................................................                 60            50, 60, 70, 80
111,000 to 127,000.................................................                 70            60, 70, 80, 90
128,000 to 144,000.................................................                 80           70, 80, 90, 100
145,000 to 161,000.................................................                 90     80, 90, 100, 110, 120
162,000 to 178,000.................................................                100    90, 100, 110, 120, 130
179,000 to 195,000.................................................                110   100, 110, 120, 130, 140
196,000 and over...................................................                130   120, 130, 140, 150, 160
----------------------------------------------------------------------------------------------------------------

    Beside each cost in the cost grid, and below the appropriate heat 
loss value taken from the heat loss table, place the cost estimate for 
the model being labeled using the table costs in place of the national 
average cost and using the heat loss values in place of the design heat 
loss used in the table with the national average cost.

[59 FR 34042, July 1, 1994, as amended at 59 FR 48798, Sept. 23, 1994]

               Appendix G2 to Part 305--Furnaces--Electric

                         [1. Range Information]
------------------------------------------------------------------------
                                      Ranges of annual fuel utilization
   Manufacturer's rated heating             efficiencies (AFUE's)
      capacities (Btu's/hr.)       -------------------------------------
                                           Low                High
------------------------------------------------------------------------
All Capacities....................                100                100
------------------------------------------------------------------------


                 [2. Yearly Cost Information: Cost Grid]
------------------------------------------------------------------------
                                                        Btu heat loss of
              Cost per kilowatt hour \1\                home (see chart
                                                             below)
------------------------------------------------------------------------
4[cent]..............................................
6[cent]..............................................
8[cent]..............................................

[[Page 280]]


10[cent].............................................
12[cent].............................................
14[cent].............................................
------------------------------------------------------------------------
\1\ For charts on natural gas, oil and propane gas, substitute the
  following cost figures:
a. Cost per therm--10[cent], 20[cent], 30[cent], 40[cent], 50[cent],
  60[cent].
b. Cost per gallon (oil)--76[cent], 79[cent], 82[cent], 85[cent],
  88[cent], 91[cent], 94[cent], 97[cent], $1.00.
c. Cost per gallon (propane)--35[cent], 40[cent], 45[cent], 50[cent],
  55[cent], 60[cent].

    The following table shows the heat loss values (in thousand Btu's/
hr.) to be used in the cost grid:

                                                [Heat Loss Table]
----------------------------------------------------------------------------------------------------------------
                                                                      Design heat loss
 Manufacturers' rated heat output of model to be labeled (Btu's per    of model to be    Heat loss values to be
                               hour)                                   labeled (1,000    used on the grid (1,000
                                                                      Btu's per hour)        Btu's per hour)
----------------------------------------------------------------------------------------------------------------
5,000 to 10,000....................................................                  5                         5
11,000 to 16,000...................................................                 10                     5, 10
17,000 to 25,000...................................................                 15                    10, 15
26,000 to 42,000...................................................                 20                15, 20, 25
43,000 to 59,000...................................................                 30            25, 30, 35, 40
60,000 to 76,000...................................................                 40            35, 40, 45, 50
77,000 to 93,000...................................................                 50            40, 45, 50, 60
94,000 to 110,000..................................................                 60            50, 60, 70, 80
111,000 to 127,000.................................................                 70            60, 70, 80, 90
128,000 to 144,000.................................................                 80           70, 80, 90, 100
145,000 to 161,000.................................................                 90     80, 90, 100, 110, 120
162,000 to 178,000.................................................                100    90, 100, 110, 120, 130
179,000 to 195,000.................................................                110   100, 110, 120, 130, 140
196,000 and over...................................................                130   120, 130, 140, 150, 160
----------------------------------------------------------------------------------------------------------

    Beside each cost in the cost grid, and below the appropriate heat 
loss value taken from the heat loss table, place the cost estimate for 
the model being labeled using the table costs in place of the national 
average cost and using the heat loss values in place of the design heat 
loss used in the table with the national average cost.

[59 FR 34042, July 1, 1994, as amended at 59 FR 48798, Sept. 23, 1994]

                 Appendix G3 to Part 305--Furnaces--Oil

                         [1. Range Information]
------------------------------------------------------------------------
                                      Range of annual fuel utilization
   Manufacturer's rated heating             efficiencies (AFUE's)
      capacities (Btu's/hr.)       -------------------------------------
                                           Low                High
------------------------------------------------------------------------
All Capacities....................                 78               86.7
------------------------------------------------------------------------


                 [2. Yearly Cost Information: Cost Grid]
------------------------------------------------------------------------
                                                        Btu heat loss of
              Cost per kilowatt hour\1\                 home (see chart
                                                             below)
------------------------------------------------------------------------
4[cent]..............................................
6[cent]..............................................
8[cent]..............................................
10[cent].............................................
12[cent].............................................
14[cent].............................................
------------------------------------------------------------------------
\1\ For charts on natural gas, oil and propane gas, substitute the
  following cost figures:
a. Cost per therm--10[cent], 20[cent], 30[cent], 40[cent], 50[cent],
  60[cent].
b. Cost per gallon (oil)--76[cent], 79[cent], 82[cent], 85[cent],
  88[cent], 91[cent], 94[cent], 97[cent], $1.00.
c. Cost per gallon (propane)--35[cent], 40[cent], 45[cent], 50[cent],
  55[cent], 60[cent].

    The following table shows the heat loss values (in thousand Btu's/
hr.) to be used in the cost grid:

[[Page 281]]



                                                [Heat Loss Table]
----------------------------------------------------------------------------------------------------------------
                                                                      Design heat loss
 Manufacturers' rated heat output of model to be labeled (Btu's per    of model to be    Heat loss values to be
                               hour)                                   labeled (1,000    used on the grid (1,000
                                                                      Btu's per hour)        Btu's per hour)
----------------------------------------------------------------------------------------------------------------
5,000 to 10,000....................................................                  5                         5
11,000 to 16,000...................................................                 10                     5, 10
17,000 to 25,000...................................................                 15                    10, 15
26,000 to 42,000...................................................                 20                15, 20, 25
43,000 to 59,000...................................................                 30            25, 30, 35, 40
60,000 to 76,000...................................................                 40            35, 40, 45, 50
77,000 to 93,000...................................................                 50            40, 45, 50, 60
94,000 to 110,000..................................................                 60            50, 60, 70, 80
111,000 to 127,000.................................................                 70            60, 70, 80, 90
128,000 to 144,000.................................................                 80           70, 80, 90, 100
145,000 to 161,000.................................................                 90     80, 90, 100, 110, 120
162,000 to 178,000.................................................                100    90, 100, 110, 120, 130
179,000 to 195,000.................................................                110   100, 110, 120, 130, 140
196,000 and over...................................................                130   120, 130, 140, 150, 160
----------------------------------------------------------------------------------------------------------------

    Beside each cost in the cost grid, and below the appropriate heat 
loss value taken from the heat loss table, place the cost estimate for 
the model being labeled using the table costs in place of the national 
average cost and using the heat loss values in place of the design heat 
loss used in the table with the national average cost.

[59 FR 34042, July 1, 1994, as amended at 59 FR 48798, Sept. 23, 1994]

              Appendix G4 to Part 305--Mobile Home Furnaces

                         [1. Range Information]
------------------------------------------------------------------------
                                      Range of annual fuel utilization
   Manufacturer's rated heating             efficiencies (AFUE's)
      capacities (Btu's/hr.)       -------------------------------------
                                           Low                High
------------------------------------------------------------------------
All Capacities....................                 75               83.2
------------------------------------------------------------------------


                 [2. Yearly Cost Information: Cost Grid]
------------------------------------------------------------------------
                                                        Btu heat loss of
              Cost per kilowatt hour \1\                home (see chart
                                                             below)
------------------------------------------------------------------------
4[cent]..............................................
6[cent]..............................................
8[cent]..............................................
10[cent].............................................
12[cent].............................................
14[cent].............................................
------------------------------------------------------------------------
\1\ For charts on natural gas, oil and propane gas, substitute the
  following cost figures:
a. Cost per therm--10[cent], 20[cent], 30[cent], 40[cent], 50[cent],
  60[cent].
b. Cost per gallon (oil)--76[cent], 79[cent], 82[cent], 85[cent],
  88[cent], 91[cent], 94[cent], 97[cent], $1.00.
c. Cost per gallon (propane)--35[cent], 40[cent], 45[cent], 50[cent],
  55[cent], 60[cent].

    The following table shows the heat loss values (in thousand Btu's/
hr.) to be used in the cost grid:

                                                [Heat Loss Table]
----------------------------------------------------------------------------------------------------------------
                                                                      Design heat loss
 Manufacturers' rated heat output of model to be labeled (Btu's per    of model to be    Heat loss values to be
                               hour)                                   labeled (1,000    used on the grid (1,000
                                                                      Btu's per hour)        Btu's per hour)
----------------------------------------------------------------------------------------------------------------
5,000 to 10,000....................................................                  5                         5
5,000 to 10,000....................................................                  5                         5
11,000 to 16,000...................................................                 10                     5, 10
17,000 to 25,000...................................................                 15                    10, 15
26,000 to 42,000...................................................                 20                15, 20, 25
43,000 to 59,000...................................................                 30            25, 30, 35, 40
60,000 to 76,000...................................................                 40            35, 40, 45, 50
77,000 to 93,000...................................................                 50            40, 45, 50, 60
94,000 to 110,000..................................................                 60            50, 60, 70, 80
111,000 to 127,000.................................................                 70            60, 70, 80, 90
128,000 to 144,000.................................................                 80           70, 80, 90, 100
145,000 to 161,000.................................................                 90     80, 90, 100, 110, 120

[[Page 282]]


162,000 to 178,000.................................................                100    90, 100, 110, 120, 130
179,000 to 195,000.................................................                110   100, 110, 120, 130, 140
196,000 and over...................................................                130   120, 130, 140, 150, 160
----------------------------------------------------------------------------------------------------------------

    Beside each cost in the cost grid, and below the appropriate heat 
loss value taken from the heat loss table, place the cost estimate for 
the model being labeled using the table costs in place of the national 
average cost and using the heat loss values in place of the design heat 
loss used in the table with the national average cost.

[59 FR 34042, July 1, 1994, as amended at 59 FR 48798, Sept. 23, 1994]

          Appendix G5 to Part 305--Boilers--Gas (Except Steam)

                         [1. Range Information]
------------------------------------------------------------------------
                                      Range of annual fuel utilization
   Manufacturer's rated heating             efficiencies (AFUE's)
      capacities (Btu's/hr.)       -------------------------------------
                                           Low                High
------------------------------------------------------------------------
All Capacities....................                 80               90.6
------------------------------------------------------------------------


                 [2. Yearly Cost Information: Cost Grid]
------------------------------------------------------------------------
                                                        Btu heat loss of
              Cost per kilowatt hour \1\                home (see chart
                                                             below)
------------------------------------------------------------------------
4[cent]..............................................
6[cent]..............................................
8[cent]..............................................
10[cent].............................................
12[cent].............................................
14[cent].............................................
------------------------------------------------------------------------
\1\ For charts on natural gas, oil and propane gas, substitute the
  following cost figures:
a. Cost per therm--10[cent], 20[cent], 30[cent], 40[cent], 50[cent],
  60[cent].
b. Cost per gallon (oil)--76[cent], 79[cent], 82[cent], 85[cent],
  88[cent], 91[cent], 94[cent], 97[cent], $1.00.
c. Cost per gallon (propane)--35[cent], 40[cent], 45[cent], 50[cent],
  55[cent], 60[cent].

    The following table shows the heat loss values (in thousand Btu's/
hr.) to be used in the cost grid:

                                                [Heat Loss Table]
----------------------------------------------------------------------------------------------------------------
                                                                      Design heat loss
 Manufacturers' rated heat output of model to be labeled (Btu's per    of model to be    Heat loss values to be
                               hour)                                   labeled (1,000    used on the grid (1,000
                                                                      Btu's per hour)        Btu's per hour)
----------------------------------------------------------------------------------------------------------------
5,000 to 10,000....................................................                  5                         5
11,000 to 16,000...................................................                 10                     5, 10
17,000 to 25,000...................................................                 15                    10, 15
26,000 to 42,000...................................................                 20                15, 20, 25
43,000 to 59,000...................................................                 30            25, 30, 35, 40
60,000 to 76,000...................................................                 40            35, 40, 45, 50
77,000 to 93,000...................................................                 50            40, 45, 50, 60
94,000 to 110,000..................................................                 60            50, 60, 70, 80
111,000 to 127,000.................................................                 70            60, 70, 80, 90
128,000 to 144,000.................................................                 80           70, 80, 90, 100
145,000 to 161,000.................................................                 90     80, 90, 100, 110, 120
162,000 to 178,000.................................................                100    90, 100, 110, 120, 130
179,000 to 195,000.................................................                110   100, 110, 120, 130, 140
196,000 and over...................................................                130   120, 130, 140, 150, 160
----------------------------------------------------------------------------------------------------------------

    Beside each cost in the cost grid, and below the appropriate heat 
loss value taken from the heat loss table, place the cost estimate for 
the model being labeled using the table costs in place of the national 
average cost and using the heat loss values in place of the design heat 
loss used in the table with the national average cost.

[59 FR 34042, July 1, 1994, as amended at 59 FR 48798, Sept. 23, 1994]

[[Page 283]]

              Appendix G6 to Part 305--Boilers--Gas (Steam)

                         [1. Range Information]
------------------------------------------------------------------------
                                      Range of annual fuel utilization
   Manufacturer's rated heating             efficiencies (AFUE's)
      capacities (Btu's/hr.)       -------------------------------------
                                           Low                High
------------------------------------------------------------------------
All Capacities....................                 75               83.5
------------------------------------------------------------------------


                 [2. Yearly Cost Information: Cost Grid]
------------------------------------------------------------------------
                                                        Btu heat loss of
              Cost per kilowatt hour \1\                home (see chart
                                                             below)
------------------------------------------------------------------------
4[cent]..............................................
6[cent]..............................................
8[cent]..............................................
10[cent].............................................
12[cent].............................................
14[cent].............................................
------------------------------------------------------------------------
\1\ For charts on natural gas, oil and propane gas, substitute the
  following cost figures:
a. Cost per therm--10[cent], 20[cent], 30[cent], 40[cent], 50[cent],
  60[cent].
b. Cost per gallon (oil)--76[cent], 79[cent], 82[cent], 85[cent],
  88[cent], 91[cent], 94[cent],[cent], 97[cent], $1.00.
c. Cost per gallon (propane)--35[cent], 40[cent], 45[cent], 50[cent],
  55[cent], 60[cent].

    The following table shows the heat loss values (in thousand Btu's/
hr.) to be used in the cost grid:

                                                [Heat Loss Table]
----------------------------------------------------------------------------------------------------------------
                                                                      Design heat loss
 Manufacturers' rated heat output of model to be labeled (Btu's per    of model to be    Heat loss values to be
                               hour)                                   labeled (1,000    used on the grid (1,000
                                                                      Btu's per hour)        Btu's per hour)
----------------------------------------------------------------------------------------------------------------
5,000 to 10,000....................................................                  5                         5
11,000 to 16,000...................................................                 10                     5, 10
17,000 to 25,000...................................................                 15                    10, 15
26,000 to 42,000...................................................                 20                15, 20, 25
43,000 to 59,000...................................................                 30            25, 30, 35, 40
60,000 to 76,000...................................................                 40            35, 40, 45, 50
77,000 to 93,000...................................................                 50            40, 45, 50, 60
94,000 to 110,000..................................................                 60            50, 60, 70, 80
111,000 to 127,000.................................................                 70            60, 70, 80, 90
128,000 to 144,000.................................................                 80           70, 80, 90, 100
145,000 to 161,000.................................................                 90     80, 90, 100, 110, 120
162,000 to 178,000.................................................                100    90, 100, 110, 120, 130
179,000 to 195,000.................................................                110   100, 110, 120, 130, 140
196,000 and over...................................................                130   120, 130, 140, 150, 160
----------------------------------------------------------------------------------------------------------------

    Beside each cost in the cost grid, and below the appropriate heat 
loss value taken from the heat loss table, place the cost estimate for 
the model being labeled using the table costs in place of the national 
average cost and using the heat loss values in place of the design heat 
loss used in the table with the national average cost.

[59 FR 34042, July 1, 1994, as amended at 59 FR 48798, Sept. 23, 1994]

                  Appendix G7 to Part 305--Boilers--Oil

                         [1. Range Information]
------------------------------------------------------------------------
                                      Range of annual fuel utilization
   Manufacturer's rated heating             efficiencies (AFUE's)
      capacities (Btu's/hr.)       -------------------------------------
                                           Low                High
------------------------------------------------------------------------
All Capacities....................                 80               88.7
------------------------------------------------------------------------


                 [2. Yearly Cost Information: Cost Grid]
------------------------------------------------------------------------
                                                        Btu heat loss of
              Cost per kilowatt hour \1\                home (see chart
                                                             below)
------------------------------------------------------------------------
4[cent]..............................................
6[cent]..............................................
8[cent]..............................................

[[Page 284]]


10[cent].............................................
12[cent].............................................
14[cent].............................................
------------------------------------------------------------------------
\1\ For charts on natural gas, oil and propane gas, substitute the
  following cost figures:
a. Cost per therm--10[cent], 20[cent], 30[cent], 40[cent], 50[cent],
  60[cent].
b. Cost per gallon (oil)--76[cent], 79[cent], 82[cent], 85[cent],
  88[cent], 91[cent], 94[cent], 97[cent], $1.00.
c. Cost per gallon (propane)--35[cent], 40[cent], 45[cent], 50[cent],
  55[cent], 60[cent].

    The following table shows the heat loss values (in thousand Btu's/
hr.) to be used in the cost grid:

                                                [Heat Loss Table]
----------------------------------------------------------------------------------------------------------------
                                                                      Design heat loss
 Manufacturers' rated heat output of model to be labeled (Btu's per    of model to be    Heat loss values to be
                               hour)                                   labeled (1,000   used on the grid (1,000)
                                                                      Btu's per hour)        Btu's per hour)
----------------------------------------------------------------------------------------------------------------
5,000 to 10,000....................................................                  5                         5
11,000 to 16,000...................................................                 10                     5, 10
17,000 to 25,000...................................................                 15                    10, 15
26,000 to 42,000...................................................                 20                15, 20, 25
43,000 to 59,000...................................................                 30            25, 30, 35, 40
60,000 to 76,000...................................................                 40            35, 40, 45, 50
77,000 to 93,000...................................................                 50            40, 45, 50, 60
94,000 to 110,000..................................................                 60            50, 60, 70, 80
111,000 to 127,000.................................................                 70            60, 70, 80, 90
128,000 to 144,000.................................................                 80           70, 80, 90, 100
145,000 to 161,000.................................................                 90     80, 90, 100, 110, 120
162,000 to 178,000.................................................                100    90, 100, 110, 120, 130
179,000 to 195,000.................................................                110   100, 110, 120, 130, 140
196,000 and over...................................................                130   120, 130, 140, 150, 160
----------------------------------------------------------------------------------------------------------------

    Beside each cost in the cost grid, and below the appropriate heat 
loss value taken from the heat loss table, place the cost estimate for 
the model being labeled using the table costs in place of the national 
average cost and using the heat loss values in place of the design heat 
loss used in the table with the national average cost.

[59 FR 34042, July 1, 1994, as amended at 59 FR 48798, Sept. 23, 1994]

               Appendix G8 to Part 305--Boilers--Electric

                         [1. Range Information]
------------------------------------------------------------------------
                                      Range of annual fuel utilization
   Manufacturer's rated heating             efficiencies (AFUE's)
      capacities (Btu's/hr.)       -------------------------------------
                                           Low                High
------------------------------------------------------------------------
All Capacities....................                100                100
------------------------------------------------------------------------


                 [2. Yearly Cost Information: Cost Grid]
------------------------------------------------------------------------
                                                        Btu heat loss of
              Cost per kilowatt hour \1\                home (see chart
                                                             below)
------------------------------------------------------------------------
4[cent]..............................................
6[cent]..............................................
8[cent]..............................................
10[cent].............................................
12[cent].............................................
14[cent].............................................
------------------------------------------------------------------------
\1\ For charts on natural gas, oil and propane gas, substitute the
  following cost figures:
a. Cost per therm--10[cent], 20[cent], 30[cent], 40[cent], 50[cent],
  60[cent].
b. Cost per gallon (oil)--76[cent], 79[cent], 82[cent], 85[cent],
  88[cent], 91[cent], 94[cent], 97[cent], $1.00.
c. Cost per gallon (propane)--35[cent], 40[cent], 45[cent], 50[cent],
  55[cent], 60[cent].

    The following table shows the heat loss values (in thousand Btu's/
hr.) to be used in the cost grid:

[[Page 285]]



                                                [Heat Loss Table]
----------------------------------------------------------------------------------------------------------------
                                                                      Design heat loss
 Manufacturers' rated heat output of model to be labeled (Btu's per    of model to be    Heat loss values to be
                               hour)                                   labeled (1,000   used on the grid (1,000)
                                                                      Btu's per hour)        Btu's per hour)
----------------------------------------------------------------------------------------------------------------
5,000 to 10,000....................................................                  5                         5
11,000 to 16,000...................................................                 10                     5, 10
17,000 to 25,000...................................................                 15                    10, 15
26,000 to 42,000...................................................                 20                15, 20, 25
43,000 to 59,000...................................................                 30            25, 30, 35, 40
60,000 to 76,000...................................................                 40            35, 40, 45, 50
77,000 to 93,000...................................................                 50            40, 45, 50, 60
94,000 to 110,000..................................................                 60            50, 60, 70, 80
111,000 to 127,000.................................................                 70            60, 70, 80, 90
128,000 to 144,000.................................................                 80           70, 80, 90, 100
145,000 to 161,000.................................................                 90     80, 90, 100, 110, 120
162,000 to 178,000.................................................                100    90, 100, 110, 120, 130
179,000 to 195,000.................................................                110   100, 110, 120, 130, 140
196,000 and over...................................................                130   120, 130, 140, 150, 160
----------------------------------------------------------------------------------------------------------------

    Beside each cost in the cost grid, and below the appropriate heat 
loss value taken from the heat loss table, place the cost estimate for 
the model being labeled using the table costs in place of the national 
average cost and using the heat loss values in place of the design heat 
loss used in the table with the national average cost.

[59 FR 34042, July 1, 1994, as amended at 59 FR 48798, Sept. 23, 1994]

  Appendix H to Part 305--Cooling Performance and Cost for Central Air 
                              Conditioners

                          1. Range Information:
------------------------------------------------------------------------
                                               Range of SEER's
   Manufacturer's rated cooling    -------------------------------------
       capacity (Btu's/hr.)                Low                High
------------------------------------------------------------------------
       Single Package Units

Central Air Conditioners (Cooling                9.70              16.05
 Only): All capacities............
Heat Pumps (Cooling Function): All               9.70              15.60
 capacities.......................

        Split System Units

Central Air Conditioners (Cooling               10.00              17.00
 Only): All capacities............
Heat Pumps (Cooling Function): All              10.00              16.40
 capacities.......................
------------------------------------------------------------------------

                       2. Yearly Cost Information:

    For each model, display three annual operating costs, based on 
8.60[cent] per kilowatt hour, rounded to the nearest $10, corresponding 
to the three building heat gains from the chart below:

------------------------------------------------------------------------
                                    Building heat gain (in 1000's BTU's/
   Manufacturers rated cooling                      hr)
        capacity (BTU/hr)         --------------------------------------

------------------------------------------------------------------------
Up to 9,000......................            3            6            9
9,100 to 15,000..................            9           12           15
15,100 to 21,000.................           15           18           21
21,100 to 27,000.................           21           24           27
27,200 to 33,000.................           27           30           33
33,200 to 39,000.................           33           36           39
39,500 to 45,000.................           39           42           45
45,500 to 51,000.................           45           48           51
51,500 to 57,000.................           51           54           57
57,500 to 63,000.................           57           60           63
63,500 and over..................           63           66           69
------------------------------------------------------------------------

    The values of building heat gain are to be considered cooling 
capacities in the calculation of annual operating cost in accordance 
with 10 CFR 430.22 (m)(1)(i).
    Include the following note on every fact sheet page that lists 
annual operating costs.

    Note: These figures are based on U.S. Government standard tests and 
are for national averages of 1000 cooling load hours and 8.60[cent]/KWH. 
Your cost will vary depending on your local energy rate and how you use 
the product. A method for estimating your cost of operation is given 
[direct user to location].


[[Page 286]]


    The methodology referred to in the note is provided below. This 
information shall be included a least once in all compendiums of fact 
sheets. If separate fact sheets are prepared for individual distribution 
to consumers, this methodology must be provided on or with the unbound 
fact sheets.

                    How To Estimate Your Cooling Cost

    To estimate your actual cost of operation, find your cooling load 
hours from the map, your average annual operating cost from the National 
Average Annual Operating Cost Table, and determine your electrical rate 
in cents per kilowatt hour (KWH) from your electric bill.
[GRAPHIC] [TIFF OMITTED] TR09SE04.007

    Example: If your cooling load hours = 1500, and your electric rate 
is 12.62[cent]/KWH and your listed annual operating cost is $100, then:,
Your estimated cost = $100 x 1,500 / 1,000 x 12.90[cent] / 8.60[cent]
Your estimated cost = $100 x 1.5 x 1.5 = $225
Your estimated cost = $225

[[Page 287]]

[GRAPHIC] [TIFF OMITTED] TC29SE91.014


[[Page 288]]


[GRAPHIC] [TIFF OMITTED] TC29SE91.015


[[Page 289]]



                            National Average Annual Operating Cost Table ($ per year)
----------------------------------------------------------------------------------------------------------------
                                                                      Building Heat Gain (BTU/hour)
                         Model                          --------------------------------------------------------
                                                               27,000             30,000             33,000
----------------------------------------------------------------------------------------------------------------
XXX/C1.................................................               $200               $220               $240
XXX/C2.................................................               $200               $220               $240
XXX/C3.................................................               $190               $210               $230
XXX/C6.................................................               $190               $210               $230
----------------------------------------------------------------------------------------------------------------
 Note: These figures are based on U.S. Goverment standard tests and are for national averages of 1000 cooling
  load hours and 8.60[cent]/KWH. Your cost will vary depending on your local energy rate and how you use the
  product. A method for estimating your cost of operation is provided on page 2 of this fact sheet.

                    How To Estimate Your Cooling Cost

    To estimate your actual cost of operation, find your actual cooling 
load hours from the map, your average annual operating cost from the 
National Average Annual Operating Cost Table, and determine your 
electrical rate in cents per kilowatt hour (KWH) from your electrical 
bill.
[GRAPHIC] [TIFF OMITTED] TR09SE04.007

    Example: If your cooling load hours are 1500, and your electric rate 
is 12.90[cent]/KWH, and your listed annual operating cost is $100, then:
Your estimated cost = $100 x 1,500 / 1,000 x 12.90[cent]/ 8.60[cent]
Your estimated cost = $100 x 1.5 x 1.5 = $225
Your estimated cost = $225

                  (This is page 2 of sample fact sheet)

[53 FR 19729, May 27, 1988, as amended at 54 FR 53318, Dec. 28, 1989; 55 
FR 43093, Oct. 26, 1990; 56 FR 46728, Sept. 16, 1991; 57 FR 44332, Sept. 
25, 1992; 59 FR 34049, July 1, 1994; 59 FR 39951 and 39952, Aug. 5, 
1994; 60 FR 56949, Nov. 13, 1995; 61 FR 48622, Sept. 16, 1996; 62 FR 
44891, Aug. 25, 1997; 63 FR 66431, Dec. 2, 1998; 64 FR 926, Jan. 6, 
1999; 64 FR 71021, Dec. 20, 1999; 65 FR 53166, Sept. 1, 2000; 66 FR 
49531, Sept. 28, 2001; 66 FR 57872, Nov. 19, 2001; 67 FR 58328, Sept. 
16, 2002; 68 FR 47451, Aug. 11, 2003; 69 FR 54560, Sept. 9, 2004]

  Appendix I to Part 305--Heating Performance and Cost for Central Air 
                              Conditioners

                          1. Range Information
------------------------------------------------------------------------
                                                       Range of HSPF's
 Manufacturer's rated heating capacity (Btu's/hr.) ---------------------
                                                       Low        High
------------------------------------------------------------------------
               Single Package Units

Heat Pumps (Heating Function): All capacities.....       6.60       8.20

                Split System Units

Heat Pumps (Heating Function): All capacities.....       6.80      10.20
------------------------------------------------------------------------
The HSPF shall be the Region IV value based on the appropriate average
  design heat loss from the table below.

                   2. Yearly Heating Cost Information:

    For each model, display a regional annual operating cost, based on 
8.60[cent] per kilowatt hour, rounded to the nearest $10, calculated 
according to 10 CFR 430.22(m)(3)(ii) for each region. The heat loss of 
home values given in the chart below are to be considered standardized 
design heating requirements in the calculation of annual operating cost 
in accordance with 10 CFR 430.22(m)(3)(ii).

----------------------------------------------------------------------------------------------------------------
                                                                     Average
                                                                   design heat
                        Capacity                          Region     loss (in   Heat loss of home values used on
                                                                      1000's     the grid (in 1000's Btu's/hr.)
                                                                    Btu's/hr.)
----------------------------------------------------------------------------------------------------------------
Up to 9,000............................................         1           10                             5, 10
                                                                2                                      5, 10, 15
                                                                3                                      5, 10, 15

[[Page 290]]


                                                                4                                     10, 15, 20
                                                                5                                     10, 15, 20
                                                                6                                      5, 10, 15
9,100 to 15,000........................................         1           20                         5, 10, 15
                                                                2                                  5, 10, 15, 20
                                                                3                                 10, 15, 20, 25
                                                                4                             10, 15, 20, 25, 30
                                                                5                             10, 15, 20, 25, 30
                                                                6                                  5, 10, 15, 20
15,100 to 21,000.......................................         1           25                        10, 15, 20
                                                                2                                 10, 15, 20, 25
                                                                3                                 15, 20, 25, 30
                                                                4                         15, 20, 25, 30, 35, 40
                                                                5                         15, 20, 25, 30, 35, 40
                                                                6                         10, 15, 20, 25, 30, 35
21,100 to 27,000.......................................         1           30                    10, 15, 20, 25
                                                                2                                 15, 20, 25, 30
                                                                3                         15, 20, 25, 30, 35, 40
                                                                4                         20, 25, 30, 35, 40, 50
                                                                5                     20, 25, 30, 35, 40, 50, 60
                                                                6                         10, 15, 20, 25, 30, 35
21,100 to 27,000.......................................         1           30                    10, 15, 20, 25
                                                                2                                 15, 20, 25, 30
                                                                3                         15, 20, 25, 30, 35, 40
                                                                4                         20, 25, 30, 35, 40, 50
                                                                5                     20, 25, 30, 35, 40, 50, 60
                                                                6                         15, 20, 25, 30, 35, 40
27,100 to 33,000.......................................         1           35                    15, 20, 25, 30
                                                                2                             20, 25, 30, 35, 40
                                                                3                         20, 25, 30, 35, 40, 50
                                                                4                         25, 30, 35, 40, 50, 60
                                                                5                 25, 30, 35, 40, 50, 60, 70, 80
                                                                6                     20, 25, 30, 35, 40, 50, 60
33,200 to 39,000.......................................         1           50                15, 20, 25, 30, 35
                                                                2                             25, 30, 35, 40, 50
                                                                3                             30, 35, 40, 50, 60
                                                                4                     35, 40, 50, 60, 70, 80, 90
                                                                5                     35, 40, 50, 60, 70, 80, 90
                                                                6                             25, 30, 35, 40, 50
39,500 to 45,000.......................................         1           60                20, 25, 30, 35, 40
                                                                2                         25, 30, 35, 40, 50, 60
                                                                3                             30, 35, 40, 50, 60
                                                                4                    40, 50, 60, 70, 80, 90, 100
                                                                5               40, 50, 60, 70, 80, 90, 100, 110
                                                                6                 25, 30, 35, 40, 50, 60, 70, 80
45,500 to 51,000.......................................         1           70                20, 25, 30, 35, 40
                                                                2                             30, 35, 40, 50, 60
                                                                3                         35, 40, 50, 60, 70, 80
                                                                4                   50, 60, 70, 80, 90, 100, 110
                                                                5                  50, 60, 70, 80, 90, 100, 110,
                                                                                                             130
                                                                6                30, 35, 40, 50, 60, 70, 80, 90,
                                                                                                   100, 110, 130
51,500 to 57,000.......................................         1           70                25, 30, 35, 40, 50
                                                                2                             35, 40, 50, 60, 70
                                                                3                         40, 50, 60, 70, 80, 90
                                                                4                   50, 60, 70, 80, 90, 100, 110
                                                                5                  50, 60, 70, 80, 90, 100 ,110,
                                                                                                             130
                                                                6                35, 40, 50, 60, 70, 80, 90, 100
57,500 to 63,000.......................................         1           80                25, 30, 35, 40, 50
                                                                2                             35, 40, 50, 60, 70
                                                                3                             50, 60, 70, 80, 90
                                                                4                       60, 70, 80, 90, 100, 110
                                                                5                  60, 70, 80, 90, 100, 110, 130
                                                                6                35, 40, 50, 60, 70, 80, 90, 100
63,500 and over........................................         1           90                30, 35, 40, 50, 60
                                                                2                             40, 50, 60, 70, 80
                                                                3                        50, 60, 70, 80, 90, 100
                                                                4                      70, 80, 90, 100, 110, 130
                                                                5                      70, 80, 90, 100, 110, 130
                                                                6                             40, 50, 60, 70, 80
----------------------------------------------------------------------------------------------------------------


[[Page 291]]

    Include the following note on every fact sheet page that lists 
annual operating costs.

    Note: These annual heating costs are based on U.S. Government 
standard tests and on a national average cost of electricity of 
8.60[cent]/KWH. Your cost will vary depending on your local energy rate 
and how you use the product. A method for estimating your cost of 
operation is given [direct user to location].

    The methodology referred to in the note is provided below. This 
information shall be included at least once in all compendiums of fact 
sheets. If separate fact sheets are prepared for individual distribution 
to consumers, this methodology must be provided on or with the unbound 
fact sheets.

                   How To Estimate Your Heating Costs

    To estimate your heating cost, determine your cost of electricity in 
cents per kilowatt hour (KWH) from your electric bill, your listed 
average annual heating cost from the National Average Annual Heating 
Cost Table, and use that number in the following equation:
[GRAPHIC] [TIFF OMITTED] TR09SE04.008

    Example: If your electric rate is 12.90cent;/KWH and the annual 
heating cost listed in the chart is $200:
Your estimated cost = $200 x 12.90[cent]/8.60[cent]
Your estimated cost = $200 x 1.5 = $300
Your estimated cost = $300

[[Page 292]]

[GRAPHIC] [TIFF OMITTED] TC29SE91.016


[[Page 293]]


[GRAPHIC] [TIFF OMITTED] TC29SE91.017

    Note: These annual heating costs are based on U.S. Government 
standard tests and on a national average cost of electricity of 
8.60[cent]/KWH. Your cost will vary depending on your local energy rate 
and how you use the product. A method for estimating your cost of 
operation is given below.

[[Page 294]]

                    How To Estimate Your Heating Cost

    To estimate your heating cost, determine your cost of electricity in 
cents per kilowatt hour (KWH) from your electric bill, your listed 
average annual heating cost from the National Average Annual Heating 
Cost Table, and substitute that number in the following equation:
[GRAPHIC] [TIFF OMITTED] TR09SE04.008

    Example: If your electric cost is 12.90[cent]/KWH and the annual 
heating cost listed in the table is $200:
Your estimated cost = $200 x 12.90[cent]/8.60[cent]
Your estimated cost = $200 x 1.5 = $300
Your estimated cost = $300

                  (This is page 2 of sample fact sheet)

[53 FR 19729, May 27, 1988, as amended at 54 FR 53318, Dec. 28, 1989; 55 
FR 43093, Oct. 26, 1990; 56 FR 46728, Sept. 16, 1991; 57 FR 44332, Sept. 
25, 1992; 59 FR 34051, July 1, 1994; 59 FR 39952, Aug. 5, 1994; 60 FR 
56949, Nov. 13, 1995; 61 FR 48623, Sept. 16, 1996; 62 FR 44891, Aug. 25, 
1997; 64 FR 926, Jan. 6, 1999; 64 FR 71021, Dec. 20, 1999; 65 FR 53166, 
Sept. 1, 2000; 66 FR 49531, Sept. 28, 2001; 66 FR 57872, Nov. 19, 2001; 
67 FR 58328, Sept. 16, 2002; 68 FR 47451, Aug. 11, 2003; 69 FR 54560, 
Sept. 9, 2004]

               Appendix J1 to Part 305--Pool Heaters--Gas

                                                Range Information
----------------------------------------------------------------------------------------------------------------
                                                                   Range of thermal efficiencies  (percent)
                                                             ---------------------------------------------------
           Manufacturer's rated heating capacities                   Natural gas                 Propane
                                                             ---------------------------------------------------
                                                                  Low          High         Low          High
----------------------------------------------------------------------------------------------------------------
All capacities..............................................         78.4         97.0         78.4         97.0
----------------------------------------------------------------------------------------------------------------


[60 FR 43369, Aug. 21, 1995]

               Appendix J2 to Part 305--Pool Heaters--Oil

                            Range Information
------------------------------------------------------------------------
                                                    Range of thermal
                                                 efficiencies  (percent)
    Manufacturer's rated heating capacities    -------------------------
                                                    Low          High
------------------------------------------------------------------------
All capacities................................         78.0         78.0
------------------------------------------------------------------------


[60 FR 43370, Aug. 21, 1995]

         Appendix K to Part 305--Suggested Data Reporting Format

1. Date of Report_______________________________________________________
2. Company Name_________________________________________________________
3. City_________________________________________________________________
4. State________________________________________________________________
5. Product______________________________________________________________
6. Energy Type (gas, oil, etc.)_________________________________________
7. Model Number_________________________________________________________
8. Estimated Annual Energy Consumption or Energy Efficiency Rating______
9. Capacity_____________________________________________________________
10. Number of Tests Performed___________________________________________
11. Total Energy Consumption (based on all tests performed)_____________

[52 FR 49647, Dec. 31, 1987; as amended at 59 FR 34053, July 1, 1994. 
Redesignated at 59 FR 49565, Sept. 28, 1994]

[[Page 295]]

                  Appendix L to Part 305--Sample Labels
[GRAPHIC] [TIFF OMITTED] TR03AP00.000


[[Page 296]]


[GRAPHIC] [TIFF OMITTED] TR18JN03.019


[[Page 297]]


[GRAPHIC] [TIFF OMITTED] TR14JY04.000


[[Page 298]]


[GRAPHIC] [TIFF OMITTED] TR25AU04.004


[[Page 299]]


[GRAPHIC] [TIFF OMITTED] TR03AP00.004


[[Page 300]]


[GRAPHIC] [TIFF OMITTED] TR03AP00.005


[[Page 301]]


[GRAPHIC] [TIFF OMITTED] TR03AP00.006


[[Page 302]]


[GRAPHIC] [TIFF OMITTED] TR18JN03.020


[[Page 303]]


[GRAPHIC] [TIFF OMITTED] TR09SE04.000


[[Page 304]]


[GRAPHIC] [TIFF OMITTED] TR14JY04.001


[[Page 305]]


[GRAPHIC] [TIFF OMITTED] TR03AP00.010


[[Page 306]]


[GRAPHIC] [TIFF OMITTED] TR03AP00.011


[[Page 307]]


[GRAPHIC] [TIFF OMITTED] TR03AP00.012


[[Page 308]]


[GRAPHIC] [TIFF OMITTED] TR03AP00.013


[[Page 309]]


[GRAPHIC] [TIFF OMITTED] TR03AP00.014


[[Page 310]]


[GRAPHIC] [TIFF OMITTED] TR03AP00.015


[[Page 311]]


[GRAPHIC] [TIFF OMITTED] TC29SE91.032


[[Page 312]]


[GRAPHIC] [TIFF OMITTED] TC29SE91.033


[[Page 313]]


[GRAPHIC] [TIFF OMITTED] TC29SE91.034


[[Page 314]]


[GRAPHIC] [TIFF OMITTED] TC29SE91.035


[[Page 315]]


[GRAPHIC] [TIFF OMITTED] TC29SE91.036


[[Page 316]]


[GRAPHIC] [TIFF OMITTED] TC29SE91.037


[59 FR 25212, May 13, 1994; 59 FR 34053, July 1, 1994. Redesignated and 
amended at 59 FR 49565, 49567, Sept. 28, 1994; 65 FR 16142, Mar. 27, 
2000; 65 FR 17564, Apr. 3, 2000; 67 FR 47445, July 19, 2002; 68 FR 
36463, June 18, 2003; 68 FR 47451, Aug. 11, 2003; 68 FR 55821, Sept. 29, 
2003; 69 FR 42110, Oct. 12, 2004; 69 FR 54561, Sept. 9, 2004]

[[Page 317]]