[Code of Federal Regulations]

[Title 30, Volume 1]

[Revised as of July 1, 2006]

From the U.S. Government Printing Office via GPO Access

[CITE: 30CFR18.53]



[Page 111-113]

 

                       TITLE 30--MINERAL RESOURCES

 

  CHAPTER I--MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR

 

PART 18_ELECTRIC MOTOR-DRIVEN MINE EQUIPMENT AND ACCESSORIES--Table of 

Contents

 

             Subpart B_Construction and Design Requirements

 

Sec.  18.53  High-voltage longwall mining systems.



    (a) In each high-voltage motor-starter enclosure, with the exception 

of a controller on a high-voltage shearer, the disconnect device 

compartment, control/communications compartment, and motor contactor 

compartment must be separated by barriers or partitions to prevent 

exposure of personnel to energized high-voltage conductors or parts. In 

each motor-starter enclosure on a high-voltage shearer, the high-voltage 

components must be separated from lower voltage components by barriers 

or partitions to prevent exposure of personnel to energized high-voltage 

conductors or parts. Barriers or partitions must be constructed of 

grounded metal or nonconductive insulating board.

    (b) Each cover of a compartment in the high-voltage motor-starter 

enclosure containing high-voltage components must be equipped with at 

least two interlock switches arranged to automatically deenergize the 

high-voltage components within that compartment when the cover is 

removed.

    (c) Circuit-interrupting devices must be designed and installed to 

prevent automatic reclosure.

    (d) Transformers with high-voltage primary windings that supply 

control voltages must incorporate grounded electrostatic (Faraday) 

shielding between the primary and secondary windings. The shielding must 

be connected to equipment ground by a minimum No. 12 AWG grounding 

conductor. The secondary nominal voltage must not exceed 120 volts, line 

to line.

    (e) Test circuits must be provided for checking the condition of 

ground-wire monitors and ground-fault protection without exposing 

personnel to energized circuits. Each ground-test circuit must inject a 

primary current of 50 percent or less of the current rating of the 

grounding resistor through the current transformer and cause each 

corresponding circuit-interrupting device to open.

    (f) Each motor-starter enclosure, with the exception of a controller 

on a high-voltage shearer, must be equipped with a disconnect device 

installed to deenergize all high-voltage power conductors extending from 

the enclosure when the device is in the ``open'' position.

    (1) When multiple disconnect devices located in the same enclosure 

are used to satisfy the above requirement they must be mechanically 

connected to provide simultaneous operation by one handle.

    (2) The disconnect device must be rated for the maximum phase-to-

phase voltage and the full-load current of the circuit in which it is 

located, and installed so that--

    (i) Visual observation determines that the contacts are open without 

removing any cover;

    (ii) The load-side power conductors are grounded when the device is 

in the ``open'' position;

    (iii) The device can be locked in the ``open'' position;

    (iv) When located in an explosion-proof enclosure, the device must 

be designed and installed to cause the current to be interrupted 

automatically prior to the opening of the contacts; and

    (v) When located in a non-explosion-proof enclosure, the device must 

be designed and installed to cause the current to be interrupted 

automatically prior to the opening of the contacts, or



[[Page 112]]



the device must be capable of interrupting the full-load current of the 

circuit.

    (g) Control circuits for the high-voltage motor starters must be 

interlocked with the disconnect device so that--

    (1) The control circuit can be operated with an auxiliary switch in 

the ``test'' position only when the disconnect device is in the open and 

grounded position; and

    (2) The control circuit can be operated with the auxiliary switch in 

the ``normal'' position only when the disconnect switch is in the closed 

position.

    (h) A study to determine the minimum available fault current must be 

submitted to MSHA to ensure adequate protection for the length and 

conductor size of the longwall motor, shearer and trailing cables.

    (i) Longwall motor and shearer cables with nominal voltages greater 

than 660 volts must be made of a shielded construction with a grounded 

metallic shield around each power conductor.

    (j) High-voltage motor and shearer circuits must be provided with 

instantaneous ground-fault protection of not more than 0.125-amperes. 

Current transformers used for this protection must be of the single-

window type and must be installed to encircle all three phase 

conductors.

    (k) Safeguards against corona must be provided on all 4,160 voltage 

circuits in explosion-proof enclosures.

    (l) The maximum pressure rise within an explosion-proof enclosure 

containing high-voltage switchgear must be limited to 0.83 times the 

design pressure.

    (m) High-voltage electrical components located in high-voltage 

explosion-proof enclosures must not be coplanar with a single plane 

flame-arresting path.

    (n) Rigid insulation between high-voltage terminals (Phase-to-Phase 

or Phase-to-Ground) must be designed with creepage distances in 

accordance with the following table:



                                                               Minimum Creepage Distances

--------------------------------------------------------------------------------------------------------------------------------------------------------

                                                                                     Minimum creepage distances (inches) for comparative tracking index

                                                                                                              (CTI) range \1\

             Phase to phase voltage                     Points of  measure        ----------------------------------------------------------------------

                                                                                   CTI=500    380<=CTI<500     175<=CTI<380       CTI<175

--------------------------------------------------------------------------------------------------------------------------------------------------------

2,400..........................................  0-0                                            1.50              1.95             2.40             2.90

                                                 0-G                                            1.00              1.25             1.55             1.85

4,160..........................................  0-0                                            2.40              3.15             3.90             4.65

                                                 0-G                                            1.50              1.95             2.40            2.90

--------------------------------------------------------------------------------------------------------------------------------------------------------

\1\ Assumes that all insulation is rated for the applied voltage or higher.



    (o) Explosion-proof motor-starter enclosures must be designed to 

establish the minimum free distance (MFD) between the wall or cover of 

the enclosure and uninsulated electrical conductors inside the enclosure 

in accordance with the following table:



                                    High-Voltage Minimum Free Distances (MFD)

----------------------------------------------------------------------------------------------------------------

                                                Steel MFD (in)                       Aluminum MFD (in)

     Wall/cover thickness (in)     -----------------------------------------------------------------------------

                                       A \1\        B \2\        C \3\          A            B            C

----------------------------------------------------------------------------------------------------------------

\1/4\.............................          2.8          4.3          5.8       \4\ NA       \4\ NA       \4\ NA

\3/8\.............................          1.8          2.3          3.9          8.6         12.8         18.1

\1/2\.............................        * 1.2          2.0          2.7          6.5          9.8         13.0

\5/8\.............................        * 0.9          1.5          2.1          5.1          7.7         10.4

\3/4\.............................        * 0.6        * 1.1          1.6          4.1          6.3          8.6

1.................................          (*)        * 0.6        * 1.0          2.9          4.5         6.2

----------------------------------------------------------------------------------------------------------------

Note: * The minimum electrical clearances must still be maintained.

\1\ Column A specifies the MFD for enclosures that have available 3-phase bolted short-circuit currents of

  10,000 amperes rms or less.

\2\ Column B specifies the MFD for enclosures that have a maximum available 3-phase bolted short-circuit

  currents greater than 10,000 and less than or equal to 15,000 amperes rms.

\3\ Column C specifies the MFD for enclosures that have a maximum available 3-phase bolted short-circuit

  currents greater than 15,000 and less than or equal to 20,000 amperes rms.



[[Page 113]]





\4\ Not Applicable--MSHA doesn't allow aluminum wall or covers to be \1/4\ inch or less in thickness (Section

  18.31).



    (1) For values not included in the table, the following formulas on 

which the table is based may be used to determine the minimum free 

distance.

    (i) Steel Wall/Cover:

    [GRAPHIC] [TIFF OMITTED] TR23NO04.000

    

    (ii) Aluminum Wall/Cover:

    [GRAPHIC] [TIFF OMITTED] TR23NO04.001

    

Where C is 1.4 for 2,400 volt systems or 3.0 for 4,160 volt systems, 

Isc is the 3-phase short circuit current in amperes of the 

system, t is the clearing time in seconds of the outby circuit-

interrupting device and d is the thickness in inches of the metal wall/

cover adjacent to an area of potential arcing.



    (2) The minimum free distance must be increased by 1.5 inches for 

4,160 volt systems and 0.7 inches for 2,400 volt systems when the 

adjacent wall area is the top of the enclosure. If a steel shield is 

mounted in conjunction with an aluminum wall or cover, the thickness of 

the steel shield is used to determine the minimum free distances.

    (p) The following static pressure test must be performed on each 

prototype design of explosion-proof enclosures containing high-voltage 

switchgear prior to the explosion tests. The static pressure test must 

also be performed on every explosion-proof enclosure containing high-

voltage switchgear, at the time of manufacture, unless the manufacturer 

uses an MSHA accepted quality assurance procedure covering inspection of 

the enclosure. Procedures must include a detailed check of parts against 

the drawings to determine that the parts and the drawings coincide and 

that the minimum requirements stated in part 18 have been followed with 

respect to materials, dimensions, configuration and workmanship.

    (1) Test procedure. (i) The enclosure must be internally pressurized 

to at least the design pressure, maintaining the pressure for a minimum 

of 10 seconds.

    (ii) Following the pressure hold, the pressure must be removed and 

the pressurizing agent removed from the enclosure.

    (2) Acceptable performance. (i) The enclosure during pressurization 

must not exhibit--

    (A) Leakage through welds or casting; or

    (B) Rupture of any part that affects the explosion-proof integrity 

of the enclosure.

    (ii) The enclosure following removal of the pressurizing agents must 

not exhibit--

    (A) Visible cracks in welds;

    (B) Permanent deformation exceeding 0.040 inches per linear foot; or

    (C) Excessive clearances along flame-arresting paths following 

retightening of fastenings, as necessary.



[67 FR 10999, Mar. 11, 2002; 69 FR 68078, Nov. 23, 2004; 69 FR 70752, 

Dec. 7, 2004]