Sec.  18.42  Explosion-proof distribution boxes.



    (a) A cable passing through an outside wall(s) of a distribution box 

shall be conducted either through a packing gland or an interlocked plug 

and receptacle.

    (b) Short-circuit protection shall be provided for each branch 

circuit connected to a distribution box. The current-carrying capacity 

of the specified connector shall be compatible with the automatic 

circuit-interrupting device.

    (c) Each branch receptacle shall be plainly and permanently marked 

to indicate its current-carrying capacity and each receptacle shall be 

such that it will accommodate only an appropriate plug.

    (d) Provision shall be made to relieve mechanical strain on all 

connectors to distribution boxes.