Sec.  75.801  Grounding resistors.



                         [Statutory Provisions]



    The grounding resistor, where required, shall be of the proper ohmic 

value to limit the voltage drop in the grounding circuit external to the 

resistor to not more than 100 volts under fault conditions. The 

grounding resistor shall be rated for maximum fault current continuously 

and insulated from ground for a voltage equal to the phase-to-phase 

voltage of the system.