[Code of Federal Regulations] [Title 30, Volume 1] [Revised as of July 1, 2006] From the U.S. Government Printing Office via GPO Access [CITE: 30CFR77] [Page 647] TITLE 30--MINERAL RESOURCES CHAPTER I--MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR PART 77_MANDATORY SAFETY STANDARDS, SURFACE COAL MINES AND SURFACE WORK AREAS OF UNDERGROUND COAL MINES--Table of Contents Subpart I_Surface High-Voltage Distribution Sec. 77.803 Fail safe ground check circuits on high-voltage resistance grounded systems. On and after September 30, 1971, all high-voltage, resistance grounded systems shall include a fail safe ground check circuit or other no less effective device approved by the Secretary to monitor continuously the grounding circuit to assure continuity. The fail safe ground check circuit shall cause the circuit breaker to open when either the ground or ground check wire is broken.