May 08, 2008Improper Set-up of Aerial Ladders with a Locking Waterway May Put Fire Fighters at Risk NIOSH recommends that all fire departments utilizing aerial ladder trucks with locking (pin-anchored, lever actuated, clamped) waterways immediately take the following actions to reduce the risk of fire fighters being struck by unsecured waterways or parts of the waterway:
|
|
Circumstances of incident under investigation by NIOSH
On April 8, 2008, a volunteer Deputy Fire Chief (the Incident Commander), was killed when struck by a motorized water monitor and 30 feet of aluminum pipe that was “launched” off an elevated aerial ladder at a fire at an industrial manufacturing plant in Pennsylvania. The truck was normally transported in the “rescue mode” with the monitor pinned to the second section of ladder so that the waterway would not be in the way if the ladder was set up for rescue operations. At the incident scene, when the waterway was pressurized, the monitor and its support bracket, along with the last 30-foot section of pipe were “launched” off the aerial ladder by the force of the water pressure in the pipe. The monitor flew approximately 75 feet and fell, striking the Incident Commander on the head, killing him instantly. After the incident, the anchor pin was found on the ground, in front of the truck’s cab. The waterway did not include any secondary mechanical stops to prevent the separation of the water monitor in the event the anchoring pin was not properly seated. The NIOSH Fire Fighter Fatality Investigation and Prevention Program is currently investigating this incident and a full report will be available at a later date.
NIOSH would like to bring this information to the attention of all U.S. fire departments and fire fighters who operate or work around aerial ladder trucks with locking (pin-anchored, lever actuated, clamped) waterways so that future occurrences of waterway monitor “launches” or the unexpected movement of the waterway monitor can be prevented. If secondary mechanical stops are present, the unexpected impact of the waterway monitor against the mechanical stop could cause structural damage to the aerial ladder and jeopardize the safety of any fire fighter standing on the aerial ladder. While not a contributing factor in the fatal incident, NIOSH reminds fire departments to comply with relevant federal regulations and NFPA standards for fire apparatus inspections and certification.
Photo 2 – Aerial ladder with monitor at tip |
Photo 3 – anchoring pin | |
Photo 4 – Monitor and pipe that “launched” | Photo 5 - The receiver assembly where the pin is inserted |
The NIOSH Fire Fighter Fatality Investigation and Prevention Program is conducted by the National Institute for Occupational Safety and Health (NIOSH). The purpose of the program is to investigate fire fighter line-of-duty-deaths and formulate recommendations for preventing future deaths and injuries. The program does not seek to determine fault or place blame on fire departments or individual fire fighters but to learn from these tragic events and prevent future similar events. For more information, visit the program website at www.cdc.gov/niosh/fire or call 1-800-CDC-INFO. |