U.S. Department of Labor | ||||||
Occupational Safety & Health Administration |
Standard Interpretations
08/26/2003 - Requirements for perimeter columns and perimeter safety cables in the Steel Erection standard. |
Standard Interpretations - Table of Contents |
Standard Number: | 1926.756(e)(1); 1926.756(e); 1926.760(a)(2) |
August 26, 2003 Mr. Troy Russell Safety Director Superior Steel, Inc. 5225 North National Drive Knoxville, Tennessee 37914 Dear Mr. Russell: This is in response to your letter of June 20, 2003, to the Occupational Safety and Health Administration (OSHA) concerning requirements in the steel erection standard regarding perimeter columns and perimeter safety cables. We have paraphrased your question below: Question: Under §1926.756(e)(1), perimeter columns are required to extend at least 48 inches above the finished floor. Do the perimeter columns have to extend beyond the roof level when the building has topped out? Are perimeter safety cables required in this situation under §1926.760(a)(2)? Answer: Section 1926.756(e) states: Perimeter columns shall not be erected unless:The standard requires perimeter columns to extend 48 inches above the finished floor "to permit installation of perimeter safety cables prior to erection of the next tier..." Since there is no "next tier" once the final tier has been erected, the language of the provision indicates that the requirement does not apply to the final tier's columns. Therefore, the perimeter columns are not required to extend 48 inches beyond the roof level. Section 1926.760(a)(2) states: Perimeter safety cables. On multi-story structures, perimeter safety cables shall be installed at the final interior and exterior perimeters of the floors as soon as the metal decking has been installed. [Emphasis added.]This provision applies to the perimeters of "floors," not roofs. Therefore, it does not require perimeter safety cables on the roof level. However, fall protection, whether accomplished by guardrails, nets, personal fall arrest systems, etc., is nonetheless required on the roof level at fall heights over 15 feet (with certain exceptions) pursuant to the requirements of §1926.760(a)(1). If you need additional information, please contact us by fax at: U.S. Department of Labor, OSHA, Directorate of Construction, Office of Construction Standards and Guidance, fax # 202-693-1689. You can also contact us by mail at the above office, Room N3468, 200 Constitution Avenue, N.W., Washington, D.C. 20210, although there will be a delay in our receiving correspondence by mail. Sincerely, Russell B. Swanson, Director Directorate of Construction |
Standard Interpretations - Table of Contents |
Back to Top | www.osha.gov | www.dol.gov |
Contact Us | Freedom of Information Act | Customer Survey Privacy and Security Statement | Disclaimers |
||
Occupational Safety & Health Administration 200 Constitution Avenue, NW Washington, DC 20210 |