30 CFR § 75.703-3
Approved methods of grounding offtrack mobile, portable and stationary direct-current machines.
In grounding offtrack direct-current machines and the enclosures of their
component parts, the following methods of grounding will meet the
requirements of §75.703:
(a) The use of a separate grounding conductor located within the
trailing cable of mobile and portable equipment and connected between such
equipment and the direct-current grounding medium;
(b) The use of a separate ground conductor located within the
direct-current power cable feeding stationary equipment and connected
between such stationary equipment and the direct-current grounding
medium;
(c) The use of a separate external ground conductor connected between
stationary equipment and the direct-current grounding medium; or,
(d) The use of silicon diodes; however, the installation of such
devices shall meet the following minimum requirements:
(1) Installation of silicon diodes shall be restricted to
electric equipment receiving power from a direct-current system with one
polarity grounded;
(2) Where such diodes are used on circuits having a
nominal voltage rating of 250, they must have a forward current rating of 400
amperes or more, and have a peak inverse voltage rating of 400 or more;
(3) Where such diodes are used on circuits having a
nominal voltage rating of 550, they must have a forward current rating of 250
amperes or more, and have a peak inverse voltage rating of 800 or more;
(4) Where fuses approved by the Secretary are used at the
outby end of a trailing cable connected to electrical equipment employing
silicon diodes, the rating of such fuses must not exceed 150 percent of the
nominal current rating of the grounding diodes;
(5) Where circuit breakers are used at the outby end of a
trailing cable connected to electrical equipment employing silicon diodes,
the instantaneous trip setting shall not exceed 300 percent of the nominal
current rating of the grounding diode;
(6) Overcurrent devices must be used and installed in such
a manner that the operating coil circuit of the main contactor will open when
a fault current with a value of 25 percent or less of the diode rating flows
through the diode;
(7) The silicon diode installed must be suitable to the
grounded polarity of the power system in which it is used and its threaded
base must be solidly connected to the machine frame on which it is
installed;
(8) In addition to the grounding diode, a polarizing diode
must be installed in the machine control circuit to prevent operation of the
machine when the polarity of a trailing cable is reversed;
(9) When installed on permissible equipment, all grounding
diodes, overcurrent devices, and polarizing diodes must be placed in
explosion proof compartments;
(10) When grounding diodes are installed on a continuous
miner, their nominal diode current rating must be at least 750 amperes or
more; and,
(11) All grounding diodes shall be tested, examined and
maintained as electrical equipment in accordance with the provisions of
§75.512.