PRIORITY ATTENTION REQUIRED  MORNING REPORT - REGION IV  SEP. 29, 2000

Licensee/Facility:                     Notification:

Arizona Public Service Co.             MR Number: 4-00-0016
Palo Verde 3                           Date: 09/29/00
Wintersburg,Arizona                    FROM SENIOR RESIDENT INSPECTOR     
Dockets: 50-530
PWR/CE80                              

Subject: PLANT SHUTDOWN TO REPAIR SECONDARY LEAK                         

Discussion:

On September 27, 2000, the licensee completed a shutdown of Palo Verde   
Nuclear Generating Station Unit 3, to repair a cracked seal weld on a    
Steam Generator 2 sample line.  The cracked seal weld was on a 3/8-inch  
diameter sample line fitting located inside the containment building. The
crack in the weld resulted in a leak from the secondary system of        
approximately 8 gallons per hour.  The plant is currently in Mode 5 to   
repair the cracked weld.                                                 

Regional Action:

Resident inspectors will continue to monitor licensee followup activities
associated with the plant shutdown.                                      

Contact:  Phil Harrell               (817)860-8250