PRIORITY ATTENTION REQUIRED  MORNING REPORT - HEADQUARTERS AUGUST 10, 2000

Licensee/Facility:                     Notification:

Part 21 Database                       MR Number: H-00-0048
Abb Automation                         Date: 08/10/00
Allentown,Pennsylvania                                                    

Subject: Part 21 - Defective Siemens Output Interface Relays for ABB Type
         27N, 87B, 81, 47H, and 50D Protective Relays                    


Discussion:

VENDOR: ABB Automation                  PT21 FILE NO: mm-18-0            
                                                                         
DATE OF DOCUMENT: 08/02/00              ACCESSION NUMBER:                
                                                                         
SOURCE DOCUMENT: LETTER                 REVIEWER: REXB, D. Skeen         
                                                                         
                                                                         
ABB Automation Incorporated (ABB), located in Allentown, Pennsylvania,   
notified the NRC that a piece part (small double pole, double throw      
output relay) on some of ABB's protective relay assemblies was defective.
The ABB protective relays employ a solid state electronic sensing unit in
combination with an electro-mechanical output relay to provide the       
interface with external control circuitry. The output interface relay    
(part number RTE24048) is made by Siemens. The defect is the epoxy seal  
on the underside of the relay housing. The Siemens relay is intended to  
be a sealed unit, such that when ABB performs the wave soldering and     
washing process during assembly of the protective relay unit, no water is
introduced into the internals of the Siemens relay. However, ABB         
discovered that 19 of 67 relays failed during testing.                   
                                                                         
ABB contacted Siemens and found that there was a problem with the epoxy  
seals on relays with a date code prior to the 10th week of 2000. The     
Siemens relays were manufactured in Austria using a one-step epoxy       
sealant. Two possible failure mechanisms were identified: (1) an         
insufficient amount of epoxy may have been applied, and (2) the          
ultraviolet light method of curing the epoxy may not be effective in     
assuring a complete seal during the wave solder and washing process.     
                                                                         
Water intrusion into the Siemens relay can result in (1) corrosion of the
armature, causing it to stick and hold the normally open contacts in the 
closed position, or (2) the contacts may become corroded and experience  
either intermittent contact or no contact operation.                     
                                                                         
ABB has identified all customers who procured the protective relay units 
as 1E nuclear safety-related equipment. The plants affected are Oyster   
Creek Nuclear Station, Peach Bottom Atomic Power Station, Limerick       
Generating Station, and Perry Nuclear Power Plant. ABB has informed these
customers of the defective Siemens relays and recommended that the ABB   
protective relay units be returned to the Allentown, Pennsylvania        
facility for replacement of the Siemens relays with those of another     
approved manufacturer. In addition, ABB has issued a Product Advisory    
Recall letter to customers who may have received the affected product for
non-safety applications.                                                 
                                                                         