PRIORITY ATTENTION REQUIRED  MORNING REPORT - HEADQUARTERS JANUARY 20, 2000

Licensee/Facility:                     Notification:

Part 21 Database                       MR Number: H-00-0001
Westinghouse                           Date: 01/20/00
                                                                          

Subject: Part 21 - Degraded stock DB-25 circuit breaker                  

Discussion:

VENDOR: Westinghouse                    PT21 FILE NO: 99-44-0            
                                                                         
DATE OF DOCUMENT: 06/18/99              ACCESSION NUMBER: 9908090058     
                                                                         
SOURCE DOCUMENT: LETTER                 REVIEWER: REXB, T. Koshy         
                                                                         
                                                                         
NEW ISSUE. The Ginna licensee reports that a safety-related Westinghouse 
DB-25 breaker mechanism in stock did not pass degradation checks.        
Misaligned drilled holes in the mechanism caused misalignment of the pin 
above the toggle lever. Also, the right rear quarter section of the      
tripper pan is bent upward, resulting in unsatisfactory tripper bar gaps.
                                                                         
NRC contact with the manufacturer confirmed that the assembly would      
continue to operate if the mechanism is positioned geometrically         
compatible with the other pieces because the pin out of level is not one 
of the critical characteristics for the operation. The bent trip pan     
could be the result of handling but the breaker performed properly with  
these deficiencies when tested as a part of incoming inspection.         
_