Morning Report for June 11, 2001

                       Headquarters Daily Report

                         JUNE 11, 2001

***************************************************************************
                    REPORT             NEGATIVE            NO INPUT
                    ATTACHED           INPUT RECEIVED      RECEIVED

HEADQUARTERS        X                                      
REGION I                               X                   
REGION II                              X                   
REGION III                             X                   
REGION IV                              X                   
PRIORITY ATTENTION REQUIRED  MORNING REPORT - HEADQUARTERS JUNE 11, 2001

Licensee/Facility:                     Notification:

Part 21 Database                       MR Number: H-01-0042
Conval                                 Date: 06/11/01
Somers,Connecticut                                                        

Subject: Part 21 - Flow coefficients less than procurement specification 
         for ball check valves                                           


Discussion:

VENDOR: Conval                      PT21 FILE NO: m1-20-0                
                                                                         
DATE OF DOCUMENT: 05/23/01          ACCESSION NUMBER: ML011500422        
                                                                         
SOURCE DOCUMENT: EN 38027           REVIEWER: REXB, V. Hodge             
                                                                         
The valve vendor Conval reports a noncompliance involving flow           
coefficients for ball check valves with the angle pattern or tee pattern 
body style used in charging water riser isolation and scram discharge    
riser isolation applications. The vendor learned from tests that the flow
coefficient values for both styles are less than 1.5, though procurement 
documents specify higher values. In one case, scram time increased from  
1.5 seconds to 2 seconds. The vendor states that it notified both the    
affected domestic nuclear power plants at Oyster Creek and Nine Mile     
Point Unit 1.                                                            
                                                                         
The NRC will post ensuing reports on this subject on its Web site at     
http://www.nrc.gov/NRC/PUBLIC/PART21/2001.                               
                                                                         
Contact:    V. Hodge, NRR                                                
            301-415-1861                                                 
            E-mail: cvh@nrc.gov                                          