![]() |
Search Options | |||
Index | Site Map | FAQ | Facility Info | Reading Rm | New | Help | Glossary | Contact Us | ![]() |
UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF NUCLEAR REACTOR REGULATION
WASHINGTON, D.C. 20555-0001
January 21, 1998
NRC INFORMATION NOTICE 98-03: INADEQUATE VERIFICATION OF OVERCURRENT TRIP SETPOINTS IN METAL-CLAD, LOW-VOLTAGE CIRCUIT BREAKERS
Addressees
All holders of operating licenses for nuclear power reactors.
Purpose
The U.S. Nuclear Regulatory Commission (NRC) is issuing this information notice to alert addressees that inadequate verification of overcurrent trip setpoints for metal-clad, low-voltage circuit breakers may result in the loss of multiple safety functions. It is expected that recipients will review the information for applicability to their facilities and consider actions, as appropriate, to avoid similar problems. However, suggestions contained in this information notice are not NRC requirements; IN 98-03
Description of Circumstances
On September 16, 1996, an Asea Brown Boveri (ABB) Company type K600S 480-Vac circuit breaker prematurely tripped on overcurrent at Centerior Energy Company's Perry Nuclear Power Plant and de-energized a safety-related motor control center (MCC). The circuit breaker's SS-5 solid-state trip device (Power Shield) sensed an overcurrent even though actual MCC current at the time of the trip was well below the Power Shield's expected trip setpoint. Subsequent inspection of the circuit breaker revealed that the leads from one of the three current transformers (CTs) used to sense fault currents were reversed. The reversed CT leads caused the Power Shield's long time overcurrent trip setpoint to shift downwards from 660 amps of primary current to approximately 330 amps and caused the breaker to trip inadvertently on overcurrent.
Discussion
Three-phase solid-state and microprocessor trip units are sensitive to the polarity (or phase) of the signal from the phase sensor CTs. The signal can be effectively shifted 180 out of phase if the CT leads are reversed (or connections between the lower CT terminals and the Power Shield unit terminals are reversed) or if the CT coil is installed upside down. Normally, the signals from the three phase sensor CTs are separated by 120 of phase. However, when a single 180 phase shifted signal from an incorrectly wired or installed CT is combined in the processor with the other two, the sensed peak amplitude of the combined signal can be effectively doubled. In at least one instance, as described above, this condition has caused the solid-state trip unit to actuate at a primary current level significantly below the expected level.
However, such an unexpected phase shift in CT secondary output current is not detected during single-phase primary current calibration and testing. Therefore, additional inspections or tests may be necessary to adequately verify proper operation of circuit breakers equipped with solid-state trip units. ABB's procedure to check phase sensor polarity for solid-state trip devices, Types SS-3, -4, -5, -13, -14, and -15 is as follows:
Normally, this test will confirm that both the wiring and the Phase Sensor CT orientation are correct. However, it should be noted that if both the wiring and the CT orientation on the same pole are reversed, this will also produce a signal of the correct polarity or correct phase relationship to the other two poles, but this is not the preferred condition. The factory uses this test as a troubleshooting procedure, not a substitute for good visual inspection of the assembly. In addition, the test will confirm correct CT winding, internal lead-to-winding connections and cover marking, which would not otherwise be readily apparent if incorrect on new CTs from the CT manufacturing facility.
The circuit breaker that tripped prematurely on overcurrent at Perry was a new circuit breaker supplied by ABB Power T&D Co., Inc. On March 26, 1997, ABB notified the NRC in a 10 CFR Part 21 report that a potential exists for new low-voltage, K-line circuit breakers, equipped with the Power Shield solid-state trip device, to trip well below the device's trip setting if the circuit breaker's overcurrent sensing CTs are incorrectly connected to the Power Shield trip device. Although the circuit breaker that tripped prematurely at Perry was a new circuit breaker, the potential exists for refurbished breakers to have a similar wiring defect. The NRC is aware of instances in which ABB K-line circuit breakers have been sent to ABB service centers for refurbishment, and the service center returned the circuit breakers to the licensee with the CTs incorrectly wired.
A typical metal-clad ABB K-line circuit breaker has six CTs. Three of these six CTs are referred to as "phase sensors," and are used to detect fault currents. The remaining three CTs are referred to as "power sensors," and are used to develop a trip reference signal within the Power Shield trip unit. Two CTs, a phase sensor and a power sensor, are installed on each phase of the circuit breaker. The leads from all six CTs are terminated on three terminal blocks attached to the front of the moulded CT mounting board near the bottom of the circuit breaker. These three terminal blocks, in turn, are connected to the Power Shield solid-state trip unit by a multiconductor wiring harness. Attachment 1 to this notice is a copy of ABB Wiring Diagram 709551, Revision 16, for reference. Attachment 2 to this notice is a photograph of the CT mounting board at the bottom of a K-line breaker to aid in interpreting the drawing. Typical wiring and assembly errors that have been discovered in ABB K-line circuit breakers include the following:
Circuit breaker wiring or assembly errors can be introduced by the original equipment manufacturer, companies performing circuit breaker refurbishment services, or utilities during testing. Incorrectly wired or assembled circuit breakers may be currently in service or stored in a warehouse for service at a later date. Because single-phase calibration testing cannot detect the CT wiring or installation errors described herein, the potential exists for incorrectly wired or assembled circuit breakers to pass normal single-phase calibration testing but to trip load currents less than the desired trip setpoint (e.g., on startup of the breaker's safety-related load during a design-basis accident) resulting in a loss of safety functions.
This information notice establishes no new NRC requirements; therefore, no specific action or written response is required by this notice. However, recipients are reminded that they are required by 10 CFR 50.65 to take industry-wide operating experience (including information presented in NRC information notices) into consideration, where practical, when setting goals and performing periodic evaluations. If you have any questions about the information in this notice, please contact one of the technical contacts listed below or the appropriate NRR project manager.
signed by Dave B. Matthews FOR
Jack W. Roe, Acting Director |
Technical contacts: | Donald Kosloff, RIII 440-259-3610 E-mail: dck@nrc.gov Stephen Alexander, NRR Virgil Beaston, NRR David Skeen, NRR |
Attachments: |