Protecting People and the EnvironmentUNITED STATES NUCLEAR REGULATORY COMMISSION
SSINS No. 6835
IN 82-35
UNITED STATES
NUCLEAR REGULATORY COMMISSION
WASHINGTON, D. C. 20555
August 25, 1982
Information Notice No. 82-35: FAILURE OF THREE CHECK VALVES ON HIGH
PRESSURE INJECTION LINES TO PASS FLOW
Addressee:
All nuclear power reactors With an operating license or construction permit.
Purpose:
This information notice is provided as notification of an event that may
have safety significance. It is expected that recipients will review the
information for applicability to their facilities. No specific action or
response is required.
Description of Circumstances:
At Davis-Besse Unit 1 on June 4, 1982, a stop check valve (HP-57) in the
normal makeup system failed to pass flow although 120 psid was applied
across the valve. Normal opening pressure is about 5 psid. The problem was
discovered while filling the reactor coolant system (RCS) using a small
low-head pump following a refueling and maintenance outage. Normal makeup at
Davis-Besse is via one of the four 2 1/2-inch high-pressure injection (HPI)
lines. Upon further investigation, HPI valves HP-48 and HP-56 also failed to
pass flow at 120 psid. Each HPI line has a stop check valve and a swing
check valve in series (see Figure 1 for HPI system diagram).
The stop check valves are manufactured by Velan. Similar valves may be used
in safety related systems at other plants (an exact listing of affected
plants is not yet available). According to the manufacturer, all Velan 2
1/2-inch stop check valves are of the same basic design. The internals
consist of a disc which is lightly spring loaded against the valve seat. The
disc opens to allow flow at pressures sufficient to overcome spring tension.
A valve stem, which is not connected to the disc, can be turned down on the
disc via a handwheel to block it against the seat. In this mode, the valve
provides an isolating function in addition to preventing backflow (see
Figure 2 for valve internals diagram).
Upon detection of the initial failure, special testing was performed in
order to determine the status of the four HPI stop check valves. A portable
hydropump was used to find the differential pressures at which the valves
would lift open. The testing yielded the following results:
1. Valve HP-57 required 580 psid to open. Since the valve is in the normal
makeup path, however, its operability was not in question before the
outage.
2. Valve HP-48 required 180 psid to open. Its operability is uncertain
since the last pass flow surveillance tests were conducted on the
valves on September 17, 1980.
8204210414
.
IN 82-35
August 25, 1982
Page 2 of 5
.
IN 82-35
August 25, 19
Page 3 of 5
.
IN 82-35
August 25, 1982
Page 4 of 5
3. Valve HP-56 did not pass flow with up to 120 psid pressure. Its
operability since the last surveillance test is also in question.
Additional differential pressure had not been used to open the valve so
as to inspect the closed valve internals and determine the failure
mechanism. No damage to the seat, disc, or valve body was detected upon
visual inspection of internals.
4. Valve HP-49 opened with less than 5 psid, as designed; thus, it was
determined to be functional prior to the refueling outage.
5. All valves were tested by applying up to 150 ft-lbs of torque to the
stems and observing the differential pressure required to open them
after the stem was raised. Only a valve HP-56 continued to bind, even
with as low as 25 ft-lbs of torque applied to the stem. According to
these tests, it has been calculated that RCS back pressure, while in
the operating mode, would have caused HP-56 to bind.
The causes for valve failure are thought to be a combination of overtorquing
by operators and a steep valve seat angle. Wear may have also been a
contributing factor; however, no obvious signs of wear have been detected by
visual inspection. Before the failures, surveillance testing of the HPI
system was performed, and all the valves opened properly. Then the operators
manually closed the stop check valves to isolate the HPI system from the
RCS. Normally the motor-operated valves (MOVs) located outside containment
are used for HPI isolation.
Because the stem packing of the valves was so tight, the operators used a 1
1/2-foot valve wrench rather than the handwheel to close the valves. The
valve manufacturer recommends that no more than 150 ft-lbs of torque be used
to close the valve. With the valve wrench the operator could have easily
overtorqued the valve. Later, the stop check valve stems were returned to
the open position to allow refilling the RCS. At this point it was found
that HP-57 failed to pass forward flow when makeup was being provided by a
small booster pump rather than by the normal charging pump. If the normal
charging pump had been used to refill RCS, the binding valve would not have
been detected because the high pressure would have opened the valve. HP-48
and HP-56 also failed to pass flow except with large differential pressures.
The manual closure of the valves resulted in the failure of the valves to
open, although the earlier pass flow test have demonstrated operability.
In addition to overtorquing the valves, a steep seat angle of 15 could
have contributed,to the valves binding. Valves HP-57, HP-56 and HP-48 had
seat angles of 15 and valve HP-49 had a seat angle of 30. This is
because HP-49 was a later replacement valve and the manufacturer changed
seat angle specifications after three original valves were installed. The
licensee has since replaced the plugs and relapped the seats for the other
three valves to help prevent binding.
.
IN 82-35
August 25, 1982
Page 5 of 5
If you have any questions regarding this matter, please contact the Regional
Administrator of the appropriate Regional Office, or this office.
Edward L. Jordan, Director
Division of Engineering and
Quality Assurance
Office of Inspection and Enforcement
Technical Contact: George Lanik, IE
(301) 49-29636
Attachment:
1. List of Recently Issued Information Notices