IE INFORMATION NO. 82-23: MAIN STEAM ISOLATION VALVE (MSIV) LEAKAGE
Addressees:
All boiling water power reactor facilities holding an operating license or a
construction permit.
Purpose:
This information notice is provided as notification of events that may have
safety significance. It is expected that recipients will review the
information for applicability to their facilities; however, no specific
action or response is required at this time.
Description of Circumstances:
IE has completed a survey of MSIV performance at BWRs for the years 1979
through 1981. IE found that 19 of 25 operating BWRs had MSIVs which failed
to meet, during one or more surveillance tests, the limiting condition for
operation (LCO) which specifies the maximum permissible leak rate. The
number of MSIV test failures exceeded 151 and occurred with MSIVs supplied
by all three MSIV vendors, i.e., Atwood & Morrill, Crane, and Rockwell.
Measured leak rates which exceeded the LCO ranged from greater than 11.5
standard cubic feet per hour (scfh) to 3427 scfh. Twelve stations had 57
MSIV tests with results greater than 11.5 scfh and less than 100 scfh, and
five stations (nine units) had 66 MSIV tests with results between 100 and
3500 scfh. Four other licensees had more than 24 test failures but did not
measure, estimate, or report the magnitudes of the leak rates. These results
are summarized in Attachment (1) and are shown in detail in Attachment (2).
This information indicates that some MSIVs may not adequately limit release
of radioactivity to the environment if called upon to do so. NRC is
considering the need for improved MSIV maintenance, more frequent MSIV
testing or installation of leakage control systems.
8204210393
.
IN 82-23
July 16, 1982
Page 2 of 2
If you have any questions regarding this matter, please contact the Regional
Administrator of the appropriate NRC Regional Office, or this office.
Edward L. Jordan, Director
Division of Engineering and
Quality Assurance
Office of Inspection and Enforcement
Technical Contact: R. W. Woodruff
49-24507
Attachments:
1. Distribution of MSIV Test Failures
2. Adverse MSIV Test ResUlts for 1979 - 1981
3. List of Recently Issued IE Information Notices