Protecting People and the EnvironmentUNITED STATES NUCLEAR REGULATORY COMMISSION
UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF NUCLEAR REACTOR REGULATION
WASHINGTON, D.C. 20555
March 13, 1991
Information Notice No. 90-43, SUPPLEMENT 1: MECHANICAL INTERFERENCE
WITH THERMAL TRIP FUNCTION
IN GE MOLDED-CASE CIRCUIT
BREAKERS
Addressees:
All holders of operating licenses or construction permits for nuclear power
reactors.
Purpose:
This supplement is intended to alert addressees to new information received
from the General Electric Co. (GE) regarding the problem identified in NRC
Information Notice (IN) 90-43, "Mechanical Interference With Thermal Trip
Function in GE Molded-Case Circuit Breakers." The new information could
potentially expand the scope of the problem and limits the conclusiveness of
the previously identified screening test. It is expected that recipients
will review the information for applicability to their facilities and
consider actions, as appropriate, to avoid similar problems. However,
suggestions contained in this supplement do not constitute NRC requirements;
therefore, no specific action or written response is required.
Background:
IN 90-43 addressed a manufacturing deviation in GE types TED and THED,
3-pole, molded-case circuit breakers that has caused failures of the thermal
overcurrent trip function on pole C of those breakers when they are equipped
with undervoltage release devices (UVRs). The manufacturer, GE Electrical
Distribution and Control (ED&C), determined that the cause of the failures
was improper installation (misorientation) of the calibration screw spring
clips on the thermal trip elements of the breakers at the factory. The
misoriented spring clips caused mechanical interference between C-pole
thermal trip elements and installed UVRs. UVR testing did not detect this
condition because misoriented spring clips interfere only with thermal
overcurrent trip operation and not with the operation of the UVR. In
addition, overcurrent trip testing was not being done after UVR
installation.
Description of Circumstances:
Since the issuance of IN 90-43, GE ED&C instituted overcurrent trip testing
of breakers following installation of internal accessory devices (including
UVRs) at its accessory installation facility. Subsequently, GE Nuclear
Energy (GENE) informed the NRC that successful testing of the thermal
overcurrent trip function of a UVR-equipped breaker with misoriented spring
clips does not guarantee
9103060369
.
IN 90-43, Supplement 1
March 13, 1991
Page 2 of 3
that the breaker will not fail subsequently on its C-pole. GENE also
reported that the population of breakers that could have the misoriented
spring clips was much greater than previously believed.
Discussion:
IN 90-43 discussed ED&C examination and testing of UVR-equipped, types TED
and THED breakers that had failed pre-installation testing at the Oyster
Creek Nuclear Generating Station. This testing of specimens from a 1989
GENE shipment to Oyster Creek implicated the misoriented spring clips.
Subsequently, Oyster Creek returned the rest of the shipment to ED&C for
testing and repair. ED&C determined that the shipment was part of a large
population of breakers believed to contain misoriented spring clips. After
testing all the breakers, ED&C repaired the failed breakers and returned to
Oyster Creek those that passed the trip test without repairing them (i.e.,
without repositioning the spring clips). However, in November 1990, GENE
informed the NRC that when Oyster Creek retested the unrepaired breakers,
some failed the same tests that they had reportedly passed at ED&C.
ED&C postulated that the unrepaired breakers (i.e., those that had passed
the ED&C testing) failed at Oyster Creek because of tight clearances and
minor shifts in component positions during handling. This combination may
have created an interference condition that was not present previously.
Nevertheless, these test failures on breakers that previously passed
indicate that as long as the breakers still contain misoriented spring
clips, they are prone to failure on the C-pole if UVRs are installed.
Therefore, passing a thermal overcurrent trip test is no longer considered
conclusive for UVR-equipped breakers of the affected types with respect to
the absence of a potential interference condition.
As noted in IN 90-43, GE ED&C has stated that the problem is limited because
the misoriented spring clips can affect only the thermal overcurrent trip
function on the C-pole of UVR-equipped, 3-pole, types TED and THED breakers.
The thermal trips on poles A and B and the instantaneous magnetic trips on
all three poles remain unaffected. Although GE concluded that misoriented
spring clips could only prevent a UVR-equipped breaker from tripping on a
low-level overload solely on phase C, the combined current from multiple
single phase loads connected to phase C (particularly if in excess of the
design load factor) is one condition that could conceivably produce such a
single phase overload.
The NRC recently learned that Oyster Creek has taken effective corrective
action by sending all the UVR-equipped, types TED and THED, molded-case
circuit breakers in question back to the manufacturer, GE ED&C, where they
were all checked for misoriented spring clips and repaired as necessary.
.
IN 90-43, Supplement 1
March 13, 1991
Page 3 of 3
This information notice supplement requires no specific action or written
response. If you have any questions about the information in this
supplement, please contact the technical contact listed below or the
appropriate NRR project manager.
Charles E. Rossi, Director
Division of Operational Events Assessment
Office of Nuclear Reactor Regulation
Technical Contact: S. Alexander, NRR
(301) 492-0995
Attachment: List of Recently Issued NRC Information Notices
.ENDEND