Protecting People and the EnvironmentUNITED STATES NUCLEAR REGULATORY COMMISSION
UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF NUCLEAR REACTOR REGULATION
WASHINGTON, D.C. 20555
April 17, 1992
NRC INFORMATION NOTICE 92-29: POTENTIAL BREAKER MISCOORDINATION CAUSED BY
INSTANTANEOUS TRIP CIRCUITRY
Addressees
All holders of operating licenses or construction permits for nuclear power
reactors.
Purpose
The U.S. Nuclear Regulatory Commission (NRC) is issuing this information
notice to alert addressees to potential breaker miscoordination involving
instantaneous trip circuitry installed by the manufacturer in certain solid
state trip units. It is expected that recipients will review the
information for applicability to their facilities and consider actions, as
appropriate, to avoid similar problems. However, suggestions contained in
this information notice are not NRC requirements; therefore, no specific
action or written response is required.
Description of Circumstances
On November 6, 1991, personnel at the Sequoyah Nuclear Plant (Sequoyah)
calibrated a solid state trip unit in a 480 Volt power circuit breaker. The
licensee had recently revised the procedure used for the calibration and had
increased the test current required for measuring the response time of the
short time delay trip element from 10 to 13.5 times the rating of the
current sensor. When plant personnel applied the test current, the current
caused the breaker to trip instantly rather than after the expected short
time delay. The instantaneous trip indicated that breaker miscoordination
existed between the 480 Volt power circuit breaker and any downstream load
breaker.
Discussion
The trip unit was an "Amptector Solid State Trip Device" (Amptector) which
was installed in a type DS power circuit breaker. Both the circuit breaker
and the trip unit were manufactured by the Westinghouse Electric Corporation
(Westinghouse). The licensee knew that the trip unit was equipped with a
long and a short time delay element. However, the licensee did not know
that the Amptector trip unit included a circuit which provided an
instantaneous trip feature. After the unexpected instantaneous trip, the
licensee reviewed the vendor's manual, "Westinghouse Instructions for
Low-Voltage Power Circuit Breakers Types DS and DSL." In Section 8.3 of the
manual the licensee found that Westinghouse had included a "making current
release" feature in certain models of Amptector trip units not equipped with
an instantaneous trip element. The manual
9204100124
.
IN 92-29
April 17, 1992
Page 2 of 3
referred to this feature as a "Discriminator." The Discriminator is a
circuit in the trip unit which determines at the time of a fault whether or
not there was any current flow in the primary circuit previous to the fault.
The trip unit would trip instantaneously if (1) there was "no measurable
current" flow previous to the fault, indicating that the circuit is just
being closed or that another switching device upstream of the breaker has
been closed, and (2) the current in the primary circuit exceeded
approximately 12 times the sensor's rating. Otherwise, the short time delay
element would function to delay the breaker tripping. Westinghouse stated
that, in the event of a fault, this feature allowed the breaker to provide
selectivity and continuity in unfaulted sections of a system so that service
to those sections could be maintained but if there was no previously
operating load in the faulted circuit the trip unit would function
instantaneously to limit damage.
Based on the information found in Section 8.3, the licensee determined that
the instantaneous trip that occurred during calibration of the above circuit
breaker resulted from the Discriminator circuit sensing that there was no
measurable current flow previous to the test and that the test current was
greater than 12 times the sensor's rating. Previous calibrations of similar
circuit breakers had not resulted in instantaneous trips because the test
current was less than 12 times the sensor's rating. The licensee noted
that, for the Discriminator feature, "no measurable current" is current flow
that is less than approximately 10 percent of the sensor's rating.
The licensee determined that the Discriminator feature could cause breaker
miscoordination in other electrical systems. This problem could occur in
those systems in which a motor control center (MCC) serves both
safety-related and nonsafety-related loads and current flow in the
nonsafety-related portion of the circuit could be less than 10 percent of
the sensor's rating. In these circuits, a fault on a nonsafety-related
portion of the circuit could cause the safety-related MCC to become
deenergized and result in the loss of the safety-related loads.
After consulting with Westinghouse, the licensee issued a design change to
disable the Discriminator feature on 41 circuit breakers. Westinghouse
stated that its DS type circuit breakers receive interrupting tests with the
short and long time delay elements only (i.e. no instantaneous element) and
disabling the Discriminator feature would not affect the interrupting
ratings of the breakers. However, Westinghouse also indicated that
disabling the Discriminator feature could increase the potential for
equipment damage and personnel injury in downstream portions of the circuit.
Westinghouse informed the licensee that the Discriminator circuit had been a
part of the Amptector trip unit since its first installation in DS type
circuit breakers. However, Westinghouse did not address the Discriminator
feature in the vendor's manual from the time of the manual's original issue
in January 1971 until Revision C was issued in August 1976.
Licensees may have designed circuits without considering the effect of the
Discriminator feature on breaker coordination because this feature was not
.
IN 92-29
April 17, 1992
Page 3 of 3
addressed in early revisions of the vendor's manual and because testing of
the time delay elements with current less than approximately 12 times the
sensor's rating may not reveal the presence of the Discriminator circuit.
The staff previously discussed the importance of proper breaker coordination
in NRC Information Notice 88-45, "Problems In Protective Relay and Circuit
Breaker Coordination," July 7, 1988.
This information notice requires no specific action or written response. If
you have any questions about the information in this notice, please contact
one of the technical contacts listed below or the appropriate Office of
Nuclear Reactor Regulation (NRR) project manager.
Charles E. Rossi, Director
Division of Operational Events Assessment
Office of Nuclear Reactor Regulation
Technical contacts: Paul J. Fillion, RII
(404) 331-7288
Joseph Birmingham, NRR
(301) 504-2829
Attachment: List of Recently Issued NRC Information Notices
.