Information Notice No. 80-21
ANCHORAGE AND SUPPORT OF SAFETY-RELATED ELECTRICAL EQUIPMENT
Description of Circumstances:
Seismic design evaluations in connection with the NRC Systematic Evaluation
Program (SEP) have indicated a potential safety deficiency in the anchorage
and support of safety-related electrical equipment. This subject was
highlighted for more in-depth evaluation after site visits to several
facilities. The site reviews indicated that equipment was supported in a
non-uniform manner. In some cases, design modifications were required to
render acceptable seismic design margins. The deficiencies in anchorage and
support may be due to the fact that earlier engineering design criteria did
not require rigorous analyses.
Letters were issued in January 1980 to the SEP plants which requested a
review of the anchorage of safety-related electrical equipment. The findings
from the reviews at Haddam Neck, Big Rock Point, Dresden 2, Oyster Creek,
and Palisades identified various safety-related electrical equipment that
did not have positive anchorage. The reviews at other SEP plants are
continuing. A summary is provided below of those items so far identified.
Station Service Transformers Motor Control Centers
(4160 V - 480V) Cable Trays
DC to AC Inverters Computer
Emergency Diesel Generator Control Panels - MG Set
Room Heater - Air Compressor
Batteries - Emergency Diesel - Control Room
Generator Instrument Rack
- Diesel Fire Pump Battery Room Main Breaker and
- Station Distribution Panel
Station Battery Rack
A related item has been identified at Comanche Peak (under construction) in
which the welds to the floor supports for the main control panels were found
to be undersized and improperly spaced. Also, the SEP reviewers observed
that non-seismic Category I ancillary items (dolleys, gas bottles, block and
tackle gear, ductwork, etc.) may be located such that they could potentially
dislodge, impact, and damage safety related equipment during an earthquake.
The type of anchorage systems utilized in the SEP plants and their expected
capacities vary widely. For example, high uncertainty exists relative to the
capacity of non-engineered tack welds and attachments that rely on
frictional clamping forces. In some cases, equipment has been found free
standing with no means of positive lateral support. (Friction being the only
lateral load
.
Information Notice No. 80-21 May 16, 1980
Page 2 of 2
carrying mechanism). Most often, heavier equipment is anchored using (1)
tack welds to steel angles embedded in concrete; (2) clips that rely on
frictional resistance; (3) concrete embedded anchor bolts; or (4) external
braced frames. Lighter equipment housed in cabinets or attached to panels
or racks has been anchored using (1) bolts; (2) sheet metal screws; (3) tack
welds; and (4) braced racks.
The potential concern is that certain pieces of equipment may not have
adequate levels of seismic resistance capability due to limited anchorage
capacity. The potential problems relate to overturning and/or sliding of
large equipment and gross movement or unacceptable forces on smaller
attached equipment that may render it inoperable during an earthquake. For
certain large battery racks, this judgment is supported by analysis that
predict unacceptable seismic behavior.
Section 3.10 of the Standard Review Plan provides acceptance criteria for
the seismic qualification of Category I electrical equipment. These criteria
include IEEE Std. 344, "Guide for Seismic Qualification of Class 1E
Electrical Equipment for Nuclear Power Generating Stations", first issued in
1971. Facilities designed before about 1971 without benefit of such design
and testing criteria may have some anchorage deficiencies.
The NRC staff is continuing to evaluate this issue on the SEP plants as part
of the seismic review in the SEP. Remedial actions have been planned for the
affected plants.
This Information Notice is provided as notification of a possibly
significant matter. It is expected that recipients will review the
information for possible applicability to their facilities. No specific
action or response is requested at this time. If NRC evaluations so
indicate, additional actions may be requested or required. If you have any
questions regarding this matter, please contact the Director of the
appropriate NRC Regional Office.