Protecting People and the EnvironmentUNITED STATES NUCLEAR REGULATORY COMMISSION
UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF NUCLEAR REACTOR REGULATION
WASHINGTON, D.C. 20555
December 30, 1988
Information Notice No. 88-46, SUPPLEMENT 2: LICENSEE REPORT OF DEFECTIVE
REFURBISHED CIRCUIT BREAKERS
Addressees:
All holders of operating licenses or construction permits for nuclear power
reactors.
Purpose:
This information notice supplement is being provided to present additional
information regarding the supply of surplus or refurbished electrical equip-
ment such as circuit breakers (CBs) to nuclear power plants as discussed in
NRC Information Notice (IN) No. 88-46 including Supplement 1. It is expected
that recipients will review this information for applicability to their faci-
lities. However, suggestions contained in this information notice do not
constitute NRC requirements; therefore, no specific action or written response
is required.
Description of Circumstances:
Information Notice No. 88-46 discussed a report by Pacific Gas and Electric
(PG&E) that defective refurbished CBs were supplied to PG&E's Diablo Canyon
Nuclear Power Plant by a California electrical supplier. Supplement No. 1 to
IN 88-46 provided a list of shipments of circuit breakers to nuclear power
plants or nuclear utilities by five California companies that may have
supplied defective refurbished electrical equipment.
The NRC has conducted followup inspections and investigations at selected CB
distributors and at companies suspected of selling used or refurbished circuit
breakers. Additionally, nuclear utility sales information related to poten-
tially refurbished CBs has been voluntarily provided to the NRC by
distributors of electrical equipment. This information is summarized in
Attachment 1. Sev-eral utilities identified in the Attachment have already
been contacted by the NRC concerning specific licensee procurements and
disposition of the equipment involved.
The NRC staff does not have any specific information on the condition of the
equipment provided by these companies; however, the activities observed at
some of the companies visited by the NRC were not considered sufficient to
assure breaker functionality and quality.
8812280051
. IN 88-46, Supplement 2
December 30, 1988
Page 2 of 2
No specific action or written response is required by this information notice.
If you have any questions about this matter, please contact one of the
technical contacts listed below or the Regional Administrator of the
appropriate regional office.
Charles E. Rossi, Director
Division of Operational Events Assessment
Office of Nuclear Reactor Regulation
Technical Contacts: J. B. Jacobson, NRR
(301) 492-0996
K. R. Naidu, NRR
(301) 492-0980
Attachments: 1. Shipments of Circuit Breakers to Nuclear
Power Plants or Nuclear Utilities
2. List of Recently Issued NRC Information Notices
. Attachment 2
IN 88-46, Supplement 2
December 30, 1988
Page 1 of 1
LIST OF RECENTLY ISSUED
NRC INFORMATION NOTICES
_____________________________________________________________________________
Information Date of
Notice No._____Subject_______________________Issuance_______Issued to________
88-101 Shipment of Contaminated 12/28/88 All holders of OLs
Equipment between Nuclear or CPs for nuclear
Power Stations power reactors.
88-100 Memorandum of Understanding 12/23/88 All major nuclear
between NRC and OSHA materials
Relating to NRC-licensed licensees and
Facilities (53 FR 43950, utilities holding
October 31, 1988) CPs and OLs.
88-99 Detection and Monitoring 12/20/88 All holders of OLs
of Sudden and/or Rapidly or CPs for PWRs.
Increasing Primary-to-
Secondary Leakage
88-98 Electrical Relay Degradation 12/19/88 All holders of OLs
Caused by Oxidation of or CPs for nuclear
Contact Surfaces power reactors.
88-97 Potentially Substandard 12/16/88 All holders of OLs
Valve Replacement Parts or CPs for nuclear
power reactors.
88-96 Electrical Shock Fatalities 12/14/88 All holders of OLs
at Nuclear Power Plants or CPs for nuclear
power reactors.
88-95 Inadequate Procurement 12/8/88 All holders of OLs
Requirements Imposed by or CPs for nuclear
Licensees on Vendors power reactors.
88-94 Potentially Undersized 12/2/88 All holders of OLs
Valve Actuators or CPs for nuclear
power reactors.
88-93 Teletherapy Events 12/2/88 All NRC medical
licensees.
88-92 Potential for Spent Fuel 11/22/88 All holders of OLs
Pool Draindown or CPs for nuclear
power reactors.
_____________________________________________________________________________
OL = Operating License
CP = Construction Permit
.
.